Plan Review Notes For Permit 06090892 |
Permit Number |
06090892 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-11-06 18:00:16 | BUILDING REVIEW 2ND CHECKLIST: | | | | ***FROM PREVIOUS CHECKLIST: | | 1- DRAWING 7 OF 13: INCORRECTANCHOR SPACING WAS | | MARKED. CALCULATED DESIGN PRESSURES ARE -33PSF.ANCHOR | | SPACING WAS MARKED FOR DESIGN PRESSURES OF -31.2PSF. | | ACCORDING TO NOTE #2 NEED TO USE HIGHER LOADS FOR | | TABULATED VALUES. THEREFORE, NEED TO USE THE ANCHOR | | SPACING FOR -47.2PSF. REVISE AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|