Plan Review Notes
Plan Review Notes For Permit 06090691
Permit Number 06090691
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-12 17:10:50*****UNSAT 2ND REVIEW ******
  
 FED-EX GROUND.
  
 ** PLEASE ADDRESSING ON PLANS SHALL BE REQUIRED TO
 CORRELATE. PLEASE SEE PERMIT APPLICATION, THE ASSIGNED
 ADDRESS AND PLANS DO NOT MATCH. PLEASE SEE THE ADDRESS
 SHALL APPEAR ON ALL SHEETS TITLE BLOCKS. FAC 61G1,
 61G15
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING.
 COMMENTS WILL BE IDENTIFIED AS FOLLOWS IN THE SAME
 NUMERICAL ORDER FROM THE PREVIOUS REVIEW. ANY NEW NOTES
 WILL BE ADDED TO THE END OF THE REVIEW.
  
 A) NO, MEANS THE COMMENT IS STILL IN NEED OF FURTHER OR
 CORRECTED INFORMATION. IT WILL BE FOLLOWED BY FURTHER
 EXPLANATION FOR MORE INFORMATION OR TO TRY AND BETTER
 EXPLAIN THE COMMENT.
 B) OK, IS COMMENT IS ADDRESSED AND THE PREVIOUS NOTE
 WILL BE REMOVED.
 C) NO/OK IS THAT PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED BUT NOT ALL. A FURTHER EXPLANATION WILL BE
 TYPED TO PROVIDE MORE INFORMATION FOR WHAT IS NEED.
  
  
 1) NOTE:NO, PLEASE SEE THERE ARE NUMEROUS SHEETS IN
 ONE SET WHICH ARE NOT SIGNED, DATED OR SEALED AT ALL.
 PLEASE SEE YET ANOTHER SET ONLY CONTAINS ONE ELECTRICAL
 SHEET WHICH IS SIGNED, DATED AND SEALED.PLEASE SEE
 THE THIRD SETS ALSO.
 PLEASE SEE THE SAME SETS CONTAINS MANY MECHANICAL AND
 PLUMBING SHEETS WHICH ARE NOT SIGNED, DATED OR SEALED
 EITHER?
 PLEASE SEE OTHER SETS WHICH SOME SHEETS ARE SIGNED,
 DATED AND SEALED AND MANY OTHER SHEETS ARE NOT?
 PLEASE SEE OTHER DOCUMENTS WHICH ARE IN FACT
 PHOTO-COPIES OF SIGNED AND SEALED DOCUMENTS.
 AS PREVIOUSLY MENTIONED, ALL THREE SETS, ALL DOCUMENTS
 PREPARED BY THE DESIGNERS OF RECORD ARE REQUIRED TO
 CONTAIN AN ORIGINAL SIGNATURE, DATED AND A RAISED
 EMBOSSED SEALED AS REQUIRED IN THE SECTIONS OF THE
 FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUTES GIVEN
 ON PREVIOUS REVIEW.
 ** PLEASE KNOW, SETS OF PLANS MAY BE RETAINED BY THIS
 OFFICE.
 ** PLEASE ALSO KNOW THAT THIS COMMENT IS REQUIRED FOR
 ALL TRADES AND FOR ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL MEP SHEETS SHALL CONTAIN THE RAISED
 EMBOSSED SEAL FOR THE ENGINEER OF RECORD. PLEASE SEE
 FAC 61G15-23.001,FS 471.025
 PLEASE ALSO SEE THE SEAL WHICH IS BEING INDICATED ON
 SAID MEP'S IS NO LONGER VALID WITH THE STATE OF
 FLORIDA. PLEASE SEE FAC 61G15-23.001, WHICH PASSED A
 RULING IN FEB 04" WHICH REQUIRED THE SEAL WORDING TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE". PLEASE KNOW AN
 EXTENSION WAS GIVEN TO 12/31/05.
  
 2) NOTE: OK.
  
 3) NOTE: NO, THIS IS STILL REQUIRED AND IT HAS COME TO
 OUR ATTENTION THAT THE FIRM DOES NOT CONTAIN THE
 LICENSE NUMBER AS NEEDED AND AS REQUIRED PER SECTIONS
 GIVEN BELOW IN THE PREVIOUS REVIEW. PLEASE SEE RESPONSE
 MENTIONS THE ENGINEER WAS ADDED TO THE TITLE BLOCKS,
 HOWEVER THIS IS NOT THE ONLY REQUIRED INFORMATION.
 PLEASE ALSO KNOW THAT EVEN THOUGH THE ENGINEERING FIRM
 AS SHOWN IS LOCATED OUT OF STATE, THIS HAS NO BEARING
 ON THE REQUIREMENT.
 ** THE TITLE BLOCKS WERE REVISED FOR THE FOUNDATION
 PERMIT. IF THIS IS DONE, ADDRESS AND COMPLETED
 INFORMATION FOR THE INDIVIDUAL ENGINEER OF EACH TRADE
 IS REQUIRED TO BE COMPLETED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE
 BLOCKS. PLEASE SEE MISSING THE PRINTED LICENSE # OF
 ARCHITECT ON A SHEETS. PLEASE SEE THE MISSING
 INFORMATION AS REQUIRED ON ENGINEERING FIRM. PLEASE SEE
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 ALL TITLE BLOCKS FOR ALL SHEETS ARE REQUIRED TO MEET
 FAC 61G1-16.004, 61G15-23.002 AND FS 481.219, 471.023.
 ** REQUIRED FOR ALL WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 4) NOTE: OK.
  
 5) NOTE: NO, PLEASE SEE THE ENERGY CALCULATIONS
 SUBMITTED DO NOT COMPLY OR SUPPLY THE INFORMATION AS
 NEEDED UNDER 13-415.1AB.1 OR 13-415.2. PLEASE SEE THE
 SHEETS SUBMITTED, SOME ARE SIGNED AND SEALED AND SOME
 ARE NOT.
 PLEASE SEE LIGHTING PERFORMANCE ON PLANS INDICATES THE
 2003 ICC WHICH IS NOT ADOPTED INTO THE STATE OF
 FLORIDA.
 PLEASE ALSO SEE THE ENTIRE BUILDING IS BEING DESIGNATED
 AS ONE USE?
 PLEASE SEE THE PREVIOUS NOTE AS THE COMPLIANCE
 BREAKDOWN REQUIRED FOR METHOD A SHOULD BE SUBMITTED
 SHOWING ALL INFORMATION AS NEEDED.
 THIS MAY NOT BE CONSIDERED INDUSTRIAL WORK. A CALL TO
 GO OVER USAGE MAY HELP.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE FBC 2004 FOR REQUIRED ENERGY CALCULATIONS.
 PLEASE SEE 1993 ASHAE/ ETC IS BEING REFLECTED ON SAID
 DOCUMENTS. PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.AB.1
 PLEASE KNOW THESE WILL ALSO BE REQUIRED TO BE SIGNED,
 DATED AND SEALED AS REQUIRED ON NOTES ABOVE. PLEASE SEE
 THESE ARE ALSO STAMPED WITH A "RUBBER STAMP" FOR SAID
 SEAL AND CONTAINS "CERTIFICATE" IN SEAL.
  
 6) NOTE:OK/NO. PLEASE SEE RESPONSE LETTER MENTIONS
 THAT THE ENTIRE BUILDING WILL BE OPERATING 24/7. THIS
 EXCEPTION SHALL BE NOTED AND STATED ON THE PLANS.
 PLEASE SEE NO INFORMATION FOR THE WORST CASE VOLTAGE
 DROP CALCULATIONS OR SCENARIOS COULD BE LOCATED ON
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CHAPTER 13 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR MINIMUM LIGHTING CONTROLS REQUIRED. PLEASE PROVIDE
 PERFORMANCE CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.
 PLEASE SEE TABLES AND SPACE BY SPACE METHODS.
 PLEASE PROVIDE SCHEDULING.
 PLEASE SEE ALL OF CHAPTER 13, BASED ON THE 2004 FBC.
 PLEASE PROVIDE ALL WORST CASE SCENARIO'S FOR VOLTAGE
 DROP CALCULATIONS PER13-413.1ABC.1 FOR BOTH BRANCH
 CIRCUIT AND FEEDERS.
  
 7) NOTE:NO, THE ATTACHED DOCUMENTS DO NOT PROVIDE THE
 WIND LOAD INFORMATION, DO NOT SUPPLE THE MAXIMUM EPA,
 AND IF SUBMITTING SHOP/PRODUCTS, FOR COMPLIANCE AND
 SHOWING AND STATING THE INFORMATION ON PLANS, THEN ALL
 OF THESE DOCUMENTS FOR POLES, WIND LOAD INFORMATION AND
 EPA'S SHALL BE REVIEWED AND STAMPED/SIGNED BY THE
 ENGINEER OF RECORD.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE WIND LOAD CALCULATIONS FOR SITE LIGHTING
 POLES. PLEASE KNOW, THE BUILDING/STRUCTURAL REVIEWER
 WILL REVIEW SAID DOCUMENTS FOR ACTUAL WIND LOADS WHICH
 WILL BE REQUIRED TO SHOW EPA FOR PROPOSED FIXTURES.
 FBC 2004 140MPH. ETC.
  
 8) NOTE:NO, PLEASE SEE RESPONSE MENTIONS DESIGN WILL
 MEET THIS; HOWEVER NO REVIEW FOR COMPLIANCE CAN BE DONE
 UNTIL PHOTO-METRICS ARE SHOWN FOR COMPLIANCE. THE
 LEVELS ARE BEING SUBMITTED FOR WAREHOUSE UNDER NORMAL,
 HOWEVER NO INFORMATION FOR CONDITIONS UNDER EMERGENCY
 OR OFFICE EGRESS AREAS IS SHOWN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR EGRESS
 LIGHTING PER NFPA-101 7.8, 7.9
 PLEASE SEE NORMAL IS SHOWN, HOWEVER NEED TO SEE MIN
 UNDER EMERGENCY CONDITIONS.
  
 9) NOTE: OK, AS NOTED HOWEVER SEE OTHER NEW COMMENTS AS
 THE PLANS WERE REVIEWED AS THIS MAIN DIST PANEL
 CONTAINING A SINGLE MCB RATED AT THE 1600AMPS.
 SEE NEW NOTES.
  
 10) NOTE: OK.
  
 11) NOTE: PLEASE SEE 110.9, 240.13 AND PROVIDE ALL
 MINIMUM REQUIRED AIC RATINGS AND SELECTIVE COORDINATION
 FOR EQUIPMENT AS SHOWN. PLEASE SHOW DETAIL FOR
 EQUIPMENT.
  
 12) NOTE: NO, PLEASE SEE RESPONSE SAYS THE EGC IS
 AFTER; HOWEVER PLEASE SEE RISER NOTE WHICH SHOWS ALL
 PHASE CONDUCTORS AND AN EGC FROM THE FPL(LOCAL POWER
 COMPANY ) TRANSFORMER.
 PLEASE SEE RISER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.6, 250.24B AS AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS BEING SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT ON THE LINE SIDE OF THE MAIN. PLEASE KNOW
 THE EGC IS ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 13) NOTE: OK.
  
 14) NOTE: NO, RESPONSE MENTIONS WHAT TO DO, HOWEVER
 WHERE IS THIS DETAIL ON PLANS AS PREVIOUSLY REQUESTED?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A STRUCTURAL SUPPORT DETAIL FOR BOTH
 TRANSFORMERS.
 PLEASE KNOW THIS STRUCTURAL DETAIL WILL BE REVIEWED BY
 BUILDING REVIEWER.
 FBC 106.1.2
  
 15) NOTE: OK.
  
 16) NOTE:NO. PLEASE SEE RESPONSE MENTIONS THE MINIMUM
 LEVELS WHICH ARE REQUIRED PER ADA UNDER THE FBC AS
 EXCESSIVE. THESE ARE MINIMUM LEVELS. PLEASE SEE THE FBC
 DICTATES THE LEVELS WHICH ARE MORE RESTRICTIVE THAN
 THAT OF THE LEVELS IN NFPA-72. PLEASE SEE THAT THERE
 ARE MAXIMUM LEVELS WHICH ARE 1000 CD.
 THE LEVELS FOR THESE AREAS WHICH ARE TAKEN DIRECTLY
 FROM THE SECTIONS GIVEN MUST MEET THESE LEVELS AT A
 MINIMUM.
 AS REVIEWING THE RESPONSE IT HAS BEEN NOTED, HOWEVER
 THESE ARE STATED IN THE CODE THERE IS NO MENTION FOR
 EXCEPTIONS DUE TO MEDICAL CONDITIONS AS MENTIONED.
 PLEASE PROVIDE MORE INFORMATION FOR THESE LEVELS FROM
 THE FBC IF SECTIONS WRE INF THE CODE WHICH WILL SUPPORT
 THESE LESSER LEVELS.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 11-4.28, 11-4.28.2 AND .3(4) WHICH
 REQUIRE A MIN OF 75 CANDELAS AT ALL AREAS AS STATED FOR
 ADA. PLEASE SEE MIN LEVELS STATED FOR ADA ON PLANS
 MENTIONS 15CD?
 PLEASE KNOW ALL OF THESE AREAS WILL BE TESTED FOR
 MINIMUM LEVELS, PLEASE BE SURE THE DEVICES AS SHOWN AND
 INSTALLED WILL MEET TESTED LEVELS. PLEASE ADJUST NOTES
 ON PLANS AT THIS TIME.
  
 17) NOTE: OK.
  
 18) NOTE: OK/NO, PLEASE SEE RESPONSE MENTIONS THAT ALL
 CONVEYOR SYSTEMS AND ELECTRICAL WORK WILL BE UNDER A
 SEPARATE PERMIT PLANS AND FEES. PLEASE SEE THE MDP
 SHOWS CONDUCTORS AND CONDUITS BEING INSTALLED AT THIS
 TIME YET THE RISER DOES NOT SHOW THESE CONDUITS BEING
 DONE AT THIS TIME. PLEASE ALSO SEE NEW NOTE WITH
 RESPECT TO THE AMOUNT OF MAINS.
 PLEASE ADJUST MDP IF THIS WORK IS NOT BEING DONE AT
 THIS TIME AS SHOWN ON RISER AS FUTURE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE INFORMATION FOR CONVEYOR SYSTEM, PLEASE
 PROVIDE INFORMATION ON ALL LISTINGS FOR EQUIPMENT BRING
 INSTALLED.
 PLEASE PROVIDE SPECS ON THE MCC.
 110.3, 90.7.
 FBC 106.1.2
  
 19) NOTE: OK.
  
 20) NOTE:OK, THIS WAS ONLY NOTED A
  
 21) NOTE: NO, PLEASE SEE RESPONSE MENTIONS THAT THE
 LOCK ON/OFF DEVICE WILL PART OF THE BREAKER, HOWEVER
 THIS IS ONLY BEING NOTED IN RESPONSE LETTER, PLEASE
 PLACE THIS NOTE ON PLANS RELEVANT TO THE PANEL
 SCHEDULES AND BREAKERS BEING INSTALLED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL NOTES MENTIONS "LOCK-OFF" BREAKERS,
 PLEASE KNOW THESE TYPE OF LOCK OFF DEVICES SHALL BE AN
 INTEGRAL PART OF THE BREAKER AND SHALL NOT BE REMOVABLE
 WITHOUT THE REMOVAL OF SAID BREAKER. 90.7, 110.3, 90.4
  
 22) NOTE: OK, FUELING STATION WILL NOT BE PART OF THIS
 PERMIT.
  
 ** NEW NOTES THIS REVIEW **
  
 23) NOTE: PLEASE SEE AS THE MDP CONTAINS MORE THAN SIX
 SPACES AND THEY ARE NOT BEING COMPLETED AND SPACES ARE
 NOT FILLED AT THIS TIME, A MCB WILL BE REQUIRED. OTHER
 OPTIONS WOULD BE TO INSTALL THE 3-POLE BREAKERS AS
 SPARES AT THIS TIME AND WILL BE REQUIRED TO BE SHOWN,
 OR THE PLANS SHALL BE NOTED THAT THE DEAD-FRONT FROM
 THE MANUFACTURE SHALL CONTAIN A PERMANENT FACTORY
 INSTALLED FILLER FOR THIS SECTION FOR 2D.
 230.70, 230.71 90.4.
 PLEASE KNOW, THE OTHER OPTION WOULD BE TO INSTALL A
 1600AMP MCB WITH GF PROTECTION.
  
 24) NOTE: PLEASE SEE MDP WHICH SHOWS 1/0'S FOR THE
 FEEDERS TO THE TRANSFORMER FOR PP1, HOWEVER RISER SHOWS
 #1'S. PLEASE CORRELATE.
 PLEASE KEEP IN MIND THE VOLTAGE DROP AS PREVIOUSLY
 NOTED.
  
 25) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) IS
 BEING GIVEN AS A NOTICE AT THIS TIME WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE; HOWEVER ONE SET OF PLANS MAY BE RETAINED.
  
 ** PLEASE KNOW AS THERE IS INFORMATION WHICH HAS NOT
 YET BEEN SUBMITTED FOR REVIEW, THERE MAY BE COMMENTS ON
 NEXT REVIEW WHICH ARE NOT STATED IN THESE REVIEW
 NOTES.
  
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected] ND IF IT IS AN ISSUE THEN RELOCATION
 WILL BE REQUIRED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved