Plan Review Notes For Permit 06090903 |
Permit Number |
06090903 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-12-15 08:30:58 | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE | | 2004 FBC EXISTING BUILDING CODE SECTION 301.5. | | | | 3) SPECIFY THE SQUARE FOOTAGE FOR THE AREA, THE | | OCCUPANT LOAD, THE NUMBER OF REQUIRED EXITS AND THE | | WIDTHS OF THE EGRESS DOORS ON THE PLANS. | | | | 4)SPECIFY THE TYPE OF CONSTRUCTION BASED ON THE 2004 | | FBC DESIGNATIONS ON THE PLANS. NOTE: NON-COMBUSTIBLE IS | | NOT A CONSTRUCTION TYPE. SEE FBC 602.1 BUILDINGS AND | | STRUCTURES ERECTED OR TO BE ERECTED, ALTERED OR | | EXTENDED IN HEIGHT OR AREA SHALL BE CLASSIFIED IN ONE | | OF THE FIVE CONSTRUCTION TYPES DEFINED IN SECTIONS | | 602.2 THROUGH 602.5. | | | | 5) PLEASE REMOVE THE OLD PLAN SHEETS AND REPLACE THEM | | WITH THE NEW ONES, MAKING TWO COMPLETE SETS. ONE SET OF | | THE OLD PLANS MARKED VOIDED CAN BE RESUBMITTED FOR | | REFERENCE TO AID IN PLAN REVIEW. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|