2006-10-23 10:52:13 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| 561-233-5025 FOR MORE INFORMATION. |
| |
| 3.)THE COPY OF THE PLAT PROVIDED IS NOT RECORDED. |
| PLEASE ADVISE AS TO STATUS.IF THIS IS RECORDED, |
| PROVIDE PLAT FILING INFORMATION (BOOK/PAGE). |
| |
| 4.)THE PLAT PROVIDED AND THE PROPOSED PLAT LINES ON |
| THE OVERALL SITE PLAN PREPARED BY BOWYER SINGLETON DO |
| NOT MATCH.FOR INSTANCE, THE CIRCULAR SECTION AT THE |
| END OF THE ROAD (PARCEL G) DOES NOT APPEAR ON THE |
| OVERALL SITE PLAN.THE PLAT LINES ARE INCOMPLETE ON |
| THE OVERALL SITE PLAN. |
| |
| 5.)THE APPLICATION REFERS TO TWO DIFFERENT PARCEL ID |
| NUMBERS.YOU CANNOT CROSS PROPERTY LINES.PROVIDE |
| INFORMATION IN REGARDS TO THE LOCATION OF THE TWO |
| PARCELS, ENDING IN 3010 AND 3040.OUR GIS RECORDS |
| SHOWS 3010 AS A VERY SMALL PARCEL (POSSIBLY A ROAD) |
| GOING THROUGH THE MIDDLE OF THE LARGER PARCEL, 3040. |
| PLEASE CONTACT ME TO DISCUSS IF YOU ARE UNSURE AS TO |
| HOW TO GET THIS MATTERS RESOLVED. |
| |
| 6.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO |
| ONE OR MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE |
| DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQFT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS |
| OF CONSTRUCTION |
| |
| ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION |
| SERVICES MANAGER - TEL: |
| 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS |
| MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL |
| SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. |
| |
| 7.)THERE ARE TWO FULL SETS OF CIVILS WITH DIFFERENT |
| DATES.MANY SHEETS APPEAR UNNECESSARY AS THEY ARE FOR |
| OTHER BUILDINGS.THERE IS ALREADY A SITEWORK PERMIT |
| PENDING.PLEASE COORDINATE WITH ENGINEERING; ANY CIVIL |
| SHEETS REQUIRED IN THIS PACKAGE TO SHOW CODE COMPLIANCE |
| IS TO MATCH OTHER APPROVED DRAWINGS.ALSO NOTE THAT |
| THERE ARE DETAILS FROM THE CITY OF RIVIERA BEACH. |
| |
| 8.)RADON FEES DUE, FS553.721.SEE ATTACHED. |
| |
| 9.)A SEPARATE PERMIT WILL BE REQUIRED FOR THE SIGN |
| SHOWN ON A-0.1.SEPARATE PLANS AND PERMIT APPLICATION |
| WILL BE REQUIRED.NOTE THAT WIND DESIGN CRITERIA |
| FBC1603.1.4 WILL BE REQUIRED.DESIGN CRITERIA SHOWN |
| DOES NOT PROVIDE ALL REQUIRED INFORMATION. |
| |
| 10.)THE ACCESSIBLE ROUTE FROM THE PUBLIC WAY IS SHOWN |
| ON A-0.1, SHOW SLOPE AND WIDTH FBC11-4.1.2(1). |
| |
| 11.)S2 DECLARED, SEE FBC302; IT APPEARS THAT THIS IS |
| A MIXED USE DUE TO THE 5000 SF OF BUSINESS AREA, |
| FBC302.3. |
| |
| 12.)S2 DECLARED, SEE FBC311.3, DEFINITION IS FOR |
| NON-COMBUSTIBLE STORAGE.PROVIDE INFORMATION IN |
| REGARDS TO WHAT WILL BE STORED AND WHAT ACTIVITY WILL |
| TAKE PLACE IN THIS BUILDING.NOTE THAT PACKAGING MUST |
| BE ADDRESSED AS WELL AS THE ITEMS STORED. |
| |
| 13.)THE FEDEX FREIGHT SITE PLAN (CIVIL) SHOWS A 10FT |
| CANOPY.SEE FBC502, DEFINITION OF AREA, BUILDING. |
| PLEASE CLARIFY WHAT THIS IS, AND SHOULD THIS BE |
| INCLUDED IN BUILDING AREA? |
| |
| 14.)EXTRA FP1 SHEETS WERE SUBMITTED; NOT CLEAR AS TO |
| WHY.PLEASE PROVIDE ONLY THREE COMPLETE ORIGINAL SETS |
| FOR PERMITTING, COLLATED. |
| |
| 15.)ELECTRIC SHEETS SHOW EXIT LIGHTS LEADING TO THE |
| WAREHOUSE AREA, NONE AT DOORS TO THE OUTSIDE.SEE |
| FBC1006.3. |
| |
| 16.)PROVIDE A LIFE SAFETY PLAN, FBC*106.3.5.1.1(6) |
| AND (7).INCLUDE THE FOLLOWING: |
| OCCUPANT LOAD FOR EACH AREA, FBC302. |
| EGRESS CAPACITIES, FBC1005. |
| EXIT LIGHTS, FBC1006.3. |
| EXITING INFORMATION, FBC10. |
| ANY OTHER INFORMATION REQUIRED TO DETERMINE CODE |
| COMPLIANCE |
| |
| 17.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF EGRESS SHALL |
| BE PROVIDED IN THE SAME NUMBER AS REQUIRED FOR EXITS BY |
| LOCAL BUILDING/LIFE SAFETY REGULATIONS. A RAMP IS SHOWN |
| AT THE BUILDING ENTRANCE, NO OTHER ACCESSIBLE EXITS |
| SHOWN. |
| |
| 18.)THIS BUILDING REQUIRES MORE THAN ONE EXIT, SEE |
| FBC1018.2. |
| |
| 19.)A1.0 SHOWS A CHECK WRITING STAND, REFERS TO DTL |
| 4/A2.01.I COULD NOT LOCATE THAT SHEET.PROVIDE A |
| DETAIL, OR CHANGE REFERENCE, AND SHOW ACCESSIBILITY |
| FBC11-7.2. |
| |
| 20.)BREAK ROOM IS SHOWN AS POD AREA, WHAT DOES THIS |
| MEAN? |
| |
| 21.)A1.0 SHOWS AN AREA OF RESCUE.DO YOU MEAN AREA |
| OF RESCUE ASSISTANCE?IT IS ACCEPTABLE TO EXCEED CODE, |
| BUT NOTE THAT THIS IS NOT REQUIRED FBC11-4.1.3(9) |
| EXCEPTION.ALSO THIS IS FOR EXITS FROM OCCUPIABLE |
| LEVELS ABOVE OR BELOW THE LEVEL OF THE MEANS OF |
| ACCESSIBLE EXIT DISCHARGE.THIS IS THE LEVEL OF |
| ACCESSIBLE EXIT DISCHARGE, SO AN ACCESSIBLE EXIT IS |
| REQUIRED. |
| |
| 22.)FBC11-4.1.3(8)(A)(II), ACCESSIBLE ENTRANCES |
| REQUIRED AT LEAST EQUIVALENT TO THE NUMBER OF |
| ACCESSIBLE EXITS. |
| |
| 23.)EXIT OR EXIT ACCESS DOORWAY ARRANGEMENT SHALL |
| COMPLY WITH FBC1014.2 OR FBC1014.2.2., SHOW DISTANCE |
| APART, SEE EXCEPTION 2. |
| |
| 24.)S2.1, CONCRETE NOTE 1, REFERS TO ACI318-95, |
| PLEASE USE CURRENT STANDARD.CHECK ALL REFERENCES. |
| |
| 25.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC. |
| |
| 26.)IMPACT PROTECTION REQUIRED.NONIMPACT STOREFRONT |
| PRODUCT APPROVALS WERE SUBMITTED.SEE ATTACHED POLICY, |
| ITEM 13, IN REGARDS TO IMPACT PROTECTION ON COMMERCIAL |
| BUILDINGS.USE IF REMOVABLE SHUTTERS ON COMMERCIAL |
| BUILDINGS MUST BE APPROVED BY THE BUILDING OFFICIAL. |
| |
| |
| 27.)IF YOU ARE USING HURRICANE SHUTTERS, SEE ATTACHED |
| SCHEDULE FOR INSTALLATION.PROVIDE PRODUCT APPROVALS |
| AND ALL REQUIRED INFORMATION TO DETERMINE CODE |
| COMPLIANCE. |
| |
| 28.)SQUARE FOOT AREAS ON THE ENERGY CALCS DO NOT |
| MATCH THE PLAN. |
| |
| 29.)THE ENGINEER'S TITLE BLOCK IS TO COMPLY WITH |
| FAC61G15-23.002, VP BUILDINGS. |
| |
| 30.)INCLUDE THE CORRECT JURISDICTION ON THE ENERGY |
| CALCS, 604700 FBC13. |
| |
| 31.)THE ENGINEER'S SIGNATURE IS A TITLE BLOCK, |
| ORIGINAL WET SIGNATURE REQUIRED. |
| |
| 32.)PROVIDE ROOF DRAINAGE CALCULATIONS FBC1503.4. |
| PROVIDE DETAILS, SHOW OVERFLOW. |
| |
| |
| TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER |
| INDICATING HOW EACH ITEM WAS ADDRESSED WHEN |
| RESUBMITTING. |