Plan Review Notes For Permit 06090950 |
Permit Number |
06090950 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-12-08 13:11:44 | BUILDING REVIEW 4TH CHECKLIST: | | 1- NOW, PROPOSED INSTALLATION IS "GROMMET TWO SIDE | | ATTACHMENT INSTALLATION".PRODUCT IS STILL LIMITED TO | | 154" MAX. SPAN. IT CAN'T BE USED FOR OPENING #12 WHICH | | HAS AN SPAN OF 180". PRODUCT DOESN'T WORK FOR PROPOSED | | INSTALLATION. | | | | ***NOTE: THIS IS THE 4TH TIME THE PERMIT APPLICATION IS | | DENIED FOR THE SAME ITEM.THIS PRODUCT DOESN'T WORK | | FOR THE PROPOSED INSTALLATION. | | | | 2- OPENING #19 CALLS FOR AND EDGE DISTANCE OF 3". | | ANCHOR SPACING IS 12"O.C.. NEED TO REDUCE ANCHOR | | SPACING AS REQUIRED BY ANCHOR SPACING CHART ON PAGE 7 | | OF 8 OF DRAWING SC 02-06. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|