Plan Review Notes
Plan Review Notes For Permit 06090950
Permit Number 06090950
Review Stop B
Sequence Number 4
Notes
Date Text
2006-12-08 13:11:44BUILDING REVIEW 4TH CHECKLIST:
 1- NOW, PROPOSED INSTALLATION IS "GROMMET TWO SIDE
 ATTACHMENT INSTALLATION".PRODUCT IS STILL LIMITED TO
 154" MAX. SPAN. IT CAN'T BE USED FOR OPENING #12 WHICH
 HAS AN SPAN OF 180". PRODUCT DOESN'T WORK FOR PROPOSED
 INSTALLATION.
  
 ***NOTE: THIS IS THE 4TH TIME THE PERMIT APPLICATION IS
 DENIED FOR THE SAME ITEM.THIS PRODUCT DOESN'T WORK
 FOR THE PROPOSED INSTALLATION.
  
 2- OPENING #19 CALLS FOR AND EDGE DISTANCE OF 3".
 ANCHOR SPACING IS 12"O.C.. NEED TO REDUCE ANCHOR
 SPACING AS REQUIRED BY ANCHOR SPACING CHART ON PAGE 7
 OF 8 OF DRAWING SC 02-06.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER