Plan Review Notes For Permit 06090950 |
Permit Number |
06090950 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-11-17 09:22:57 | BUILDING REVIEW 3RD CHECKLIST: | | | | 1- ACCORDING TO INSTALLATION SCHEDULE SUBMITTED, | | PROPOSED INSTALLATION IS A GROMMET THREE SIDE | | ATTACHMENT OF THE STORM CATCHER. PAGE 7 OF 8 OF DRAWING | | NO SC 02-06SUBMITTEDINDICATES ANCHOR SPACING OF | | 1/4" TAPCON TO BE AT 12"O.C. AT CONDITION 1 AND 4"O.C. | | AT CONDITION 2 WHEN EDGE DISTANCE IS 3-1/2".EDGE | | DISTANCE INDICATED ON PROPOSED INSTALLATION SCHEDULE IS | | 3". THEREFORE, NEED TO REDUCE ANCHOR SPACING ACCORDING | | TO TABLE ON SHEET 7 OF 8. REVISE INSTALLATION SCHEDULE | | AS REQUIRED. | | | | 2- MAXIMUM PANEL SPAN IS 154". SPAN FOR OPENING #12 IS | | 180". REVISE AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|