Plan Review Notes For Permit 06090903 |
Permit Number |
06090903 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-02-12 15:22:21 | DENIED; | | FBC-2004 PLUMBING CODE TABLE REQUIRES A DRINKING | | FOUNTAIN. SECTION 410 ALLOWS WATER COOLERS TO | | SUBSTITUED FOR NOT MORE THAN 50% OF THE DRINKING | | FOUNTAIN, SO THE BOTTLED WATER COOLER SHOWN ON PLAN | | MUST BE CHANGED TO A DRINKING FOUNTAIN. PLEASE SHOW ON | | FLOOR PLAN AND PLUMBING RISERS. ALSO SHOW A DETAIL TO | | SHOW COMPLIANCE TO CHAPTER 11 OF THE BUILDING CODE. | | SECTIONS 11-4.1.3(10)AND SECTIONS 11-4.15.2 SPOUT | | HEIGHT 11-4.15.3 SPOUT LOCATION, 11-4.15.4 CONTROLS, | | AND 11-4.15.5 CLEARANCES. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|