Plan Review Notes For Permit 06090790 |
Permit Number |
06090790 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-05 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | 2- STORM PANELS: | | A) ANCHOR TYPE SPECIFIED FOR STORM | | PANELS IS NOT THE SAME ANCHOR TYPE THAT | | IS USED IN THE PRODUCT APPROVAL. REVISE | | AS REQUIRED. | | B) 2" EDGE DISTANCE REQUIRES ANCHOR | | SPACING TO BE REDUCED USING THE | | MULTIPLIER AS REQUIRED ON TABLE AT | | BOTTOM OF PAGE 9 OF 17 OF STORM PANELS | | DRAWINNG NO 05-284. REVISE ANCHOR | | SPACING AS REQUIRED. | | | | 3- PRODUCT APPROVAL FOR ACCORDION | | SHUTTERS IS NOT LEGIBLE. PROVIDE CLEAR | | AND LEGIBLE DRAWINGS TO BE ABLE TO READ | | DRAWINGS AND CHECK PROPOSED | | INSTALLATION. | | | | 4- WIND LOAD SCHEDULE IS NOT REQUIRED | | FOR BUILDINGS WITH MEAN ROOF HEIGHT OF | | 30'-0" OR LESS. CONTRACTOR MAY USE TABLE | | 1609.6B OF FBC 2004 TO DETERMINE THE | | DESIGN PRESSURES. ON THE OTHER HAND, IF | | SCHEDULE IS SUBMITTED, THEN IT MUST HAVE | | ENGINEER'S ORIGINAL SEAL, SIGNATURE AND | | DATE AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES. COPIES ARE NOT ALLOWED | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|