Date |
Text |
2007-03-19 10:51:03 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| MUNICIPAL CODE |
| |
| ***FROM PREVIOUS REVIEWS**** |
| |
| 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE |
| NUMBER IS REQUIRED IN THE TITLE BLOCK PER FAC |
| 61G1-16.004(2) & FS 481.2055. |
| ****RESPONSE NOTED, BUT COMMENT WAS NOT ADDRESSED. |
| ******NO RESPONSE, NOT ADDRESSED |
| |
| 2. OK |
| |
| 3. ALL M,E,P SHEETS. A CERTIFICATE OF AUTHORIZATION IS |
| REQUIRED FOR THE ENGINEERING COMPANY PER FAC |
| 61G15-23.002(2) & FS 471.025. - THE SIGNATURE OF THE |
| ENGINEER IS REQUIRED ON THE SEAL. IT APPEARS TO BE AN |
| INITIAL AND NOT A SIGNATURE. PLEASE PROVIDE A SIGNED, |
| SEALED, DATED, NOTORIZED LETTER INDICATING THE LEGAL |
| SIGNATURE OF THE ENGINEER FOR OUR FILES. FAC |
| 61G15-23.002(1) & FS 471.025. |
| ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. THE |
| CERTIFICATE OF AUTHORIZATION NUMBER (EB) IS NOT SHOWN |
| ON THE TITLE BLOCK OF THE ENGINEER. ALSO THE SIGNED, |
| SEALED, NOTORIZED LETTER REQUESTED INDICATING THE LEGAL |
| SIGNATURE FOR OUR FILES HAS NOT BEEN SUBMITTED. |
| ******RESPONSE NOTED, BUT THE SIGNED, SEALED, DATED, |
| NOTORIZED LETTER REQUESTED SHOWING THE LEGAL SIGNATURE |
| HAS NOT BEEN SUBMITTED. |
| |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| 8. OK |
| |
| *************NEW COMMENTS************* |
| |
| 1B. PER SECTION 11-4.1.3(10)(B) 50% OF ALL DRINKING |
| FOUNTAINS PROVIDED SHALL COMPLY WITH 11-4.15. PLANS |
| SHOW 7 DRINKING FOUNTAINS, BUT ONLY 1, (P8) COMPLIES. A |
| MINIMUM OF 4 DRINKING FOUNTAINS SHALL COMPLY WITH |
| SECTION 11-4.15 & ALL SUBSECTIONS. |
| ******RESPONSE NOTED, BUT WITH ALL DRINKING FOUNTAINS |
| BEING AT ACCESSIBLE HEIGHT, SECTION 11-4.1.3(10)(A), |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING NOW NEEDS TO BE ADDRESSED. |
| |
| 2B. OK |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6713 |
| E-MAIL [email protected] |