2007-01-24 19:00:39 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| MUNICIPAL CODE |
| |
| 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE |
| NUMBER IS REQUIRED IN THE TITLE BLOCK PER FAC |
| 61G1-16.004(2) & FS 481.2055. |
| ****RESPONSE NOTED, BUT COMMENT WAS NOT ADDRESSED. |
| |
| 2. ALL M,E,P SHEETS. SEAL REQUIRED TO BE AN EMBOSSING |
| TYPE SEAL, AND THE SEAL SHALL CONTAIN THE WORD |
| "LICENSE" EFFECTIVE FEBRUARY 5, 2004, BUT A GRACE |
| PERIOD TO JANUARY 1, 2006 WAS GIVEN. PLEASE CHANGE SEAL |
| AND MAKE SURE IT IS A RAISED, IMPRESSION TYPE SEAL. |
| (SEE ATTACHED SHEET)FAC 61G15-23.001 & FS 471.025. |
| ****RESPONSE NOTED, BUT NOT ALL SHEETS FROM ALL THREE |
| SETS HAVE BEEN SIGNED, SEALED, DATED. RECHECK SOME |
| SHEETS THAT HAVE THE NEW SEAL AFFIXED AS NOT ALL THE |
| INFORMATION FROM THE SEAL IS LEGIBLE. |
| |
| 3. ALL M,E,P SHEETS. A CERTIFICATE OF AUTHORIZATION IS |
| REQUIRED FOR THE ENGINEERING COMPANY PER FAC |
| 61G15-23.002(2) & FS 471.025. - THE SIGNATURE OF THE |
| ENGINEER IS REQUIRED ON THE SEAL. IT APPEARS TO BE AN |
| INITIAL AND NOT A SIGNATURE. PLEASE PROVIDE A SIGNED, |
| SEALED, DATED, NOTORIZED LETTER INDICATING THE LEGAL |
| SIGNATURE OF THE ENGINEER FOR OUR FILES. FAC |
| 61G15-23.002(1) & FS 471.025. |
| ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. THE |
| CERTIFICATE OF AUTHORIZATION NUMBER (EB) IS NOT SHOWN |
| ON THE TITLE BLOCK OF THE ENGINEER. ALSO THE SIGNED, |
| SEALED, NOTORIZED LETTER REQUESTED INDICATING THE LEGAL |
| SIGNATURE FOR OUR FILES HAS NOT BEEN SUBMITTED. |
| |
| 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: |
| 11-4.16.5 FLUSH CONTROLS, 11-4.18.4 FLUSH CONTROLS, |
| 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED PIPES & |
| SURFACES, 11-4.19.5 FAUCETS. |
| ****RESPONSE NOTED, BUT COMMENTS ARE NOT ADDRESSED. |
| (SEE DETAIL 13 FLUSH CONTROLS FOR 11-4.16.5- ALL |
| OTHER INFORMATION NOT INDICATED). |
| |
| 5. OK |
| |
| 6. SHT P3.1 THE SAND/OIL INTERCEPTOR SHALL BE SIZED AND |
| APPROVED BY THE UTILITY DEPT. CONTACT LYNN MASSON, |
| ENVIRONMENTAL COMPLIANCE AT (561) 822-2271, OR FAX |
| (561) 822-2279, OR E-MAIL [email protected]. WASTE ORD. |
| 3434. |
| ****RESPONSE NOTED. PLEASE SEE ATTACHED SHEET FROM MR. |
| RODNEY COMPO INDICATING THE APPROVED MINIMUM |
| RECOMMENDED SIZE OF INTERCEPTOR. THIS SHALL BE |
| INDICATED ON THE PLANS. ALSO A ZURN MODEL Z1188 IS |
| INDICATED. PLEASE INDICATE IF THIS IS THE MAKE & MODEL |
| INTERCEPTOR BEING INSTALLED. IF NOT PLEASE INDICATE |
| MAKE & MODEL OF INTERCEPTOR TO BE INSTALLED AND SUBMIT |
| MANUF. SPECIFICATION SHEETS. |
| |
| 7. OK |
| |
| 8. SHT P8.2 WATER RISER DIAGRAM. SUBMIT A WATER RISER |
| DIAGRAM IN AN ISOMETRIC FORM THAT REFLECTS THE FLOOR |
| PLAN. SHOW ALL PIPE SIZES, VALVES, AND WATER HAMMER |
| ARRESTORS REQUIRED BY SECTION 604.9 LOCATED IN AN |
| "EFFECTIVE RANGE" (NOT IN THE CEILING). SECTION |
| 106.1.3. - FULL OPEN VALVES ARE REQUIRED ON ALL WATER |
| DOWN-FEED LINES. SECTION 606.1(2). |
| ****RESPONSE NOTED, BUT SOME FULL OPEN VALVES ARE NOT |
| INDICATED ON THE WATER DOWN-FEED LINES TO THE HOSE |
| BIBBS. |
| |
| *************NEW COMMENTS************* |
| |
| 1B. PER SECTION 11-4.1.3(10)(B) 50% OF ALL DRINKING |
| FOUNTAINS PROVIDED SHALL COMPLY WITH 11-4.15. PLANS |
| SHOW 7 DRINKING FOUNTAINS, BUT ONLY 1, (P8) COMPLIES. A |
| MINIMUM OF 4 DRINKING FOUNTAINS SHALL COMPLY WITH |
| SECTION 11-4.15 & ALL SUBSECTIONS. |
| |
| 2B. SHT P4.1 PREVIOUSLY, THE RPZV BACKFLOW WAS LOCATED |
| AT THE METER FOR THIS BUILDING. IS THE BACKFLOW AT THE |
| METER TO BE DELETED? IS THERE A MASTER METER AND RPZV |
| BACKFLOW FOR THE PROJECT? IF NOT, THE BACKFLOW WILL |
| HAVE TO BE LOCATED AS NEAR THE METER AS POSSIBLE, ON |
| PRIVATE PROPERTY.PLEASE CLARIFY. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6713 |
| E-MAIL [email protected] |