Plan Review Notes
Plan Review Notes For Permit 06090790
Permit Number 06090790
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-05 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- STORM PANELS:
 A) ANCHOR TYPE SPECIFIED FOR STORM
 PANELS IS NOT THE SAME ANCHOR TYPE THAT
 IS USED IN THE PRODUCT APPROVAL. REVISE
 AS REQUIRED.
 B) 2" EDGE DISTANCE REQUIRES ANCHOR
 SPACING TO BE REDUCED USING THE
 MULTIPLIER AS REQUIRED ON TABLE AT
 BOTTOM OF PAGE 9 OF 17 OF STORM PANELS
 DRAWINNG NO 05-284. REVISE ANCHOR
 SPACING AS REQUIRED.
  
 3- PRODUCT APPROVAL FOR ACCORDION
 SHUTTERS IS NOT LEGIBLE. PROVIDE CLEAR
 AND LEGIBLE DRAWINGS TO BE ABLE TO READ
 DRAWINGS AND CHECK PROPOSED
 INSTALLATION.
  
 4- WIND LOAD SCHEDULE IS NOT REQUIRED
 FOR BUILDINGS WITH MEAN ROOF HEIGHT OF
 30'-0" OR LESS. CONTRACTOR MAY USE TABLE
 1609.6B OF FBC 2004 TO DETERMINE THE
 DESIGN PRESSURES. ON THE OTHER HAND, IF
 SCHEDULE IS SUBMITTED, THEN IT MUST HAVE
 ENGINEER'S ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES. COPIES ARE NOT ALLOWED
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712