2006-12-20 11:05:35 | BUILDING REVIEWSECOND CHECKLIST: |
| |
| ***NOTE: THE FOLLOWING ITMES FROM FIRST CHECKLIST WERE |
| NOT ADDRESSED: |
| |
| 1-STOREFRONT PRODUCT APPROVAL IS FOR STRAIGHT AND |
| CONTINUOUS STOREFRONT SYSTEM. PROPOSED STOREFRONT IS |
| ANGLED TO 141 DEGREES. PROVIDE PRODUCT APPROVAL THAT |
| INCLUDES PROPOSED INSTALLATION ORPROVIDE COMPLETE |
| ENGINEERINGANALYSIS FOR STRUCTURAL MULLION TO RECEIVE |
| STOREFRONT AT ANGLED SIDES. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004 AND SECTION 1609 FBC 2004. |
| |
| ***ENGINEER DIDN'T ADDRESSED THIS ISSUE.DRAWINGS |
| DON'T SHOW ANY SPECIFICATIONS AND DETAILS FOR |
| INSTALLATION OF STRUCTURAL MULLIONS AT ANGLED |
| STOREFRONT AND AT LEFT HAND CORNER OF DRAWING 1/P1. |
| DETAILS 1/ D3, 2/D3 AND 3/D3 DON'T PROVIDE ANY |
| SPECIFICATIONS FOR ANGLED MULLION AND CORNER MULLION. |
| PROVIDE ALL INFORMATION AS REQUIRED.SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 2- SPECIFY CALCULATED DESIGN PRESSURES REQUIRED FOR THE |
| STOREFRONT. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| AND SEC. 1609 FBC 2004. |
| |
| *** ENGINEER DIDN'T ADDRESSED THIS ISSUE. PROVIDE ALL |
| DESIGN INFORMATION REQUIRED BY SEC. 1603.1.4 FBC 2004. |
| INCLUDING BUILDING CODE USED. |
| |
| 3- DESIGNER OF RECORD TO REVIEW AND APPROVEIN |
| WRITTING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| ***NO DONE. ENGINEER NEEDS TO REVIEW AND APPROVE IN |
| WRITING ALL PRODUCT APPROVALS. THIS IS TO BE DONE ON |
| THE PRODUCT APPROVALS, NOT ON THE ENGINEERED DRAWINGS |
| AS IT WAS DONE. THE ENGINEERED DRAWINGS ARE THE |
| ENGINEER'S DESIGN, NOT REVIEWD DRAWINGS. |
| |
| 4- DESIGNER OF RECORD TO SIGN AND PROVIDE ALL HIS |
| INFORMATION IN ALL DRAWINGS AS REQUIRED BYSEC. 106.1 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| *** ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATIONIN |
| ALL DRAWINGS AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE |
| SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTES. |
| |
| 5- NEED PRODUCT APPROVAL FOR SIZE OF DOORS AS SPECIFIED |
| ON DRAWINGS. PRODUCT APPROVAL SUBMITTED DOESN'T COVER |
| SIZE SPECIFIED ON DRAWINGS E1 AND E2.. |
| |
| ***NO DONE. |
| |
| 6-SIZE OF STOREFRONT PANELSHOWNON DRAWING 2/E2 IS |
| BIGGER THAN SIZESCOVERED IN THE STOREFRONT PRODUCT |
| APPROVAL. REVISE AS REQUIRED. |
| |
| ***NO DONE. NEED PRODUCT APPROVAL FOR STOREFRONT PANEL |
| SIZE SHOWN ON DETAILS 2/E2, 4/E1,1/E1, AND 4/E1. |
| |
| |
| 7-UPDATESTATE AND COUNTY LICENSESWITH PERMIT |
| CLERK. |
| |
| ***NO DONE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |