Plan Review Notes
Plan Review Notes For Permit 06090692
Permit Number 06090692
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-09 13:22:47** UNSAT **
  
 2ND REVIEW
 FED EX FREIGHT
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 ARE IN NEED OF PROVIDING MORE INFORMATION AND/OR
 ADDRESSING.
  
 ** PLEASE SEE SOME NEW COMMENTS BASED ON SUBMITTALS AND
 PLANS SUBMITTED.
  
 1) NOTE: ** THIS IS NOT A COMMENT FOR KAMM CONSULTING,
 HOWEVER IS BEING NOTED BY THIS REVIEWER.
 PLEASE SEE THE VP SHEETS AND THE PN SHEETS CONTAIN
 RAISED SEALS OVER PHOTO-COPIED SIGNATURES FOR THE
 ENGINEERS ON EACH OF THESE WHICH IS NOT PERMITTED UNDER
 FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002
 PLEASE SEE BUILDING REVIEW COMMENTS FOR THIS ALSO.
 **THIS WAS COMMENT #2 FROM THE PREVIOUS REVIEW.
 PLEASE KNOW ONE SET OF PLANS MAY BE RETAINED BY THIS
 OFFICE.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3
 WHICH SPEAKS OF MAXIMUM TIMES PERMITTED ON THE TYPE OF
 DEVICES INSTALLED.
 PLEASE SEE NOTES ON E0.1 AND 2.1 IN SEVERAL PLACES
 INDICATE OCCUPANCY TYPE DEVICES WITH 3HRS AND 4HRS FOR
 MAXIMUM TIMES. PLEASE SEE THE SECTIONS AS NOTED ABOVE
 AS THE MAXIMUM PERMITTED TIMES ON THESE TYPES OF
 DEVICES IS 30MINS FROM THE LAST SENSING OF THE
 OCCUPANT.
 PLEASE ADJUST NOTES AND ALSO PLEASE BE SURE TO ADJUST
 ALL DEVICES TO CONTAIN NOTES FOR THIS.
 **PREVIOUS REVIEW NOTE #3
  
 3) NOTE: PLEASE SEE THE PERFORMANCE/ENERGY CALCULATIONS
 SUBMITTED WHICH DO NOT PROVIDE THE INFORMATION NEEDED
 FOR REVIEW.
 PLEASE SEE RESPONSE LETTER SPEAKS OF EXTERIOR LIGHTING
 CONTACTOR AND PHOTO-METRICS PLANS BY OTHERS?
 PLEASE SEE ENERGY CALCULATIONS SUBMITTED INDICATE ALL
 CONTROLS AS MANUAL ON/OFF WHEN PLANS INDICATE
 OTHERWISE?
 PLEASE PROVIDE INFORMATION FOR THE PERFORMANCE OF
 LIGHTING DENSITIES.
 **PREVIOUS REVIEW NOTE #4
  
 4) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 FEEDER(S) AND BRANCH CIRCUIT(S) PER 13-413.1.ABC.1.1.
 RESPONSE LETTER MENTIONS TO SEE 4.1 AND 5.1, HOWEVER
 4.1 IS AIC CALCULATIONS, AND 5.1 WAS THE RISER DIAGRAM
 SHEETS WHICH THIS REVIEWER COULD NOT LOCATED ANY
 VOLTAGE DROP CALCULATIONS/ OR WORST CASE INFORMATION.
 **PREVIOUS REVIEW #6
  
 5) NOTE: PLEASE SEE INFORMATION ON ACCESS CONTROL
 SYSTEM DOES NOT YET PROVIDE ENOUGH INFORMATION. PLEASE
 SEE NFPA-101 2003
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE OPENED READILY
 FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.6 SPECIAL LOCKING ARRANGEMENTS.
 PLEASE SEE FIRE REVIEW COMMENTS AS WELL AS THE RESPONSE
 AND NOTE ON PLANS MENTIONS IN THE EVENT OF POWER
 FAILURE UNDER EMERGENCY OR NORMAL POWER THE FIRE ALARM
 AND SECURITY WILL NOT BE AFFECTED.
 PLEASE SEE THIS IS BEING CONSIDERED AN EGRESS CONCERN
 AND NOT THAT OF THE NOTE AS STATED.
 ** PREVIOUS NOTE #9
  
 6) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS
 FOR THE GENERATOR, ATS, WP ENCLOSURE AND FUEL TANKS.
 PLEASE CORRELATE THESE WITH THE SUBMITTED PLANS.
 SOME OF THESE WERE SUBMITTED, HOWEVER NOT FOR BOTH
 TANKS AND PLEASE SEE SOME OF THESE DO NOT MATCH WITH
 THE SUBMITTED PLANS.
 PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A
 RESPONSE FOR NOTE #11 FROM PREVIOUS REVIEW.
 90.7, 110.3 NEC
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
 ** PREVIOUS NOTE #11
  
 7) NOTE: PLEASE SEE 225.31-225.39, 702, 110.27 FOR
 DISCONNECTING MEANS REQUIRED FOR FEEDERS FROM THE
 GENERATOR. THE RESPONSE LETTER MENTIONS TO BE BY
 OTHERS; HOWEVER THIS INFORMATION IS REQUIRED AT THIS
 TIME. PLEASE KNOW THIS IS A DISCONNECTING MEANS AND IS
 NOT REQUIRED TO CONTAIN OVER CURRENT PROTECTION. THERE
 ARE SEVERAL WAYS OF DOING THIS, HOWEVER THE USE OF THE
 BREAKER INSIDE THE GEN UNIT WHICH MAY NOT MEET 110.27
 OR 702.
 PLEASE PROVIDE MORE INFORMATION ON DISCONNECT, THIS MAY
 BE LOCATED OUTSIDE MAIN ELECTRICAL ROOM ON BUILDING OR
 IN MAIN ELECTRICAL ROOM. SIGNAGE WILL BE REQUIRED.
 702.8, 230.2E
 ** PREVIOUS REVIEW NOTE #19
  
 8) NOTE: PLEASE SEE NOTE #20 FROM THE PREVIOUS REVIEW
 WITH RESPECT TO SLAB DETAIL, HEIGHT MOUNTING ETC FOR
 THE GENERATOR PER NFPA-110 CHAPTER 7.
 PLEASE SEE THE RESPONSE LETTER DOES NOT CONTAIN A
 RESPONSE FOR NOTE #20.
  
 9) NOTE: PLEASE SHOW MORE INFORMATION FOR NEC 514.
 PLEASE SEE 514.11(A) AND (C). PLEASE SEE COMMENTARY
 WHICH SPEAKS OF THE LOCATION AND SIGNAGE REQUIREMENTS.
 PLANS DO CONTAIN SOME NOTES FOR THESE HOWEVER PLEASE
 PROVIDE MORE DETAILS. PLEASE SEE THAT THE PUSHBUTTON EM
 CUT-OFF DEVICE SHOULD BE LOCATED AWAY FROM ANY HAZARD
 BUT NOT MORE THAN 100FT.PLEASE SEE THE DISTANCE AND
 THE LOCATION AS THIS IS BEING SHOWN BEHIND THE ADJACENT
 BUILDING WHICH IS PER SCALE PERHAPS LESS THAN 20FT FROM
 THE TANK GIVES CONCERN. PLEASE SEE FIRE MARSHAL'S
 COMMENTS ALSO.
 ** PREVIOUS REVIEW NOTE #22
  
 10) NOTE: PLEASE SEE PROVIDE MORE INFORMATION ON THE
 CLASS AND DIVISION LOCATIONS SURROUNDING THE FUEL
 DISPENSING. PLEASE SEE THE RESPONSE MENTIONED TO SEE
 THE TWO SHEETS, HOWEVER THOSE SHEET 1.1 AND 1.4 ONLY
 INDICATE THE DOTTED LINES FOR THE AREA.
 PLEASE SEE NEC 500, 514
 FBC ADMIN SECTION 106.1.2
 ** PREVIOUS REVIEW NOTE #23.
  
 11) NOTE: PLEASE CLARIFY THE LIGHTING FOR LIGHTS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE THE STAIRS LOCATED
 OUTSIDE OF THE EGRESS DOORS WHICH WILL REQUIRE
 EMERGENCY LIGHTING OF SOME SORT.
 PLEASE ALSO SEE RESPONSE MENTIONS FOR SITE
 PHOTO-METRICS TO BE PROVIDED BY OTHERS, HOWEVER PLEASE
 SEE THE SITE LIGHTING IS BEING PERMITTED UNDER THIS
 BASE BUILDING.
 LS 101 7.8, 7.9
 ** PREVIOUS REVIEW NOTE #26.
  
 12) NOTE: PLEASE SEE THE MISSING STRUCTURAL BUILDING
 STEEL AND FIRE SPRINKLER LINE ATTACHMENT AS PART OF THE
 GROUNDING ELECTRODE SYSTEM.
 250.50, 250.104.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-07 19:53:192007-01-07 19:53:19
 IN ELEC FOR REVIEW.