Plan Review Notes For Permit 06090796 |
Permit Number |
06090796 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 2- FLORIDA PRODUCT APPROVAL COVER PAGE | | FL1850-R1 CALLS FOR ACCORDION SHUTTERS | | DRAWING NO 05-195. DRAWINGS SUBMITTED | | ARE NO 05-196. NEED TO PROVIDE DRAWINGS | | THAT MATCH FLORIDA COVER PAGE. | | | | 3- ANCHOR TYPE SPECIFIED ON | | INSTALLATION SCHEDULE TO MATCH ANCHOR | | SPECIFIED ON THE DRAWINGS. SEE PAGE 12 | | OF 14 OF ACCORDION SHUTTERS DRAWINGS AND | | REVISE AS REQUIRED. | | | | 4- PROVIDE 2 COPIES OF WIND LOAD | | SCHEDULE CHARTS WITH ENGINEER'S ORIGINAL | | SEAL, SIGNATURE AND DATE AS REQUIRED BY | | CHAPTER 471 FLORIDA STATUTES. ONLY ONE | | ORIGINAL PROVIDED. COPIES ARE NOT | | ALLOWED. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|