2006-11-06 18:00:16BUILDING REVIEW 2ND CHECKLIST:
  
 ***FROM PREVIOUS CHECKLIST:
 1- DRAWING 7 OF 13: INCORRECTANCHOR SPACING WAS
 MARKED. CALCULATED DESIGN PRESSURES ARE -33PSF.ANCHOR
 SPACING WAS MARKED FOR DESIGN PRESSURES OF -31.2PSF.
 ACCORDING TO NOTE #2 NEED TO USE HIGHER LOADS FOR
 TABULATED VALUES. THEREFORE, NEED TO USE THE ANCHOR
 SPACING FOR -47.2PSF. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER