Plan Review Notes
Plan Review Notes For Permit 06090692
Permit Number 06090692
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-24 19:55:53----------------DENIED----------------
 1. M0.1 OUTSIDE AIR CALCULATIONS SCHEDULE: NOTE STATES
 "ALL RTU'S ARE EXISTING..." HOW ARE UNITS EXISTING ON
 NEW BUILDING? PLEASE CORRECT OR CLARIFY.
  
 2. M0.1 MECHANICAL NOTES: NOTE 7B STATES "ALL AIR
 CONDITIONING DUCTWORK SHALL BE OF 1 1/2"...
 FIBERGLASS..."THIS IS IN CONFLICT WITH NOTE 7C.
 PLEASE CLARIFY.
  
 3. M2.1 ROOMS 117 AND 119 SHOW TRANSFER JUMPERS FOR
 RETURN AIR. PROVIDE SIZES FOR FLEX DUCTS TO SHOW
 COMPLIANCE WITH FBC,M 601.4 EXCEPTION 1. DUCT SIZES ON
 FLEX SCHEDULE DO NOT MEET THE EXCEPTION REQUIREMENTS.
  
 4. M2.1 ROOM 120 THE DESIGN CFM OF THE DUCTED RETURN
 (500CFM) IS LESS THAN THAT OF THE SUPPLY (600CFM) PLUS
 THE TRANSFER RETURN AIR FROM ROOM 119 (80CFM) FOR A
 TOTAL OF 680CFM TO BE RETURNED. PLEASE SHOW BALANCED
 RETURN I THIS AREA PER FBC,M 601.4
  
 5. M0.1 NOTE #20: NO DETAIL FOR ROOF-TO-CURB OR
 CURB-TO-EQUIPMENT ATTACHMENTS WAS PROVIDED BY
 STRUCTURAL ENGINEER. SHOW COMPLIANCE WITH WIND LOAD
 REQUIREMENTS OF FBC 1509, 1522 AND CHAPTER 16.
  
 6. PLEASE SHOW LOCATIONS FOR CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2 AND FBC 1503.6. SECONDARY
 DRAIN PROTECTION IS ALSO REQUIRED PER FBC,M 307.2.3. IS
 THIS WHAT IS MEANT ON EQUIPMENT SCHEDULE NOTE #13?
  
 7. GUARDS SHALL BE PROVIDED WHERE EQUIPMENT REQUIRING
 SERVICE IS LOCATED WITHIN 10 FEET OF ROOF EDGE PER
 FBC,M 304.10
  
 8. M7.1 GRAVITY RELIEF HOOD DETAIL: THIS HOOD APPEARS
 TO BE FOR INKATE PURPOSES BUT IT IS SHOWN ATTACHED TO
 AN EXHAUST DUCT. THE BACKDRAFT DAMPER AS SHOWN WILL NOT
 ALLOW AIR TO ENTER THE BUILDING THROUGH THE HOOD.
 PLEASE CLARIFY.
  