Date |
Text |
2007-04-04 07:45:09 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| ***NOTE - PLAN REVIEW COMMENTS WERE CHANGED 4/12/07 TO |
| DOCUMENT ITEMS DISCUSSED/NEGOTIATED WITH ARCHITECT AND |
| CONTRACTOR IN A MEETING 4/11/07** |
| ***NOTE THAT A LIFE SAFETY PLAN WAS ACCEPTED DURING THE |
| PLAN REVIEW PROCESS DURING REVIEW #3.THIS IS THE 4TH |
| COURTESY REVIEW REFERRED TO IN THE PLAN REVIEW |
| NOTES.*** |
| |
| 1-8.) ADDRESSED. |
| |
| 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN |
| SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION |
| WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT |
| REQUIRED TO BE ADDRESSED AT THIS TIME. |
| |
| 10-12.)ADDRESSED. |
| |
| 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE |
| THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET. |
| |
| THREE SETS SUBMITTED.PLEASE KEEP THE THREE SETS IN |
| THE PACKAGE.THEY ARE NOT CURRENTLY A PART OF THE |
| BOUND SET.THIS IS ACCEPTABLE; HOWEVER, PLEASE ENSURE |
| THAT THEY ARE NOT INADVERTENTLY REMOVED FROM THE |
| PACKAGE AS THIS IS A STATUTORY REQUIREMENT AND THE |
| PERMIT CANNOT BE ISSUED WITHOUT SPRINKLER PLANS. |
| |
| 14-15.) ADDRESSED. |
| |
| 16.)A NEW LIFE SAFETY PLAN WAS ACCEPTED DURING THE |
| PLAN REVIEW PROCESS.NOTE THAT THE ORIGINAL LS PLAN |
| SUBMITTED DID NOT PROPERLY ADDRESS THE COMMENTS AND A |
| NEW LS PLAN WAS SUBMITTED AFTER DISCUSSION WITH THE |
| ARCHITECT. |
| |
| 3RD REVIEW:ONLY ONE ACCESSIBLE EXIT SHOWN FOR EACH |
| AREA.BASED ON OCCUPANT LOAD, TWO EXITS ARE REQUIRED |
| FOR THE DISTRIBUTION AREA, TWO EXITS ARE REQUIRED FOR |
| THE OFFICE AREA.PROVIDE ALL INFORMATION FOR EXITING |
| ON THE LIFE SAFETY PLAN FOR THE ACCESSIBLE EXITS. |
| REVIEW WAS STOPPED AND I AGREED TO ACCEPT A NEW LIFE |
| SAFETY PLAN IN ATTEMPT TO ISSUE THE PERMIT IF ALL OTHER |
| ITEMS WERE ADDRESSED FROM ALL PLAN REVIEWERS, INCLUDING |
| MY LIST.HOWEVER, THE LIFE SAFETY PLAN SUBMITTED WAS |
| NOT COMPLIANT. |
| |
| FOURTH (COURTESY) REVIEW.THE NEW LIFE SAFETY PLAN |
| SHOULD BE REVISED TO SHOW THE FOLLOWING FOR THE SECOND |
| ACCESSIBLE MEANS OF EGRESS FROM THE DISTRIBUTION AREA: |
| |
| EXIT LIGHTS, FBC1006.3 |
| EXIT CAPACITY, FBC1004.1.3 |
| DOOR SWING, FBC1008.1.2 |
| TRAVEL DISTANCE, FBC1015 |
| EGRESS CAPACITY, FBC1005 |
| |
| NOTE THAT TRAVEL DISTANCE IS SHOWN THROUGH THE MIDDLE |
| OF SOME ROOMS; THIS IS USUALLY DONE AROUND THE |
| PERIMETER OF THE ROOM, FBC1015.1. |
| |
| ALL OF THE ABOVE INFORMATION WAS PROVIDED ON THE LIFE |
| SAFETY PLAN BUT DID NOT ADDRESS ACCESSIBLE MEANS OF |
| EGRESS.SEE COMMENT 17, ACCESSIBLE MEANS OF EGRESS |
| SHALL BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR |
| EXITS BY LOCAL BUILDING/LIFE SAFETY REGULATIONS, |
| FBC11-4.1.3(9).A LIFT WAS ADDED, EXITING THROUGH THE |
| OFFICE AREA WAS DISCUSSED BUT NOTHING IS SHOWN ON THE |
| PLAN; OTHER INFORMATION ABOVE NOT PROVIDED. |
| |
| 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL |
| BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY |
| LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN |
| AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS |
| SHOWN. |
| |
| 2ND REVIEW, THE RESPONSE LETTER STATES THAT ALL EXITS |
| ARE ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS, |
| MEANS OF; DOES NOT INCLUDE STAIRS, STEPS, OR |
| ESCALATORS. |
| |
| (REVISED 4/12) 3RD COURTESY REVIEW, TWO EXITS ARE |
| REQUIRED FROM THE DISTRIBUTION AREA AND TWO EXITS |
| REQUIRED FROM THE OFFICE AREA.ONLY ONE ACCESSIBLE |
| EXIT FOR EACH AREA IS SHOWN. |
| |
| (REVISED 4/12) 4TH REVIEW, REVISED LIFE SAFETY PLAN |
| SUBMITTED DURING REVIEW; THERE IS STILL ONLY ONE |
| ACCESSIBLE EXIT FROM THE DISTRIBUTION AREA, TWO |
| REQUIRED BASED ON OCCUPANT LOAD. |
| |
| 18.)1ST/2ND REVIEW: THIS BUILDING REQUIRES MORE THAN |
| ONE EXIT, SEE FBC1018.2.THIS WAS NOT ADDRESSED FOR |
| ACCESSIBLE EXITS; ONLY ONE SHOWN. |
| |
| (REVISED 4/12) 3RD REVIEW:SEE COMMENT 17. |
| |
| (REVISED 4/12) 4TH COURTESY REVIEW:THERE IS NOW ONE |
| ACCESSIBLE EXIT SHOWN FOR THE DISTRIBUTION AREA |
| (REQUIRES TWO BASED ON OCCUPANT LOAD) AND ONE FOR THE |
| OFFICE AREA.OFFICE AREA IS COMPLIANT AS IT REQUIRES |
| ONE EXIT BASED ON OCCUPANT LOAD, BUT TWO ACCESSIBLE |
| EXITS ARE REQUIRED FOR THE DISTRIBUTION AREA. |
| |
| 19-22.)ADDRESSED. |
| |
| 23.)1ST/2ND REVIEWS: EXIT OR EXIT ACCESS DOORWAY |
| ARRANGEMENT SHALL COMPLY WITH FBC1014.2 OR |
| FBC1014.2.2., SHOW DISTANCE APART, SEE EXCEPTION 2. |
| THERE ARE TO BE TWO ACCESSIBLE EXITS WHICH ARE REMOTELY |
| LOCATED.ONLY ONE SHOWN ON THE PLAN (ALL OTHERS HAVE |
| STAIRS). |
| |
| 3RD REVIEW (REVISED 4/12):THE TWO DOORS SHOWN SERVE |
| TWO DIFFERENT AREAS.SHOW THE TWO ACCESSIBLE EXITS, |
| REMOTELY LOCATED, AS REQUESTED. |
| |
| 4TH (COURTESY) REVIEW: THE DISTANCE IS SHOWN BETWEEN |
| THE TWO ACCESSIBLE EXITS BUT THE EXIT WITH THE RAMP |
| DOES NOT SERVE THE DISTRIBUTION AREA (NO EXIT SIGNS |
| FROM DISTRIBUTION AREA THROUGH OFFICE, NOTHING ON THE |
| PLAN TO SHOW THAT THIS IS TO BE AN EXIT TO SERVE THE |
| DISTRIBUTION AREA).IT IS CLEAR THAT NON ACCESSIBLE |
| EXITS ARE COMPLIANT.SHOW COMPLIANCE FOR ACCESSIBLE |
| EXITS AS REQUESTED ON PREVIOUS REVIEWS. |
| |
| 24.) ADDRESSED. |
| |
| 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. |
| |
| 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I |
| BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR |
| PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED |
| PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NON IMPACT |
| PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A |
| SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO |
| PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE |
| TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS |
| THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT |
| RATED, DISREGARD THE COMMENT. |
| |
| THIRD REVIEW - PLEASE SUBMIT ALL REQUIRED PRODUCT |
| APPROVALS AT THIS TIME. |
| |
| 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT |
| DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE |
| REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER |
| PRODUCT APPROVALS WERE SUBMITTED.FLORIDA STATE OR |
| LOCAL PRODUCT APPROVAL REQUIRED IN ADDITION TO THE |
| EVALUATION REPORT (MIAMIDADE NOA IN THIS CASE) |
| PROVIDED, FAC9B72; WWW.FLORIDABUILDING.ORG.IF FLORIDA |
| STATE PRODUCT APPROVAL IS NOT AVAILABLE, PLEASE CONTACT |
| ME TO DISCUSS. |
| |
| NO ROOFING PR-DUCT APPROVALS WERE SUBMITTED. CONTRACTOR |
| OR DOR IS TO SELECT THE APPROVED ASSEMBLY. |
| |
| FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM |
| ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR |
| INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR |
| DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE |
| INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT |
| CODE COMPLIANCE CAN BE DETERMINED. |
| |
| THIRD REVIEW ? THE PRODUCT APPROVALS WHICH ARE IN THE |
| PACKAGE STILL HAVE NO EVIDENCE THAT THEY HAVE BEEN |
| REVIEWED BY DESIGNER OF RECORD.THIS MAY BE DONE WITH |
| A SHOP DRAWING REVIEW STAMP, A LETTER, OR INCORPORATED |
| INTO THE PLAN BY REFERENCE. |
| |
| ALL PRODUCT APPROVALS REQUIRED BY FAC9B72 ARE REQUIRED |
| AT THIS TIME DUE TO A POLICY CHANGE.STATEMENTS IN THE |
| PREVIOUS COMMENTS THAT THEY COULD BE SUBMITTED IN THE |
| FUTURE UNDER SEPARATE PERMIT HAVE BEEN REMOVED FROM |
| THIS REVIEW TO AVOID CONFUSION. |
| |
| AS THE DOR DID NOT PROVIDE A SCHEDULE, ALL WALL |
| PRODUCTS ARE TO COMPLY WITH WORST CASE WALL PRESSURE OF |
| -48PSF.PRODUCT APPROVALS REQUIRED INCLUDE STOREFRONT, |
| SKYLIGHT, OVERHEAD DOOR, FULL LOUVER METAL DOOR, |
| LOUVERS, ROOF HATCH, 24 GA GALVALUME STANDING SEAM |
| METAL ROOF, 4 PLY BUR OVER INSULATED LW CONCRETE.THIS |
| MAY NOT BE A COMPLETE LIST; CONTRACTOR OR DOR IS |
| RESPONSIBLE FOR THE COMPLETENESS OF THE SUBMITTED |
| PACKAGE. |
| |
| **4/12/07** DURING THE MEETING WITH THE ARCHITECT I |
| BECAME AWARE THAT THE THREE BOUND SETS OF DOCUMENTS |
| SUBMITTED WERE NOT IDENTICAL SETS.THERE WERE SOME |
| PRODUCT APPROVALS REVIEWED BY DOR IN THE OTHER PACKAGE. |
| THE ROOF PRODUCT APPROVAL WAS REVIEWED BY ANOTHER |
| ARCHITECT FROM A DIFFERENT PRODUCT. |
| |
| WHEN RESUBMITTING, PLEASE PROVIDE THREE IDENTICAL BOUND |
| SETS FOR PERMIT ISSUANCE.FAILURE TO DO SO WILL RESULT |
| IN PERMIT DELAYS. |
| |
| ALL OTHER COMMENTS IN REGARDS TO PRODUCT APPROVALS |
| STILL APPLY.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED FOR ALL PRODUCTS, FAC9B72, |
| WWW.FLORIDABUILDING.ORG.FLORIDA STATE PRODUCT |
| APPROVAL IS TO BE FOR THE 2004 CODE (NOT 2001 AS IS THE |
| CASE WITH THE OVERHEAD DOOR PRODUCT APPROVAL).ONLY |
| ONE SHEET OF THE NOA FOR THE INGERSOLL RAND DOOR WAS |
| SUBMITTED; ALL SHEETS REQUIRED.IF A FLORIDA STATE |
| PRODUCT APPROVAL IS NOT AVAILABLE FOR ANY OF THE |
| PRODUCTS YOU HAVE SELECTED, PLEASE CONTACT ME IN |
| REGARDS TO THE PROCEDURE FOR APPLICATION FOR LOCAL |
| PRODUCT APPROVAL. |
| |
| 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT |
| MATCH THE PLAN. |
| |
| THIRD REVIEW - THE ARCHITECT RESPONSE LETTER STATES |
| THAT INSIDE DIMENSIONS WERE USED FOR THE ENERGY CALCS. |
| SEE FBC 13, CHAPTER 2, DEFINITION OF FLOOR AREA, GROSS. |
| AS NEW ENERGY CALCS ARE REQUIRED, ELECTRIC REVIEW WILL |
| ALSO BE REQUIRED ON RESUBMITTAL.NOTE THAT ENERGY |
| CALCS ARE A STATUTORY REQUIREMENT AND STATUTORY |
| REQUIREMENTS CAN NEVER BE WAIVED OR PROVISO?D (PER |
| BUILDING OFFICIAL). |
| |
| 29.)FROM FIRST REVIEW - THE ENGINEER'S TITLE BLOCK IS |
| TO COMPLY WITH FAC61G15-23.002, VP BUILDINGS. |
| |
| 4/12/07MR. JOHN RYAN, ATTORNEY FOR FLORIDA BOARD OF |
| PROFESSIONAL ENGINEERS, CONFIRMED THE CERTIFICATE OF |
| AUTHORIZATION REQUIREMENT, FS471.023.THE ENGINEER'S |
| LETTER STATING THAT ENGINEERING IS NOT THE PRODUCT |
| OFFERED TO THE PUBLIC IS ACKNOWLEDGED.HOWEVER, WHEN |
| PRACTICING ENGINEERING THROUGH A COMPANY, A CERTIFICATE |
| OF AUTHORIZATION IS REQUIRED REGARDLESS OF PRODUCT |
| OFFERED.PLEASE CONTACT FBPE IF YOU NEED FURTHER |
| CLARIFICATION, 850-521-0500.AS THIS IS A STATUTORY |
| REQUIREMENT, THIS CANNOT BE WAIVED OR PROVISO'D; PLANS |
| MUST BE IN COMPLIANCE FOR PERMITTING. |
| |
| 30.)ADDRESSED. |
| |
| 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL |
| WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP |
| SHEETS. |
| |
| THIRD REVIEW - PANEL ENGINEERING STILL HAS A PHOTOCOPY |
| SIGNATURE.ALSO ALL INFORMATION REQUIRED BY |
| FAC61G15-23.002 IS REQUIRED TO BE ON EACH SHEET |
| (CERTIFICATE OF AUTHORIZATION). |
| |
| THE FOOTERS, SITEWORK, AND STRUCTURE (PANELS, STEEL |
| STRUCTURE) WERE ISSUED UNDER SEPARATE PERMITS.HAVE |
| THE CHANGES SHOWN ON THE CIVIL DRAWINGS BEEN MADE TO |
| THE ISSUED SITEWORK PERMIT?PLEASE PROVIDE A PERMIT |
| NUMBER FOR THE SITEWORK. |
| |
| THE PANEL PLANS AND STEEL STRUCTURAL PLANS ARE NOT |
| REQUIRED FOR THIS PERMIT AS THEY ARE INCLUDED IN THE |
| SCOPE OF WORK OF ANOTHER PERMIT.IF EITHER PLAN IS |
| CHANGED AS A RESULT OF THESE COMMENTS, THE CHANGES |
| SHOULD BE SUBMITTED AS REVISIONS TO THE ISSUED PERMIT. |
| ALSO HAVING A SET INCLUDED FOR REFERENCE (AS LONG AS IT |
| MATCHES THE PERMIT SET) WILL ASSIST IN PLAN REVIEW. |
| |
| 32-36.) ADDRESSED. |
| |
| 37.)SEE ATTACHED FS553.80(2)(B).NOTE THAT THIS IS A |
| MANDATORY FINE AND CANNOT BE WAIVED.NOTE THAT SOME |
| COMMENTS HAVE ALREADY BEEN MADE THREE TIMES (ENERGY |
| CALCS, LIFE SAFETY).A 4X PLAN REVIEW FEE HAS BEEN |
| CHARGED. |
| |
| NEW COMMENTS: |
| |
| 38.)SEE CIVIL SHEET 17 OF 29 PREPARED BY BOYER |
| SINGLETON.THIS SHEET HAS A DATE OF FEBRUARY 12, 2007, |
| NO CHANGES CLOUDED.THE SECOND BUILDING REVIEW WAS |
| JANUARY 30, 2007.THIS IS EITHER A NEW SHEET OR |
| CHANGES WERE MADE TO THE SHEET AND NOT INDICATED.ALL |
| CHANGES TO THE PLAN ARE TO BE CLEARLY INDICATED WITH |
| CLOUDS AND REVISION NUMBERS.WHEN CHANGES ARE |
| SUBMITTED A COMPLETE NEW PLAN REVIEW IS REQUIRED AS I |
| CANNOT DETERMINE SPECIFICALLY WHAT HAS CHANGED.NOTE |
| THAT THE ARCHITECT (CORRECTLY) CLOUDED THE PAGE NUMBER |
| TO SHOW NEW SHEETS. |
| |
| THE "TURNSTILE & HANDICAPPED SECURITY GATE" DETAIL ON |
| SHEET 17 IS ILLEGIBLE.AS THIS DETAIL IS REQUIRED TO |
| SHOW CODE COMPLIANCE (ACCESSIBILITY, EGRESS) PLEASE |
| PROVIDE LEGIBLE DETAILS. |
| |
| 4/12/07 ** IN THE MEETING WITH ARCHITECT ON 4/11/7, IT |
| WAS DISCUSSED THAT THIS DETAIL IS ALSO IN THE ELECTRIC |
| DRAWINGS.TO AVOID FURTHER PERMITTING DELAYS, DO NOT |
| ADDRESS THIS COMMENT AT THIS TIME.FOR THE FUTURE, |
| PLEASE NOTE THAT ALL DETAILS ARE REQUIRED TO BE |
| LEGIBLE!!!WHEN ISSUING THE PERMIT I WILL MAKE A NOTE |
| ON THE PLAN REFERRING TO THE APPROPRIATE ELECTRIC |
| SHEET. |
| |
| 39.)SHEET 18 OF 24 OF THE CIVIL DRAWINGS CONTAINS |
| INFORMATION IN REGARDS TO THE FUEL TANK.THIS IS |
| CURRENTLY IN THE PLAN REVIEW PROCESS UNDER SEPARATE |
| PERMIT.AS THIS SHEET HAS NOT BEEN REVIEWED BY ALL |
| TRADES FOR CODE COMPLIANCE, AND TO AVOID HAVING |
| INFORMATION IN THIS PERMIT WHICH CONFLICTS WITH OTHER |
| PERMITS, PLEASE REMOVE THIS SHEET. |
| |
| 40.)A3.0, THERE IS A NEW NOTE STATING THAT A |
| SATELLITE DISH IS TO BE INSTALLED AND A SLEEVE PROVIDED |
| IN THE TILT WALL PANEL.PROVIDE A DETAIL FOR THE |
| SATELLITE DISH AND A SPECIFICATION FOR THE SLEEVE.THE |
| WALL PANEL ENGINEER IS TO INCLUDE THIS INFORMATION IN |
| HIS STRUCTURAL DRAWINGS.SEE SHEET PN10; THERE IS A |
| NOTE ADDRESSING CORE DRILLING AFTER ERECTION.IT IS |
| NOT CLEAR IF THIS SLEEVE IS TO BE PROVIDED IN THE PANEL |
| WHEN IT IS CONSTRUCTED OR IF IT IS DRILLED AFTER |
| ERECTION.IN EITHER CASE, IT REQUIRES THE APPROVAL OF |
| THE WALL PANEL ENGINEER AND SHOULD ALSO BE ADDRESSED ON |
| HIS DRAWINGS SO THAT THE STRUCTURAL DRAWINGS ARE |
| CONSISTENT WITH THE ARCHITECTURAL DRAWINGS. |
| |
| **4/12/07** IN THE MEETING WITH THE ARCHITECT, IT WAS |
| AGREED THAT THE STRUCTURE/WALL PANEL PERMIT IS TO BE |
| REVISED AND THAT THIS PLAN WILL BE REVISED TO SHOW |
| METHOD OF ATTACHMENT AND ALSO WILL STATE THAT SHOP |
| DRAWINGS WILL BE REQUIRED PRIOR TO ISSUANCE. |
| |
| 41.)A4.0, ELEVATION AND ENTRY DETAIL, SEE |
| FBC11-4.13.7.WHEN SCALED, IT APPEARS TO MEET THE |
| MINIMUM REQUIREMENT EXACTLY BUT PLEASE NOTE THAT |
| REQUIREMENT ON THE PLAN. |
| |
| 42.)SEE THE STRUCTURAL PAGES PREPARED AND SIGNED BY |
| BRADLEY B. JOHNSON, PE.FS471, FAC61G15-23, THE SEAL |
| IS NOT LEGIBLE. |
| |
| **4/12/07**IN THE MEETING WITH THE ARCHITECT AND |
| CONTRACTOR, IT WAS AGREED THAT THE BEST COURSE OF |
| ACTION WOULD BE TO SUBMIT AS SOON AS POSSIBLE.THE |
| ENGINEER HAS ORDERED A NEW SEAL.IF NEWLY SEALED |
| SHEETS ARE NOT AVAILABLE AT THE TIME OF RESUBMITTAL, I |
| WILL ALLOW THE CONTRACTOR OR ARCHITECT TO BRING IN THE |
| NEW SHEETS (NEW SEAL ONLY, NO CHANGE TO DRAWING) AFTER |
| RESUBMITTAL PROVIDED THAT ALL OTHER COMMENTS FROM ALL |
| PLANS EXAMINERS HAVE BEEN SATISFIED. |
| |
| 43.)***NEW COMMENT 4/12/07***THE ARCHITECT'S |
| OBJECTION TO SHOWING COMPLIANCE WITH ALL EXITING |
| REQUIREMENTS FOR ACCESSIBLE EXITS IS NOTED.AS |
| DISCUSSED, THE NEW LIFE SAFETY PLAN WILL SHOW |
| COMPLIANCE AS REQUESTED ALTHOUGH THE ARCHITECT DOES NOT |
| AGREE WITH THE REQUIREMENT. |
| |
| HOWEVER, WE ARE IN AGREEMENT REGARDING ITEMS #17 AND |
| 18.MY UNDERSTANDING IS THAT THE ARCHITECT AGREES THAT |
| TWO ARE REQUIRED AND ONLY ACCESSIBLE EXIT SERVING THE |
| DISTRIBUTION AREAIS SHOWN ON THE PLAN, FOUR REVIEWS. |
| |
| |
| TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER |
| INDICATING HOW EACH ITEM WAS ADDRESSED WHEN |
| RESUBMITTING. |