2007-10-01 11:04:00 | ***SUBMITTAL/REVISION*** |
| |
| ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| ROOFING SUBMITTAL: |
| |
| 1.)TAS105 IS TO BE PERFORMED BY AN APPROVED TESTING |
| LAB.PLEASE PROVIDE EVIDENCE OF NUTTING ENGINEERS AS |
| AN APPROVED TESTING LAB AS I WAS UNABLE TO LOCATE A |
| LIST ON THE INTERNET. |
| |
| **OK - REVISED 10/2 - CONTRACTOR SHOWED TO J SMITH, |
| INSPECTOR** |
| |
| 2.)FASTENER DESIGN IN ACCORDANCE WITH RAS117 IS TO BE |
| SUBMITTED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT AS PER GENERAL LIMITATION #7 OF THE |
| MIAMIDADE NOA 06-0626.05.PLEASE SUBMIT.**OK - |
| SUBMITTED W/ROOF PERMIT 07070582** |
| |
| ROOF HATCH: |
| |
| 3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| FOR THE ROOF HATCH, FAC9B72. IF A FLORIDA STATE PRODUCT |
| APPROVAL IS NOT AVAILABLE, SUBMIT APPLICATION FOR LOCAL |
| PRODUCT APPROVAL; SEE ATTACHED.ALL INFORMATION ON THE |
| APPLICATION MUST BE COMPLETED AND ALL ENGINEERING MUST |
| BE ORIGINAL.IF A MIAMIDADE NOA HAS BEEN ISSUED FOR |
| THE PRODUCT YOU ARE USING, AN APPLICATION (AND ORIGINAL |
| ENGINEERING) IS NOT REQUIRED.OTHERWISE, SUBMIT ALL |
| INFORMATION REQUIRED INCLUDING PROOF OF A QUALITY |
| ASSURANCE PROGRAM. |
| |
| ACCESSIBLE LIFT, SCUTTLE LADDER: |
| |
| 4.)HAVE THE SHOP DRAWINGS REVIEWED BY DESIGNER OF |
| RECORD. |
| |
| MISCELLANEOUS: |
| |
| 5.)AS A COURTESY, I HAVE PRINTED THE INSTALLATION |
| INSTRUCTIONS AND SUPPLEMENTARY DRAWINGS FOR THE |
| EVALUATION REPORT FOR THE OVERHEAD DOOR PRODUCT |
| APPROVAL AS THE DRAWINGS WERE ILLEGIBLE.IN THE |
| FUTURE, PLEASE SUBMIT ONLY LEGIBLE DOCUMENTS.THEY ARE |
| AVAILABLE ON THE INTERNET AT WWW.FLORIDABUILDING.ORG. |