2007-01-09 12:05:41 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| PERMIT PICKUP, FS713.13. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| 561-233-5025 FOR MORE INFORMATION. |
| |
| THE PLANS MUST BE STAMPED.ONLY A RECEIPT WAS |
| PROVIDED.PLEASE NOTE THAT THE STAMPED PLAN WHICH YOU |
| PROVIDED IS WITH THE DENIED FOUNDATION PERMIT |
| APPLICATION PACKAGE.WE MUST HAVE A COPY ON FILE PRIOR |
| TO PERMIT ISSUANCE. |
| |
| 3.-4.)ADDRESSED. |
| |
| 5.)PLEASE REVISE THE PERMIT APPLICATION TO REFLECT |
| THE CORRECT TEMPORARY PARCEL ID. |
| |
| 6.-8.)ADDRESSED. |
| |
| 9.)PROVIDE COMPONENTS & CLADDING PRESSURES, |
| FBC1603.1.4. |
| |
| NOT ADDRESSED.THE RESPONSE LETTER STATES THAT IT IS |
| PROVIDED BY VP.VP PLAN STATES THAT ALL COMPONENTS & |
| CLADDING HAVE BEEN DESIGNED BY A FLORIDA DESIGN |
| PROFESSIONAL AND ARE NOT ON THE PLAN PER FBC |
| 1606.1.7(5).THIS IS NOT A VALID CODE SECTION, AND IS |
| REQUIRED ON THE PLAN, WIND DESIGN CRITERIA, |
| FBC1063.1.4. |
| |
| DESIGNER IS TO SPECIFY COMPONENT & CLADDING PRESSURES, |
| PER OPENING AND FOR THE ROOF SYSTEMS.PRODUCT |
| APPROVALS ARE THEN VERIFIED FOR COMPLIANCE. |
| |
| 10.)ADDRESSED. |
| |
| 11.)THE RESPONSE REGARDING S2 OCCUPANCY IS |
| ACKNOWLEDGED.THIS IS ACCEPTABLE WITH THE EXCEPTION OF |
| UNLIMITED TRAVEL DISTANCE FOR ACCESSIBLE EXITS.NOTE |
| THAT THE TRAVEL DISTANCE FOR THE TWO ACCESSIBLE EXITS |
| ARE APPROXIMATELY 350 AND 450 FEET, BUT OTHER EXITS |
| HAVE LESS TRAVEL DISTANCE.PLEASE CONTACT ME TO |
| DISCUSS PRIOR TO RESUBMITTAL. |
| |
| 12.)IF NECESSARY, REVISE TRAVEL DISTANCE, OCCUPANT |
| LOAD, ANY OTHER ITEMS AFFECTED BY ITEM 11. |
| |
| 13.)ADDRESSED.PLEASE SEE ITEM 11 ABOVE. |
| |
| 14.)3-A9.2, PROVIDE A GUARD DETAIL IN COMPLIANCE WITH |
| FBC1012 AND FBC1607.7. |
| |
| PLEASE INCLUDE REQUIREMENT OF 1607.7.1.1. |
| |
| 15.)2-A9.2, THE HANDRAIL EXTENSIONS ARE TO COMPLY |
| WITH FBC1009.11.5.ANY ACCESSIBLE STAIRS ARE TO ALSO |
| COMPLY WITH FBC11-4.9.4. |
| |
| IT IS NOT CLEAR WHY THE STAIRS AT THE LOADING DOCK ARE |
| NOT ACCESSIBLE.THE EXCEPTIONS TO ACCESSIBILITY DO NOT |
| APPLY.PLEASE REVISE HANDRAIL DETAILS.ALSO SEE |
| FBC1009.3.2, STAIR TREADS TO BE SOLID. |
| |
| 16.)ADDRESSED. |
| |
| 17-18.) SEE ITEM 11. |
| |
| 19-21.)ADDRESSED. |
| |
| 22.)SUBMIT THREE ORIGINAL ENERGY CALCS (ONLY ONE |
| PROVIDED). |
| |
| 23-24.) ADDRESSED. |
| |
| 25.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION. |
| |
| ANY PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR |
| TO PERMIT ISSUANCE WILL REQUIRE SEPARATE PERMITS. |
| |
| REGARDING THE PRODUCT APPROVALS SUBMITTED, NOTE THE |
| FOLLOWING: |
| |
| A. ONLY ONE SET SUBMITTED; THREE REQUIRED. |
| |
| B. TWO PRODUCT APPROVALS WERE REVIEWED BY DOR, TWO WERE |
| NOT.ALL ARE REQUIRED TO BE REVIEWED AND APPROVED BY |
| DESIGNER OF RECORD, FBC*106.3.3. |
| |
| C. THE VP FLORIDA STATE PRODUCT APPROVAL IS DENIED. |
| PROVIDE PRODUCT APPROVALS FOR THE ROOF SYSTEMS.IF A |
| MIAMIDADE NOA IS AVAILABLE, A LOCAL.PRODUCT APPROVAL |
| CAN BE ISSUED USING THE NOA.IF IT IS NOT AVAILABLE, |
| SEE FAC9B72 IN REGARDS TO REQUIREMENTS FOR A LOCAL |
| PRODUCT APPROVAL APPLICATION.IF MORE THAN ONE |
| FASTENING OPTION IS AVAILABLE, INDICATE WHICH SYSTEM OR |
| FASTENING WILL BE USED SO THAT CODE COMPLIANCE CAN BE |
| DETERMINED. |
| |
| D. PRODUCT APPROVAL REQUIRED FOR THE WALL LOUVERS. |
| |
| 26.)ENGINEERING FOR VP BUILDINGS, DECLARE GOVERNING |
| CODE. |
| |
| GOVERNING CODE IS FBC2004.PLANS STATE ASCE7-02 AND |
| CITES CODE REFERENCES FROM FBC2001.PLEASE REVISE; |
| DESIGN IS TO BE IN COMPLIANCE WITH FBC2004. |
| |
| 27-31.) ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 32.)FIRE SPRINKLER PLANS, FP1 AND FP2, ARE LISTED ON |
| THE COVER SHEET BUT ARE NO LONGER IN THE PLANS.THIS |
| IS A STATUTORY REQUIREMENT, PLEASE PROVIDE. |
| |
| 33.)SEE ATTACHED FS553.80(2)(B). |