2006-09-28 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DRAWING
 DOES NOT REFLECT THE LAYOUT AND DOES NOT
 REFLECT ANY CORRESPONDING LENGTHS.
 PLEASE REFERENCE THE EXAMPLE ISOMETRIC
 IN RED INK OF WHAT THE FLAT PLAN
 INDICATES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE SUBMITTED ISOMETRIC DRAWING
 DOES NOT INDICATE THE ABOVE GROUND
 MATERIALS AND SIZES.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: BTU LOAD OF POOL HEATER IS NOT
 INDICATED ON DRAWING.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THERE ARE NOT ANY MEASUREMENTS
 INDICATED ON THE ISOMETRIC DRAWING TO
 VERIFY SIZING WITH TABLES.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: PLEASE INDICATE DELIVERY PRESSURE
 ON DRAWING.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: THE SHEET OF THE POOL HEATER DOES
 NOT INDICATE THE MANUFACTURER'S NAME.
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  