2006-09-21 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| _XX_1.)A NOTICE OF COMMENCEMENT |
| MUST BE FILED WITH THE CLERK OF COURTS |
| BEFORE A PERMIT CAN BE ISSUED. |
| |
| _XX_2.)CONTRACTOR IS TO PROVIDE THE |
| FOLLOWING INFORMATION ON THE |
| APPLICATION: |
| |
| MEAN ROOF HEIGHT |
| ROOF PITCH |
| ROOF DECK TYPE |
| AREA OF EACH ROOF TYPE |
| |
| ____3.)FLORIDA STATE OR LOCAL |
| PRODUCT APPROVAL REQUIRED IN ADDITION TO |
| THE EVALUATION REPORT SUBMITTED, |
| FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| _XX_4.)FOR THE FLAT DECK, SELECT THE |
| APPROVED ASSEMBLY YOU ARE USING. |
| |
| ____ 5.)ON THE TILE PRODUCT APPROVAL, |
| INDICATE WHICH METHOD OF ATTACHMENT YOU |
| ARE USING. |
| |
| ____ 6.)SEE PRODUCT LIMITATION #7. |
| CALCULATIONS PREPARED BY AN ARCHITECT, |
| ENGINEER, OR REGISTERED ROOF CONSULTANT |
| REQUIRED FOR ENHANCED FASTENING. |
| |
| _XX_ 7.)PROVIDE A REASONABLE VALUE FOR |
| THIS JOB. |
| |
| |