Plan Review Notes
Plan Review Notes For Permit 06090793
Permit Number 06090793
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- WIND LOAD SCHEDULE IS NOT REQUIRED
 FOR BUILDING WITH MEAN ROOF HEIGHT LESS
 THAN 30'-0". CONTRACTOR MAY USE TABLE
 1609.6B OF 2004 FBC TO DETERMINE DESIGN
 PRESSURES. IF SUBMITTING ENGINEER'S WIND
 LOAD SCHEDULE, THEN ALL COPIES MUST HAVE
 ORIGINAL SEAL, SIGNATURE AND DATE AS
 REQUIRED BY CHAPTER 471 FL STATUTES.
  
 3- STORM PANELS:
 A) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
 B) FASTENER SPECIFIED ON INSTALLATION
 SCHEDULE TO MATCH FASTENER SPECIFIED ON
 DRAWINGS.
 C) FASTENER SPACING MUST BE REDUCED IF
 EDGE DISTANCE IS 2". SEE PAGE 11 OF 17
 OF DRAWINGS AND USE SPECIFIED
 MULTIPLIER.
 D) PANELS ARE 103" LONG. CONTRACTOR
 MARKED INSTALLATION SCHEDULE ON PAGE 10
 OF 17. THIS SCHEDULE IS FOR PANELS UP TO
 8'-0" LONG. MARK CORRECT INSTALLATION
 SCHEDULE ON PAGE 11 OF 17.
  
 4- ACCORDION SHUTTERS:
 A) FLORIDA PRODUCT APPROVAL FL1850-R1
 CALLS FOR DRAWING NO 05-195. DRAWING
 SUBMITTED IS 05-196. PROVIDE CORRECT
 DRAWING THAT WAS SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL.
 B) CONTRACTOR MARKED INSTALLATION
 SCHEDULE ON PAGE 11 OF 14 FOR SPAN UP TO
 7'-0". PANEL SPAN FOR OPENING #3 IS 91".
 REVISE AS REQUIRED.
 C) REDUCE FASTENER SPACING AS REQUIRED
 WHEN EDGE DISTANCE IS 2". SEE PAGE 11 OF
 14 FOR MULTIPLIER TO BE USED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712