2007-09-13 13:41:09 | |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE SEE THE NEW SEPARATE ELECTRICAL SERVICE |
| AND METER LOCATION WOULD BE UNDER A SEPARATE PERMIT FOR |
| THE SERVICE. THIS IS NOT ACTUALLY COMING FROM THE |
| BUILDING ELECTRICAL SERVICE OR ANY PART OF THE |
| BUILDING. |
| PLEASE SEE THIS LOCATION WILL ALSO REQUIRE AN ADDRESS |
| EXTENSION TO PCN FOR NEW METER/SERVICE LOCATION. PLEASE |
| BE SURE TO GET WITH THE FPL REPRESENTATIVE AND THE CITY |
| ADDRESSING REVIEWER LILI LACRAMIOARA @ 561-822-1239. |
| |
| 2) NOTE: PLEASE CLARIFY RISER AS THIS SHOWS A *GROUND* |
| ON THE LINE SIDE OF THE FIRST MEANS OF DISCONNECT. IS |
| THIS THE NEUTRAL/GROUNDED CONDUCTOR? |
| NO *EQUIPMENT GROUNDING CONDUCTORS* ARE ALLOWED ON THE |
| LINE SIDE OF SERVICE MAINS. |
| 250.6, 250.24 |
| |
| 3) NOTE: TWO GROUND RODS MINIMUM WILL BE REQUIRED PER |
| 250.50 AND 250.56 |
| |
| 4) NOTE: PLEASE PROVIDE INFORMATION FOR PUMP SIZE AND |
| OVER CURRENT PROTECTION INFORMATION. |
| REVIEW OF SOME ITEMS FOR CONDUCTOR SIZES, SERVICE ETC |
| CAN NOT BE REVIEWED AT THIS TIME. |
| |
| ** PLEASE KNOW THE ABOVE ELECTRICAL WILL NEED TO BE |
| SUBMITTED UNDER AN ELECTRICAL PERMIT FOR THE NEW |
| SEPARATE SERVICE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |