Plan Review Notes For Permit 06090691 |
Permit Number |
06090691 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-04-04 07:10:33 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)N/A. | | | | 2.)VP BUILDINGS SHEETS, SEE FIRST CORRECTION LIST IN | | REGARDS TO ALL INFORMATION REQUIRED BY FAC61G15-23.002. | | I BELIEVE THAT THE ENGINEER HAS ADDRESSED THE ISSUE OF | | CERTIFICATE OF AUTHORIZATION FOR PRACTICING ENGINEERING | | THROUGH A COMPANY VERBALLY.PLEASE HAVE HIM ADDRESS | | THIS ISSUE WITH A LETTER FOR THE FILE. | | | | 3.)S2.1, PROVIDE CALCULATIONS FOR ROOF COMPONENTS & | | CLADDING, CORNER ZONE, <10SF, -69PSF.SEE FBC TABLE | | 1609.6.2.1(2), ROOF 0 TO 27 DEGREES. | | | | 4.)PROVIDE THE INSTALLATION INSTRUCTIONS, ERECTION | | GUIDE, EVALUATION REPORT FOR THE VP BUILDINGS ROOF. | | CONFIRM THAT THIS PRODUCT MEETS OR EXCEEDS DESIGN | | PRESSURES REQUIRED BY EITHER SHEET S2.1 (WITH | | CALCULATIONS) OR REVISED SHEET S2.1. | | | | 5.)N/A |
|