Plan Review Notes For Permit 06090860 |
Permit Number |
06090860 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-26 00:00:00 | | | | | DENIED | | | | 1) THE ROOFING PERMIT APPLICATION SHALL | | INCLUDE TWO COPIES OF EACH PRODUCT | | APPROVAL THAT IS RELEVANT PER 9B-72. | | THESE SHOULD INCLUDE THE FLORIDA STATE | | APPROVAL COVER PAGES, AND THE PRODUCT | | NOA THAT LISTS THE SYSTEM COMPONENTS/ | | FASTENER LIST PAGES, THE PAGES WITH THE | | CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND | | THE GENERAL LIMITATIONS PAGE. ALL CAN BE | | FOUND ON WWW.FLORIDABUILDING.ORG | | | | 2) ALL SYSTEMS IN THIS NOA ARE | | MECHANICALLY FASTENED NOT HOT MOPPED | | | | 3) PLEASE SEE THAT BECAUSE THEY ARE | | MECHANICALLY FASTENED THE LIMITATIONS | | WILL REQUIRE ENGINEERS SIGNED AND SEALED | | CALCULATIONS FOR THE ENHANCED FASTENING | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | |
|