Plan Review Notes
Plan Review Notes For Permit 06090973
Permit Number 06090973
Review Stop M
Sequence Number 3
Notes
Date Text
2007-02-12 11:04:58MECHANICAL REVISION TO PLANS.
 *** DENIED ***
 1) BY CHANGING THE RETURN AIR DUCTING FROM DIRECT
 RETURN TO TRANSFER RETURN YOU NEED TO COMPLY WITH 2004
 FBC/R M1602.4.
  
 2) BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 3) FIRST FLOOR 10" RETURN AIR TRANSFER DUCT TO DEN
 NEEDS TO BE 12", SEE NOTE #2 (A).
  
 4) SECOND FLOOR 10" RETURN AIR TRANSFER DUCT TO MASTER
 SUITE NEEDS TO BE 14", SEE NOTE #2 (A) AND (B) EXCEPT.
  
 5) 10" RETURN AIR TRANSFER DUCT TO BEDROOM 2 NEEDS TO
 BE 14" , SEE NOTE #2 (A).
  
 6) 8" RETURN AIR TRANSFER DUCT TO BEDROOM 3 NEEDS TO BE
 12", SEE NOTE #2 (A).
  
 7) 8" RETURN AIR TRANSFER DUCT TO GUEST SUITE NEEDS TO
 BE 10", SEE NOTE #2 (A).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.