Plan Review Notes
Plan Review Notes For Permit 06090692
Permit Number 06090692
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-24 10:36:28*** PLEASE SEE NOW THAT AN ADDRESS HAS BEEN CREATED,
 PLEASE PLACE ON TITLE BLOCKS FOR PLANS.
2006-10-24 10:31:25********* UNSAT **********
  
  
 1) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES
 RELEVANT TO PLANS AND DESIGNS ON THEOR RESPECTIVE
 SHEETS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED AT A MINIMUM:
 2002NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-20,
 2002 NFPA-110, 2000 NPPA-30A,2004 FBC .
 PLEASE BE AWARE OF ANY OTHER APPLICABLE CODES FROM
 OTHER REVIEWERS WHICH MAY BE REQUIRED.
  
 2) NOTE: PLEASE SEE "VP" BUILDING SHEETS AND SETS WHICH
 CONTAINEDRAISED SEALS OVER "PHOTO-COPIED" SIGNATURES.
 PLEASE SEE THIS COMMENT IS MADE WETHER OR NOT COMMENT
 IS MADE BY ANY OTHER REVIEWER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 FLORIDA STATUTES 471.025, PLEASE ALSO SEE MISSING
 REQUIRED TITLE BLOCK INFORMATION.
  
 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE NO MORE
 THAN 4HRS IS PERMITTED ON OVER-RIDE DEVICES. (SOME
 SHOWN AS 12HRS). PLEASE SEE OTHER AREAS WHERE A TIMED
 OR OCCUPANT TYPE DEVICE IS NOT INDICATED. PLEASE
 CLARIFY THE USE OF THE MOMNETARY CONTACTS, FOR AREAS OF
 INGRESS/EGRESS.THE OCCUPANT MUST BE ABLE TO OVER RIDE
 ANY TIME OF DAY SCHEDULEING DEVICE AND SEE THE LIGHTING
 BEING CONTROLLED. (TIMES OR SENSOR TYPE). PLEASE SEE
 SYSMBOL LEGEND NEEDS TO INDICATE THE MAX AMOUNT OF
 TIMES ON DEVICE WHICH ARE SHOWN ON THIS LEGEND, HOWEVER
 NOT ON PLANS.
 (30MINS MAX OS, 4HRS MAX TIMER TYPE)
  
 4) NOTE: PLEASE PROVIDE ALL LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1, TBALES
 415.2.C.1, 415.2.B1, AS SPACE BY SPACE WILL BE REQUIRED
 FOR SOME AREAS.
 PLEASE SEE METHOD "A" AS SUBMITTED DOES NOT SHOW
 THESE.
  
 5) NOTE: PLEASE SEE NO PLANS, DOCUMENTS ETC MAY CONTAIN
 "WHITE-OUT" OF ANY KIND ON SAID DOCUMENTS WITH
 HANDWRITTEN ITEMS OVER SUCH SHEETS. PLEASE SEE ENERGY
 CALCULATIONS.
 FS471
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR
 WORST CASE FOR EACH FOR FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE FBC 13-413.1.ABC.1.1 &.1.2.
  
 7) NOTE: PLEASE SEE SYMBOLSHOWN IN STORAGE/SPRINKLER
 ROOM ON 3.1, AND 2.1 APPEARS TO BE THAT OF A
 TRANSFORMER, YET THIS IS UNCLEAR AT THIS TIME.??
 FBC ADMIN SECT 106.1.2
  
 8) NOTE: PLEASE SEE IT WILL NOT BE PERMITTED THAT THE
 ONLY ACCESS TO THE MAIN ELECTRICAL ROOM IS THROUGH A
 STORAGE ROOM AND AREA. THESE TYPES OF ROOMS DO NOT
 TYPICALLY PROVIDE THE READY ACCESS TO THE ELECTRICAL
 EQUIPMENT IN THE QUICK TIME WHICH MAY BE NEED IN THE
 CASE OF AN EMERGENCY FOR FIRE DEPARTMENT OR ANY OTHER
 PERSONNEL TRYING TO SHUT OFF THE POWER. PLEASE SEE THAT
 RELOCATION OR ACCESS SEPARATELY FOR ROOM WILL BE
 REQUIRED AT THIS TIME.
 230.70,110.26, 408.7,90.4
  
 9) NOTE: PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS WIHT
 RESPECT TO ACCESS CONTROL SYSTEM WHICH WILL REQUIRE
 ADDITIONAL INFORMATION. PLEASE INDICATE THAT IN THE
 EVENT OF AN EMERGENCY OR FAILURE OF NORMAL POWER EGRESS
 FROM THE BUILDING WILL NOT BE AFFECTED. PLEASE SEE LS
 101. SEE FIRE REVIEW COMMENTS.
  
 10) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.3. PLEASE
 INDICATE THE MIN LEVELS FOR DB RATINGS OF HORNS/ OR
 COMBO DEVICES.PLEASE SEE SCHEDULE INDICATES A
 POSSIBLE OF 15CD MIN, HOWEVER AS INDICATE ON PLANS AND
 ADA REQUIREMENTS, A MIN OF 75 CD IS REQUIRED. PLEASE
 PROVIDE AND COMPLETE THE LAYOUT OF THE FA DEVICES ON
 PLANS. THE 2ND AND THIRD SECTIONS DO NOT APPEAR ON FA
 SHEETS.
 11-4.28.3(4).
  
 11) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE SPECS/CUT
 SHEETS FOR ALL OF THE FOLLOWING. GENERATOR, FUEL
 TANK(REVIEW BY OTHERS), ATS, FIRE PUMP AND FIRE PUMP
 CONTROLLER. PLEASE SEE AS NONE OF THESE ARE SUBMITTED
 AT THIS TIME NOT REVIEW FOR SOME CODE REQUIRED ITMES
 CAN EB DONE.
 110.3, 90.7.
  
 12) NOTE: PLEASE INDICATE ALL OCP DEVICE SIZES AT THE
 GEN. PLEASE SEE SHEET7.3 INDICATES A BREAKER FOR FIRE
 PUMP AT GEN AS G-1 , YET THE RISER DOES NOT INDICATE
 THIS BREAKER AT ALL ON GEN.
 PLEASE SEE 445.13 AS THE SIZING OF THE FEEDERS CAN NOT
 BE VERIFIED AT THIS TIME.
  
 13) NOTE: PLEASE SEE THE GEN SEEMS IT WILL FEED A FIRE
 PUMP, THE STAND-BY FOR THIS BUILDING AND THE POSSIBLE
 STAND-BY FOR AN ADDITIONAL LOCATION, HOWEVER A COMPLETE
 LOAD SUMMARY AND LOAD SHEDDDING DETAILS HAVE NOT BEEN
 PROVIDED AT THIS TIME. PLEASE SEE THE LOAD ON THE MD IS
 THE ONLY LOAD SHOWN AT THIS TIME. PLEASE PROVIDE A LOAD
 SUMMARY FOR THE GEN AS THIS IS A LEGALLY REQUIRED
 STAND-BY UNIT.
 701.6,6.3 OF NFPA-110, NFPA-20 9.6.1.1 ETC.,THESE
 ITEMS CAN NOT BE REVIEWED AT THIS TIME.
  
 14) NOTE: PLEASE PROVIDE ALL MINIMUM FUEL CONSUMPTION
 FOR THEGENERATOR AS THIS FEED THE FIRE PUMP AND
 SYSTEM AS SHOWN NEEDS TO MEET THE MINIMUM OF HRS FOR
 100% LOAD INCLUDING ALL OTHER LOADS 9.6.2.2.
 CAN NOT REVIEW AT THIS TIME.
  
 15) NOTE: PLEASE SUBMIT ALL THE INFORMATION FOR FIRE
 PUMP SERVICE, LOCATION, LOCKED ROTOR OCP SIZE ETC.
 PLEASE SEE PLANS AND RISER DO NOT SEEM TO INDICATE ANY
 INFORMATION FOR THE FIRE PUMP. PLEASE SEE FP SHEETS
 ALSO DO NOT INDICATE ANY FP?PLEASE SEE 2003 NFPA-20
 CHAPTER 9 FOR DISCONNECTING MEANS, ISOLATION SWITCH
 REQUIREDETC ETC.
  
 16) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE A DETAIL FOR
 SELECTIVE COORDINATION. 110.9/240.12.
 PLEASE SEE NEC 701.6, 700.5 AND NFPA-110, 6.5.2 ETC FOR
 ATS AND ALL OTHER EQUIPMENT ASSOCIATED WITH ELECTRICAL
 SYSTEM.
  
 17) NOTE: PLEASE VERFIY WITH MANUFACTURE THE GENERATOR
 GROUNDING SCENARIO, AS IT IS KNOWN TO THIS OFFICE SOME
 OF THESE DEPENDING ON THE MANUFACTURE ARE SHIPPED AND
 WIRED FOR SEPARATELY DERIVED SYSTEM, PLEASE MAKE ANY
 ADJUSTMENTS AS NEED.
 90.7., 250.20, 250.50, ETC
  
 18) NOTE: PLEASE CORRELATE CIRCUITING FOR PANEL FD,
 PANEL "LB" DOES NOT SHOW FEEDING OF THIS PANEL .
 PLEASE SEE CIRCUITS FOR OTHER ITEMS SHOWN ON SCHEDULE.
 240.4,310.16,408.4,
 FBC 106.3.5.1.2. ADMIN SECT.
  
 19) NOTE: PLEASE SEE MISSIGN A DISONNECTING MEANS FOR
 FEEDERS FROM GENERATOR INTO BLDG LOCATED IN CLOSE
 PROXIMITY OF OTHER MAINS OR MEETINGEXCEPTIONS UNDER
 CODE, HOWEVER SYSTEM IS NOT KNOWN AT THIS TIME
 CLASSIFICATION OF BACK UP POWER IS NOT CLEAR. PLEASE
 ALSO KNOW AS INFORMATION FOR THE GEN AND W/P ENCLOSURE
 AND ACCESS IS ALSO NOT KNOW AT THIS TIME.
 225.31-225.39
 700, 701, 702 ?
  
 20) NOTE: PLEASE SEE NOT INFORMATION FOR LOCATION,
 ELEVATION, MOUNTING , SLAB DETAIL ETC COULD BE LOCATED
 ON PLANS. PLEASE SEE NFPA-110 2002 CHAPTER 7, AS MANY
 OF THESE SCETIONS APPLY, HOWEVER AS NOTHING COULD BE
 LOCATED FOR THIS, A REVIEW FOR COMPLIANCE COULD NOT BE
 DONE AT THIS TIME.
  
 21) NOTE: PLEASE SEE MD AS THIS SHOWS A NEUTRAL
 CONDUCTOR BEING SHOWN FEEDING THE TRANSFORMER WHICH IS
 A SD SYSTEM. PLEASE SEE 250.30, 250.20 ETC
  
 22) NOTE: PLEASE SEE ANY COMMENTS WITH RESPECT THE EM
 SHUT OFF OF POWER FOR THEFD PANEL. PLEASE SEE 514
  
 23) NOTE: PLEASE PROVIDE A LAYOUT AND SHOW ALL
 HAZARDOUS LOCATIONSON PLANS.
 500. CLASS AND DIVISIONS.
  
 24) NOTE: PLEASE SEE MECH REVIEW NOTES FOR SEPARATE
 FUEL PERMIT REQUIRED.
  
 25: ) NOTE: PLEASE SEE THE GEN SPECIFICATIONS ON 7.3 DO
 NOT LIST THE OTHER OCP/ BREAKERS ON GEN AS SHOWN ON
 RISER.
  
 26) ) NOTE: PLEASE PROVIDE EM BATTERY BACK UP
 FIXTURE(S) OF SOME TYPE LEADING TO THE PUBLIC RIGHT OF
 WAY. PLEASE PROVIDE PHOTO-METRICS FOR EGRESS PATHS
 UNDER NORMAL AND UNDER EMERGENCY POWER. PLEASSE SEE
 NFPA-101 7.8.1.3, 7.9.2.2, PLEASE SEE STAIR AREAS
 LEADING TO THE OUTSIDE.
  
 27) NOTE: PLEASE SEE SOME SHEETS IN SETS ARE PLACED IN
 SETS BACKWARDS. PLEASE SEE THE FOLLOWING NOTE.
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW , PLEASE KNOW THERE MAY BE FURTHER
 COMMENTS UPON NEXT REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-10-22 19:47:55ONE SET IN ELEC FOR REVIEW