Plan Review Notes For Permit 06090692 |
Permit Number |
06090692 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-29 14:19:10 | *****DENIED***** | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM | | FROM 10/31/2006 WAS ADDRESSED (ON/IN THE PLANS). | | | | | | | | 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH | | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE | | MAINTAINED AT ALL TIMES.PLEASE NOTE IN LANDSCAPING | | PLANS | | | | 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE | | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, | | VESSELS, EQUIPMENT, ETC.PLEASE NOTE ON FIRE SPRINKLER | | DRAWINGS | | | | 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | DEPARTMENT CONNECTIONS.NOTE ON FIRE SPRINKLER | | DRAWINGS | | | | 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK | | IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY.NOTE | | ON FIRE SPRINKLER DRAWINGS | | | | 19.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF | | TRAVEL TO EXITS.INCLUDE TRAVEL DISTANCE TO EXITS AS | | PER 2003 NFPA 101: 7.6.1 | | | | 22.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.NOTE ON | | FIRE SPRINKLER DRAWINGS | | | | 23.FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL | | STATION SERVICE.NOTE IN FIRE ALARM DRAWING | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|