2007-01-30 11:14:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1-8.) ADDRESSED.
  
 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN
 SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION
 WILL BE REQUIRED.INFORMATIONAL ONLY; THIS IS NOT
 REQUIRED TO BE ADDRESSED AT THIS TIME.
  
 10.)ADDRESSED.
  
 11.)ADDRESSED.
  
 12.)S1 WAS DECLARED, BUT THE LIFE SAFETY PLAN SHOWS
 S2.PLEASE ADDRESS.
  
 13.)EXTRA FP1 SHEETS WERE SUBMITTED.PLEASE PROVIDE
 THREE ORIGINALS, ONE PUT INTO EACH ROLLED PERMIT SET.
  
  
 14-15.) ADDRESSED.
  
 16.)A LIFE SAFETY PLAN WAS PROVIDED IN RESPONSE TO
 THE PREVIOUS COMMENT.PLEASE ADDRESS THE FOLLOWING
 ITEMS:
  
 A. THE PURPOSE OF THE OVERLAPPING CIRCLES ON THE PLAN
 IS NOT CLEAR, AND NO PATH OF EGRESS TRAVEL WAS SHOWN.
 TYPICALLY THE WORST CASE TRAVEL DISTANCE IS SHOWN FROM
 EACH AREA TO THE REQUIRED EXITS.PLEASE REMOVE THE
 CIRCLES AS THEY MAKE THE PLAN DIFFICULT TO READ, OR
 CLARIFY THE PURPOSE.
  
 B. THE LIFE SAFETY PLAN STATES THAT TRAVEL DISTANCE IS
 UNLIMITED FOR S2 OCCUPANCY, BUT YOU HAVE DECLARED S1 ON
 SHEET A0.0.SEE FBC TABLE 1015.1, S1 HAS A MAXIMUM
 TRAVEL DISTANCE OF 250FEET, FULLY SPRINKLED BUILDING.
 ALSO SEE OTHER NOTES REGARDING ACCESSIBLE EXITS.
  
 C. OCCUPANT LOAD OF 63 HAS BEEN DECLARED FOR THE
 WAREHOUSE AREA.A0.0 DECLARES 32,720 SF.SEE FBC
 TABLE 1004.1.2, FBC 1004.1 STATES THAT OCCUPANT LOAD
 CANNOT BE LESS THAN THE TABLE, SO SHOULD BE A MINIMUM
 OF 65 BASED ON SF AREA.
  
 D. FBC1005.1, THE LOSS OF ANY ONE MEANS OF EGRESS SHALL
 NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50
 PERCENT OF THE REQUIRED CAPACITY.BASED ON DESIGN
 OCCUPANT LOAD FOR THE BUSINESS AREA, THE EXITING DOES
 NOT COMPLY.PLEASE ADDRESS.
  
 E. THE SCALE APPEARS TO BE 1/16.NOTE THE SCALE ON THE
 PLAN.PROVIDE OVERALL DIMENSIONS.
 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL
 BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY
 LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN
 AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS
 SHOWN.
  
 THE RESPONSE LETTER STATES THAT ALL EXITS ARE
 ACCESSIBLE.SEE FBC11-3, DEFINITION OF EGRESS, MEANS
 OF; DOES NOT INCLUDE STAIRS, STEPS, OR ESCALATORS.
  
 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE
 FBC1018.2.THIS WAS NOT ADDRESSED FOR ACCESSIBLE
 EXITS; ONLY ONE SHOWN.
  
 19.)A1.0 SHOWS A CHECK WRITING STAND, PLEASE NOTE ON
 THE PLAN THAT THIS AREA IS NOT OPEN TO THE PUBLIC.
  
 20-21.) ADDRESSED.
  
 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES
 REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF
 ACCESSIBLE EXITS.SEE OTHER COMMENTS.ENTRANCES WITH
 STAIRS DO NOT MEET THE REQUIREMENTS OF VERTICAL
 ACCESSIBILITY.
  
 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL
 COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE
 APART, SEE EXCEPTION 2.THERE ARE TO BE TWO ACCESSIBLE
 EXITS WHICH ARE REMOTELY LOCATED.ONLY ONE SHOWN ON
 THE PLAN (ALL OTHERS HAVE STAIRS).
  
 24.)ADDRESSED.
  
 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC.
  
 26.)THE COMMENT REGARDING REMOVABLE SHUTTERS WAS, I
 BELIEVE, ADDRESSED WITH SUBMITTAL OF IMPACT DOOR
 PRODUCT APPROVALS.IT APPEARS THAT IMPACT RATED
 PRODUCTS WILL BE USED.PLEASE NOTE THAT IF NONIMPACT
 PRODUCT APPROVALS ARE SUBMITTED ON THIRD REVIEW, A
 SHUTTER INSTALLATION PLAN WILL BE REQUIRED PRIOR TO
 PERMIT ISSUANCE.PLEASE CONTACT ME IF YOU WOULD LIKE
 TO PROPOSE THE USE OF REMOVABLE SHUTTERS TO DISCUSS
 THAT APPROVAL PROCESS.IF ALL PRODUCTS WILL BE IMPACT
 RATED, DISREGARD THE COMMENT.
  
 27.)PLEASE NOTE THAT PRODUCT APPROVALS FOR IMPACT
 DOORS WERE SUBMITTED.PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD, FBC*106.3.3.NO OTHER
 PRODUCT APPROVALS WERE SUBMITTED.NOTE THAT ANY
 PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR TO
 PERMIT ISSUANCE WILL REQUIRE SEPARATE PERMITS WITH
 SEPARATE FEES.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE EVALUATION REPORT
 (MIAMIDADE NOA IN THIS CASE) PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORGIF FLORIDA STATE PRODUCT
 APPROVAL IS NOT AVAILABLE, PLEASE CONTACT ME TO
 DISCUSS.
  
 NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.THIS MAY
 BE DONE WHEN THE ROOF PERMIT IS APPLIED FOR (WITH
 SEPARATE FEES BASED ON VALUE), OR MAY BE DONE NOW.
 CONTRACTOR OR DOR IS TO SELECT THE APPROVED ASSEMBLY.
  
  
 FOR ALL OTHER PRODUCTS, INCLUDING THE STANDING SEAM
 ROOF PANELS, IF THERE ARE DIFFERENT OPTIONS FOR
 INSTALLATION AND NOT ALL OF THEM ARE COMPLIANT FOR
 DESIGN PRESSURES FOR THIS BUILDING, CIRCLE THE
 INSTALLATION OR PARTICULAR OPTION YOU ARE USING SO THAT
 CODE COMPLIANCE CAN BE DETERMINED.
  
 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT
 MATCH THE PLAN.
  
 29.)ADDRESSED.
  
 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY
 CALCS, 604700 FBC13.
  
 31.)THE ENGINEER'S SIGNATURE IS A PHOTOCOPY, ORIGINAL
 WET SIGNATURE REQUIRED.SEE PANEL SHEETS AND VP
 SHEETS.
  
 NEW COMMENTS:
  
 32.)A1.2, SPECIFY DESIGN CRITERIA FOR STAIR AND GUARD
 RAIL RATHER THAN QUOTING A CODE SECTION.PROVIDE A
 DETAIL FOR THE STAIR HANDRAIL, GUARD RAILS, AND RAMP
 HANDRAIL.SEE FBC11-4.8.5, FBC11-4.9.4.WHEN SCALED,
 STAIR HANDRAIL EXTENSIONS ARE NOT LONG ENOUGH.
  
 CLARIFY 5-A4.0 HANDRAIL.IT APPEARS ON THE BOTTOM HALF
 OF THE RAMP BUT NOT THE TOP HALF.
  
 33.)5-A4.0, SHOW THE MINIMUM DIMENSION WHERE THE RAMP
 CHANGES DIRECTION.WHEN SCALED IT IS COMPLIANT AT
 60IN, FBC11-4.8.4(3).
  
 34.)SOILS REPORTS NOT NECESSARY AS THEY WERE PROVIDED
 WITH THE FOUNDATION PERMIT.
  
 35.)THE PANEL CALCS STATES THAT THE PROJECT NAME IS
 SEA HUNTER BOATS ON SOME PAGES.
  
 36.)S2.1, ENGINEER HAS SPECIFIED 69PSF FOR THE FLAT
 DECK ROOF, ZONES 2 AND 3.PROVIDE CALCULATIONS.
  
 37.)SEE ATTACHED FS553.80(2)(B).
  
  
 TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER
 INDICATING HOW EACH ITEM WAS ADDRESSED WHEN
 RESUBMITTING.