Plan Review Notes For Permit 06090691 |
Permit Number |
06090691 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-01-18 15:27:02 | DENIED: | | RESPONSE TO COMMENTS FROM REVIEW DATED 10/20/06: | | | | COMMENT 1:OK | | COMMENT 2:OK | | COMMENT 3:RESPONSE INDICATES CO SENSORS ACTIVATION | | WILL BE AT 25 PPM.RESPONSE DOES NOT INDICATE | | MANUFACTURER SUBMITTAL DATA WITH REGARDS TO THE | | SENSORS.PLEASE NOTE, PLANS INDICATE FUME SENSORS | | MOUNTED AT 5 FT ABOVE FINISHED FLOOR WHEREAS THE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS MAY DIFFER | | FROM THIS HEIGHT.PLEASE PROVIDE SUBMITTAL DATA ON THE | | SENORS. | | | | COMMENT 4 THROUGH 17:OK | | | | COMMENT 18: ALL ELECTRICAL & PLUMBING PLANS IN SOME OF | | THE PLAN SETS ARE MISSING SEAL, SIGNATURE AND DATE FROM | | THE ENGINEER OF RECORD AS REQUIRED BY FS 471.025 & FAC | | 61G15-23.002. | | | | NEW COMMENTS - PROVISO: | | 19.PLAN SHEET M3.1 KEYED NOTE 6 INIDCATES FANS WILL BE | | MOUNTED 36" ABOVE FINISHED FLOOR.PER 2004 FMC 303.4, | | EQUIPMENT SHALL NOT BE INSTALLED IN A LOCATION WHERE | | SUBJECT TO MECHANICAL DAMAGE UNLESS PROTECTED BY | | APPROVED BARRIERS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|