Notes
Date Text
2007-09-13 13:41:09 
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE NEW SEPARATE ELECTRICAL SERVICE
 AND METER LOCATION WOULD BE UNDER A SEPARATE PERMIT FOR
 THE SERVICE. THIS IS NOT ACTUALLY COMING FROM THE
 BUILDING ELECTRICAL SERVICE OR ANY PART OF THE
 BUILDING.
 PLEASE SEE THIS LOCATION WILL ALSO REQUIRE AN ADDRESS
 EXTENSION TO PCN FOR NEW METER/SERVICE LOCATION. PLEASE
 BE SURE TO GET WITH THE FPL REPRESENTATIVE AND THE CITY
 ADDRESSING REVIEWER LILI LACRAMIOARA @ 561-822-1239.
  
 2) NOTE: PLEASE CLARIFY RISER AS THIS SHOWS A *GROUND*
 ON THE LINE SIDE OF THE FIRST MEANS OF DISCONNECT. IS
 THIS THE NEUTRAL/GROUNDED CONDUCTOR?
 NO *EQUIPMENT GROUNDING CONDUCTORS* ARE ALLOWED ON THE
 LINE SIDE OF SERVICE MAINS.
 250.6, 250.24
  
 3) NOTE: TWO GROUND RODS MINIMUM WILL BE REQUIRED PER
 250.50 AND 250.56
  
 4) NOTE: PLEASE PROVIDE INFORMATION FOR PUMP SIZE AND
 OVER CURRENT PROTECTION INFORMATION.
 REVIEW OF SOME ITEMS FOR CONDUCTOR SIZES, SERVICE ETC
 CAN NOT BE REVIEWED AT THIS TIME.
  
 ** PLEASE KNOW THE ABOVE ELECTRICAL WILL NEED TO BE
 SUBMITTED UNDER AN ELECTRICAL PERMIT FOR THE NEW
 SEPARATE SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  