2007-04-04 07:10:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)N/A.
  
 2.)VP BUILDINGS SHEETS, SEE FIRST CORRECTION LIST IN
 REGARDS TO ALL INFORMATION REQUIRED BY FAC61G15-23.002.
 I BELIEVE THAT THE ENGINEER HAS ADDRESSED THE ISSUE OF
 CERTIFICATE OF AUTHORIZATION FOR PRACTICING ENGINEERING
 THROUGH A COMPANY VERBALLY.PLEASE HAVE HIM ADDRESS
 THIS ISSUE WITH A LETTER FOR THE FILE.
  
 3.)S2.1, PROVIDE CALCULATIONS FOR ROOF COMPONENTS &
 CLADDING, CORNER ZONE, <10SF, -69PSF.SEE FBC TABLE
 1609.6.2.1(2), ROOF 0 TO 27 DEGREES.
  
 4.)PROVIDE THE INSTALLATION INSTRUCTIONS, ERECTION
 GUIDE, EVALUATION REPORT FOR THE VP BUILDINGS ROOF.
 CONFIRM THAT THIS PRODUCT MEETS OR EXCEEDS DESIGN
 PRESSURES REQUIRED BY EITHER SHEET S2.1 (WITH
 CALCULATIONS) OR REVISED SHEET S2.1.
  