2007-01-09 13:22:47 | ** UNSAT ** |
| |
| 2ND REVIEW |
| FED EX FREIGHT |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| ARE IN NEED OF PROVIDING MORE INFORMATION AND/OR |
| ADDRESSING. |
| |
| ** PLEASE SEE SOME NEW COMMENTS BASED ON SUBMITTALS AND |
| PLANS SUBMITTED. |
| |
| 1) NOTE: ** THIS IS NOT A COMMENT FOR KAMM CONSULTING, |
| HOWEVER IS BEING NOTED BY THIS REVIEWER. |
| PLEASE SEE THE VP SHEETS AND THE PN SHEETS CONTAIN |
| RAISED SEALS OVER PHOTO-COPIED SIGNATURES FOR THE |
| ENGINEERS ON EACH OF THESE WHICH IS NOT PERMITTED UNDER |
| FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE |
| CODE 61G15-23.002 |
| PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO. |
| **THIS WAS COMMENT #2 FROM THE PREVIOUS REVIEW. |
| PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS |
| OFFICE. |
| |
| 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| WHICH SPEAKS OF MAXIMUM TIMES PERMITTED ON THE TYPE OF |
| DEVICES INSTALLED. |
| PLEASE SEE NOTES ON E0.1 AND 2.1 IN SEVERAL PLACES |
| INDICATE OCCUPANCY TYPE DEVICES WITH 3HRS AND 4HRS FOR |
| MAXIMUM TIMES. PLEASE SEE THE SECTIONS AS NOTED ABOVE |
| AS THE MAXIMUM PERMITTED TIMES ON THESE TYPES OF |
| DEVICES IS 30MINS FROM THE LAST SENSING OF THE |
| OCCUPANT. |
| PLEASE ADJUST NOTES AND ALSO PLEASE BE SURE TO ADJUST |
| ALL DEVICES TO CONTAIN NOTES FOR THIS. |
| **PREVIOUS REVIEW NOTE #3 |
| |
| 3) NOTE: PLEASE SEE THE PERFORMANCE/ENERGY CALCULATIONS |
| SUBMITTED WHICH DO NOT PROVIDE THE INFORMATION NEEDED |
| FOR REVIEW. |
| PLEASE SEE RESPONSE LETTER SPEAKS OF EXTERIOR LIGHTING |
| CONTACTOR AND PHOTO-METRICS PLANS BY OTHERS? |
| PLEASE SEE ENERGY CALCULATIONS SUBMITTED INDICATE ALL |
| CONTROLS AS MANUAL ON/OFF WHEN PLANS INDICATE |
| OTHERWISE? |
| PLEASE PROVIDE INFORMATION FOR THE PERFORMANCE OF |
| LIGHTING DENSITIES. |
| **PREVIOUS REVIEW NOTE #4 |
| |
| 4) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| FEEDER(S) AND BRANCH CIRCUIT(S) PER 13-413.1.ABC.1.1. |
| RESPONSE LETTER MENTIONS TO SEE 4.1 AND 5.1, HOWEVER |
| 4.1 IS AIC CALCULATIONS, AND 5.1 WAS THE RISER DIAGRAM |
| SHEETS WHICH THIS REVIEWER COULD NOT LOCATED ANY |
| VOLTAGE DROP CALCULATIONS/ OR WORST CASE INFORMATION. |
| **PREVIOUS REVIEW #6 |
| |
| 5) NOTE: PLEASE SEE INFORMATION ON ACCESS CONTROL |
| SYSTEM DOES NOT YET PROVIDE ENOUGH INFORMATION. PLEASE |
| SEE NFPA-101 2003 |
| 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE OPENED READILY |
| FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| |
| 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| OPERATION FROM THE EGRESS SIDE. |
| 7.2.1.6 SPECIAL LOCKING ARRANGEMENTS. |
| PLEASE SEE FIRE REVIEW COMMENTS AS WELL AS THE RESPONSE |
| AND NOTE ON PLANS MENTIONS IN THE EVENT OF POWER |
| FAILURE UNDER EMERGENCY OR NORMAL POWER THE FIRE ALARM |
| AND SECURITY WILL NOT BE AFFECTED. |
| PLEASE SEE THIS IS BEING CONSIDERED AN EGRESS CONCERN |
| AND NOT THAT OF THE NOTE AS STATED. |
| ** PREVIOUS NOTE #9 |
| |
| 6) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS |
| FOR THE GENERATOR, ATS, WP ENCLOSURE AND FUEL TANKS. |
| PLEASE CORRELATE THESE WITH THE SUBMITTED PLANS. |
| SOME OF THESE WERE SUBMITTED, HOWEVER NOT FOR BOTH |
| TANKS AND PLEASE SEE SOME OF THESE DO NOT MATCH WITH |
| THE SUBMITTED PLANS. |
| PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A |
| RESPONSE FOR NOTE #11 FROM PREVIOUS REVIEW. |
| 90.7, 110.3 NEC |
| FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| ** PREVIOUS NOTE #11 |
| |
| 7) NOTE: PLEASE SEE 225.31-225.39, 702, 110.27 FOR |
| DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM THE |
| GENERATOR. THE RESPONSE LETTER MENTIONS TO BE BY |
| OTHERS; HOWEVER THIS INFORMATION IS REQUIRED AT THIS |
| TIME. PLEASE KNOW THIS IS A DISCONNECTING MEANS AND IS |
| NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION. THERE |
| ARE SEVERAL WAYS OF DOING THIS, HOWEVER THE USE OF THE |
| BREAKER INSIDE THE GEN UNIT WHICH MAY NOT MEET 110.27 |
| OR 702. |
| PLEASE PROVIDE MORE INFORMATION ON DISCONNECT, THIS MAY |
| BE LOCATED OUTSIDE MAIN ELECTRICAL ROOM ON BUILDING OR |
| IN MAIN ELECTRICAL ROOM. SIGNAGE WILL BE REQUIRED. |
| 702.8, 230.2E |
| ** PREVIOUS REVIEW NOTE #19 |
| |
| 8) NOTE: PLEASE SEE NOTE #20 FROM THE PREVIOUS REVIEW |
| WITH RESPECT TO SLAB DETAIL, HEIGHT MOUNTING ETC FOR |
| THE GENERATOR PER NFPA-110 CHAPTER 7. |
| PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A |
| RESPONSE FOR NOTE #20. |
| |
| 9) NOTE: PLEASE SHOW MORE INFORMATION FOR NEC 514. |
| PLEASE SEE 514.11(A) AND (C). PLEASE SEE COMMENTARY |
| WHICH SPEAKS OF THE LOCATION AND SIGNAGE REQUIREMENTS. |
| PLANS DO CONTAIN SOME NOTES FOR THESE HOWEVER PLEASE |
| PROVIDE MORE DETAILS. PLEASE SEE THAT THE PUSHBUTTON EM |
| CUT-OFF DEVICE SHOULD BE LOCATED AWAY FROM ANY HAZARD |
| BUT NOT MORE THAN 100FT.PLEASE SEE THE DISTANCE AND |
| THE LOCATION AS THIS IS BEING SHOWN BEHIND THE ADJACENT |
| BUILDING WHICH IS PER SCALE PERHAPS LESS THAN 20FT FROM |
| THE TANK GIVES CONCERN. PLEASE SEE FIRE MARSHAL'S |
| COMMENTS ALSO. |
| ** PREVIOUS REVIEW NOTE #22 |
| |
| 10) NOTE: PLEASE SEE PROVIDE MORE INFORMATION ON THE |
| CLASS AND DIVISION LOCATIONS SURROUNDING THE FUEL |
| DISPENSING. PLEASE SEE THE RESPONSE MENTIONED TO SEE |
| THE TWO SHEETS, HOWEVER THOSE SHEET 1.1 AND 1.4 ONLY |
| INDICATE THE DOTTED LINES FOR THE AREA. |
| PLEASE SEE NEC 500, 514 |
| FBC ADMIN SECTION 106.1.2 |
| ** PREVIOUS REVIEW NOTE #23. |
| |
| 11) NOTE: PLEASE CLARIFY THE LIGHTING FOR LIGHTS TO THE |
| PUBLIC RIGHT OF WAY. PLEASE SEE THE STAIRS LOCATED |
| OUTSIDE OF THE EGRESS DOORS WHICH WILL REQUIRE |
| EMERGENCY LIGHTING OF SOME SORT. |
| PLEASE ALSO SEE RESPONSE MENTIONS FOR SITE |
| PHOTO-METRICS TO BE PROVIDED BY OTHERS, HOWEVER PLEASE |
| SEE THE SITE LIGHTING IS BEING PERMITTED UNDER THIS |
| BASE BUILDING. |
| LS 101 7.8, 7.9 |
| ** PREVIOUS REVIEW NOTE #26. |
| |
| 12) NOTE: PLEASE SEE THE MISSING STRUCTURAL BUILDING |
| STEEL AND FIRE SPRINKLER LINE ATTACHMENT AS PART OF THE |
| GROUNDING ELECTRODE SYSTEM. |
| 250.50, 250.104. |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |