Plan Review Notes For Permit 06090795 |
Permit Number |
06090795 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- ACCORDION SHUTTERS INSTALLATION | | SCHEDULE CALLS FOR METAL FRAME AS THE | | SUBSTRUCTURE. NEED PRODUCT APPROVAL FOR | | PROPOSED INSTALLATION. PRODUCT APPROVAL | | SUBMITTED IS FOR ATTACHMENT TO CONCRETE, | | CONCRETE BLOCK OR WOOD ONLY. THEREFORE, | | IT DOESN'T APPLY TO PROPOSED | | INSTALLATION. | | | | 2- ENGINEERED WIND LOAD SCHEDULE NEED TO | | HAVE ENGINEER'S ORIGINAL SEAL, SIGNATURE | | AND DATE AS REQUIRED BY CHAPTER 471 | | FLORIDA STATUTES. BOTH COPIES. | | | | 3- SPECIFY SIZE OF WINDOWS AND LOCATION. | | SPECIFY WINDOW SIZE IN BEDROOMS TO | | VERIFY COMPLIANCE WITH THE EGRESS | | REQUIREMENTS. | | | | 4- WHEN RE-SUBMITTING CHECK THE | | FOLLOWING: | | A) CLEAR AND LEGIBLE DRAWINGS. | | B) ANCHOR SPECIFIED MATCHES ONE IN THE | | PRODUCT APPROVAL. | | C) EDGE DISTANCE AND SPACING REDUCTION | | IF REQUIRED. | | | | 5- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|