2006-10-24 10:36:28 | *** PLEASE SEE NOW THAT AN ADDRESS HAS BEEN CREATED, |
| PLEASE PLACE ON TITLE BLOCKS FOR PLANS. |
2006-10-24 10:31:25 | ********* UNSAT ********** |
| |
| |
| 1) NOTE: PLEASE LIST ALL OF THE FOLLOWING CODES |
| RELEVANT TO PLANS AND DESIGNS ON THEOR RESPECTIVE |
| SHEETS. |
| PLEASE SEE THE FOLLOWING ARE REQUIRED AT A MINIMUM: |
| 2002NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-20, |
| 2002 NFPA-110, 2000 NPPA-30A,2004 FBC . |
| PLEASE BE AWARE OF ANY OTHER APPLICABLE CODES FROM |
| OTHER REVIEWERS WHICH MAY BE REQUIRED. |
| |
| 2) NOTE: PLEASE SEE "VP" BUILDING SHEETS AND SETS WHICH |
| CONTAINEDRAISED SEALS OVER "PHOTO-COPIED" SIGNATURES. |
| PLEASE SEE THIS COMMENT IS MADE WETHER OR NOT COMMENT |
| IS MADE BY ANY OTHER REVIEWER. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, |
| FLORIDA STATUTES 471.025, PLEASE ALSO SEE MISSING |
| REQUIRED TITLE BLOCK INFORMATION. |
| |
| 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE NO MORE |
| THAN 4HRS IS PERMITTED ON OVER-RIDE DEVICES. (SOME |
| SHOWN AS 12HRS). PLEASE SEE OTHER AREAS WHERE A TIMED |
| OR OCCUPANT TYPE DEVICE IS NOT INDICATED. PLEASE |
| CLARIFY THE USE OF THE MOMNETARY CONTACTS, FOR AREAS OF |
| INGRESS/EGRESS.THE OCCUPANT MUST BE ABLE TO OVER RIDE |
| ANY TIME OF DAY SCHEDULEING DEVICE AND SEE THE LIGHTING |
| BEING CONTROLLED. (TIMES OR SENSOR TYPE). PLEASE SEE |
| SYSMBOL LEGEND NEEDS TO INDICATE THE MAX AMOUNT OF |
| TIMES ON DEVICE WHICH ARE SHOWN ON THIS LEGEND, HOWEVER |
| NOT ON PLANS. |
| (30MINS MAX OS, 4HRS MAX TIMER TYPE) |
| |
| 4) NOTE: PLEASE PROVIDE ALL LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.1, TBALES |
| 415.2.C.1, 415.2.B1, AS SPACE BY SPACE WILL BE REQUIRED |
| FOR SOME AREAS. |
| PLEASE SEE METHOD "A" AS SUBMITTED DOES NOT SHOW |
| THESE. |
| |
| 5) NOTE: PLEASE SEE NO PLANS, DOCUMENTS ETC MAY CONTAIN |
| "WHITE-OUT" OF ANY KIND ON SAID DOCUMENTS WITH |
| HANDWRITTEN ITEMS OVER SUCH SHEETS. PLEASE SEE ENERGY |
| CALCULATIONS. |
| FS471 |
| |
| 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR |
| WORST CASE FOR EACH FOR FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE FBC 13-413.1.ABC.1.1 &.1.2. |
| |
| 7) NOTE: PLEASE SEE SYMBOLSHOWN IN STORAGE/SPRINKLER |
| ROOM ON 3.1, AND 2.1 APPEARS TO BE THAT OF A |
| TRANSFORMER, YET THIS IS UNCLEAR AT THIS TIME.?? |
| FBC ADMIN SECT 106.1.2 |
| |
| 8) NOTE: PLEASE SEE IT WILL NOT BE PERMITTED THAT THE |
| ONLY ACCESS TO THE MAIN ELECTRICAL ROOM IS THROUGH A |
| STORAGE ROOM AND AREA. THESE TYPES OF ROOMS DO NOT |
| TYPICALLY PROVIDE THE READY ACCESS TO THE ELECTRICAL |
| EQUIPMENT IN THE QUICK TIME WHICH MAY BE NEED IN THE |
| CASE OF AN EMERGENCY FOR FIRE DEPARTMENT OR ANY OTHER |
| PERSONNEL TRYING TO SHUT OFF THE POWER. PLEASE SEE THAT |
| RELOCATION OR ACCESS SEPARATELY FOR ROOM WILL BE |
| REQUIRED AT THIS TIME. |
| 230.70,110.26, 408.7,90.4 |
| |
| 9) NOTE: PLEASE SEE POSSIBLE FIRE REVIEW COMMENTS WIHT |
| RESPECT TO ACCESS CONTROL SYSTEM WHICH WILL REQUIRE |
| ADDITIONAL INFORMATION. PLEASE INDICATE THAT IN THE |
| EVENT OF AN EMERGENCY OR FAILURE OF NORMAL POWER EGRESS |
| FROM THE BUILDING WILL NOT BE AFFECTED. PLEASE SEE LS |
| 101. SEE FIRE REVIEW COMMENTS. |
| |
| 10) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.3. PLEASE |
| INDICATE THE MIN LEVELS FOR DB RATINGS OF HORNS/ OR |
| COMBO DEVICES.PLEASE SEE SCHEDULE INDICATES A |
| POSSIBLE OF 15CD MIN, HOWEVER AS INDICATE ON PLANS AND |
| ADA REQUIREMENTS, A MIN OF 75 CD IS REQUIRED. PLEASE |
| PROVIDE AND COMPLETE THE LAYOUT OF THE FA DEVICES ON |
| PLANS. THE 2ND AND THIRD SECTIONS DO NOT APPEAR ON FA |
| SHEETS. |
| 11-4.28.3(4). |
| |
| 11) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURE SPECS/CUT |
| SHEETS FOR ALL OF THE FOLLOWING. GENERATOR, FUEL |
| TANK(REVIEW BY OTHERS), ATS, FIRE PUMP AND FIRE PUMP |
| CONTROLLER. PLEASE SEE AS NONE OF THESE ARE SUBMITTED |
| AT THIS TIME NOT REVIEW FOR SOME CODE REQUIRED ITMES |
| CAN EB DONE. |
| 110.3, 90.7. |
| |
| 12) NOTE: PLEASE INDICATE ALL OCP DEVICE SIZES AT THE |
| GEN. PLEASE SEE SHEET7.3 INDICATES A BREAKER FOR FIRE |
| PUMP AT GEN AS G-1 , YET THE RISER DOES NOT INDICATE |
| THIS BREAKER AT ALL ON GEN. |
| PLEASE SEE 445.13 AS THE SIZING OF THE FEEDERS CAN NOT |
| BE VERIFIED AT THIS TIME. |
| |
| 13) NOTE: PLEASE SEE THE GEN SEEMS IT WILL FEED A FIRE |
| PUMP, THE STAND-BY FOR THIS BUILDING AND THE POSSIBLE |
| STAND-BY FOR AN ADDITIONAL LOCATION, HOWEVER A COMPLETE |
| LOAD SUMMARY AND LOAD SHEDDDING DETAILS HAVE NOT BEEN |
| PROVIDED AT THIS TIME. PLEASE SEE THE LOAD ON THE MD IS |
| THE ONLY LOAD SHOWN AT THIS TIME. PLEASE PROVIDE A LOAD |
| SUMMARY FOR THE GEN AS THIS IS A LEGALLY REQUIRED |
| STAND-BY UNIT. |
| 701.6,6.3 OF NFPA-110, NFPA-20 9.6.1.1 ETC.,THESE |
| ITEMS CAN NOT BE REVIEWED AT THIS TIME. |
| |
| 14) NOTE: PLEASE PROVIDE ALL MINIMUM FUEL CONSUMPTION |
| FOR THEGENERATOR AS THIS FEED THE FIRE PUMP AND |
| SYSTEM AS SHOWN NEEDS TO MEET THE MINIMUM OF HRS FOR |
| 100% LOAD INCLUDING ALL OTHER LOADS 9.6.2.2. |
| CAN NOT REVIEW AT THIS TIME. |
| |
| 15) NOTE: PLEASE SUBMIT ALL THE INFORMATION FOR FIRE |
| PUMP SERVICE, LOCATION, LOCKED ROTOR OCP SIZE ETC. |
| PLEASE SEE PLANS AND RISER DO NOT SEEM TO INDICATE ANY |
| INFORMATION FOR THE FIRE PUMP. PLEASE SEE FP SHEETS |
| ALSO DO NOT INDICATE ANY FP?PLEASE SEE 2003 NFPA-20 |
| CHAPTER 9 FOR DISCONNECTING MEANS, ISOLATION SWITCH |
| REQUIREDETC ETC. |
| |
| 16) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL |
| SERVICE EQUIPMENT. PLEASE PROVIDE A DETAIL FOR |
| SELECTIVE COORDINATION. 110.9/240.12. |
| PLEASE SEE NEC 701.6, 700.5 AND NFPA-110, 6.5.2 ETC FOR |
| ATS AND ALL OTHER EQUIPMENT ASSOCIATED WITH ELECTRICAL |
| SYSTEM. |
| |
| 17) NOTE: PLEASE VERFIY WITH MANUFACTURE THE GENERATOR |
| GROUNDING SCENARIO, AS IT IS KNOWN TO THIS OFFICE SOME |
| OF THESE DEPENDING ON THE MANUFACTURE ARE SHIPPED AND |
| WIRED FOR SEPARATELY DERIVED SYSTEM, PLEASE MAKE ANY |
| ADJUSTMENTS AS NEED. |
| 90.7., 250.20, 250.50, ETC |
| |
| 18) NOTE: PLEASE CORRELATE CIRCUITING FOR PANEL FD, |
| PANEL "LB" DOES NOT SHOW FEEDING OF THIS PANEL . |
| PLEASE SEE CIRCUITS FOR OTHER ITEMS SHOWN ON SCHEDULE. |
| 240.4,310.16,408.4, |
| FBC 106.3.5.1.2. ADMIN SECT. |
| |
| 19) NOTE: PLEASE SEE MISSIGN A DISONNECTING MEANS FOR |
| FEEDERS FROM GENERATOR INTO BLDG LOCATED IN CLOSE |
| PROXIMITY OF OTHER MAINS OR MEETINGEXCEPTIONS UNDER |
| CODE, HOWEVER SYSTEM IS NOT KNOWN AT THIS TIME |
| CLASSIFICATION OF BACK UP POWER IS NOT CLEAR. PLEASE |
| ALSO KNOW AS INFORMATION FOR THE GEN AND W/P ENCLOSURE |
| AND ACCESS IS ALSO NOT KNOW AT THIS TIME. |
| 225.31-225.39 |
| 700, 701, 702 ? |
| |
| 20) NOTE: PLEASE SEE NOT INFORMATION FOR LOCATION, |
| ELEVATION, MOUNTING , SLAB DETAIL ETC COULD BE LOCATED |
| ON PLANS. PLEASE SEE NFPA-110 2002 CHAPTER 7, AS MANY |
| OF THESE SCETIONS APPLY, HOWEVER AS NOTHING COULD BE |
| LOCATED FOR THIS, A REVIEW FOR COMPLIANCE COULD NOT BE |
| DONE AT THIS TIME. |
| |
| 21) NOTE: PLEASE SEE MD AS THIS SHOWS A NEUTRAL |
| CONDUCTOR BEING SHOWN FEEDING THE TRANSFORMER WHICH IS |
| A SD SYSTEM. PLEASE SEE 250.30, 250.20 ETC |
| |
| 22) NOTE: PLEASE SEE ANY COMMENTS WITH RESPECT THE EM |
| SHUT OFF OF POWER FOR THEFD PANEL. PLEASE SEE 514 |
| |
| 23) NOTE: PLEASE PROVIDE A LAYOUT AND SHOW ALL |
| HAZARDOUS LOCATIONSON PLANS. |
| 500. CLASS AND DIVISIONS. |
| |
| 24) NOTE: PLEASE SEE MECH REVIEW NOTES FOR SEPARATE |
| FUEL PERMIT REQUIRED. |
| |
| 25: ) NOTE: PLEASE SEE THE GEN SPECIFICATIONS ON 7.3 DO |
| NOT LIST THE OTHER OCP/ BREAKERS ON GEN AS SHOWN ON |
| RISER. |
| |
| 26) ) NOTE: PLEASE PROVIDE EM BATTERY BACK UP |
| FIXTURE(S) OF SOME TYPE LEADING TO THE PUBLIC RIGHT OF |
| WAY. PLEASE PROVIDE PHOTO-METRICS FOR EGRESS PATHS |
| UNDER NORMAL AND UNDER EMERGENCY POWER. PLEASSE SEE |
| NFPA-101 7.8.1.3, 7.9.2.2, PLEASE SEE STAIR AREAS |
| LEADING TO THE OUTSIDE. |
| |
| 27) NOTE: PLEASE SEE SOME SHEETS IN SETS ARE PLACED IN |
| SETS BACKWARDS. PLEASE SEE THE FOLLOWING NOTE. |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| SUBMITTED FOR REVIEW , PLEASE KNOW THERE MAY BE FURTHER |
| COMMENTS UPON NEXT REVIEW. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
2006-10-22 19:47:55 | ONE SET IN ELEC FOR REVIEW |