2007-02-12 11:04:58 | MECHANICAL REVISION TO PLANS. |
| *** DENIED *** |
| 1) BY CHANGING THE RETURN AIR DUCTING FROM DIRECT |
| RETURN TO TRANSFER RETURN YOU NEED TO COMPLY WITH 2004 |
| FBC/R M1602.4. |
| |
| 2) BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| ACHIEVE PROPER RETURN AIR BALANCE. |
| (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| 3) FIRST FLOOR 10" RETURN AIR TRANSFER DUCT TO DEN |
| NEEDS TO BE 12", SEE NOTE #2 (A). |
| |
| 4) SECOND FLOOR 10" RETURN AIR TRANSFER DUCT TO MASTER |
| SUITE NEEDS TO BE 14", SEE NOTE #2 (A) AND (B) EXCEPT. |
| |
| 5) 10" RETURN AIR TRANSFER DUCT TO BEDROOM 2 NEEDS TO |
| BE 14" , SEE NOTE #2 (A). |
| |
| 6) 8" RETURN AIR TRANSFER DUCT TO BEDROOM 3 NEEDS TO BE |
| 12", SEE NOTE #2 (A). |
| |
| 7) 8" RETURN AIR TRANSFER DUCT TO GUEST SUITE NEEDS TO |
| BE 10", SEE NOTE #2 (A). |
| |
| MECHANICAL PLAN REVIEW BY; |