2006-10-13 11:22:03BUILDING REVIEW CHECKLIST;
 1- PROVIDE STRUCTURAL DETAIL WITH COMPLETE SPECS FOR
 FOOTING USING #5 REBAR AS SPECIFIED ON DRAWING
 SUBMITTED. WHY IS A FOOTER REQUIRED?.HOW IS FOOTER
 FASTENED? SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 2- DRAWING5 OF 13 OFSHUTTERS DRAWINGS HAVE WALL
 MOUNT SECTION CIRCLED. IF THIS IS THE PROPOSED MOUNTING
 CONDITIONS, THEN WHY IS A FOOTER REQUIRED?. PROVIDE
 CLARIFICATION AND SPECIFIC MOUNTING CONDITIONS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- DRAWING 7 OF 13: INCORRECT ANCHOR SPACING WAS
 MARKED.CALCULATED DESIGN PRESSURES ARE -33PSF (OR 35
 IF USING TABLE 1).SEE TABLE NOTE #2 AT BOTTOM OF PAGE
 AND REVISE AS REQUIRED.
  