Plan Review Notes
Plan Review Notes For Permit 06090691
Permit Number 06090691
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-20 15:28:51DENIED:
 1.PLAN SHEET M1.1 INDICATES THE DESIGN IS TO THE
 INTERNATIONAL MECHANICAL CODE.THIS SHOULD READ 2004
 FLORIDA BUILDING CODE/MECHANICAL.
  
 2.PLAN SHEET M3.1 "KEYED NOTES" NUMBER 6 INDICATES
 THE INTAKE LOUVER FOR MAKE-UP AIR IS LOCATED 36" A.F.F.
 THIS APPEARS TO BE LOCATED IN A LOADING OR PARKING
 AREA.PER 2004 401.5.1 INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM ANY NOXIOUS CONTAMINANT
 SUCH AS PARKING LOTS, STREETS, ALLEYS, AND LOADING
 DOCKS.PLEASE CLARIFY.
  
 3.PLAN SHEET M3.1 NOTE 3 INDICATES FUME SENSOR
 MOUNTED 5 FT A.F.F., MATCH TO EXISTING & CONNECT TO
 EXISTING SYSTEM.THE PERMIT APPLICATION INDICATES THIS
 IS A NEW BUILDING, WHAT WILL BE "EXISTING"? PROVIDE
 MANUFACTURE SUBMITTAL DATA FOR THE SENSOR.AT WHAT
 PARTS PER MILLION WILL THE SENSOR BE SET AT (25 PPM -
 PER 2004 FMC 404.1).
  
 4.PLEASE INDICATE HOW THE REQUIREMENT FOR
 VENTILATION RATE OF .05 CFM PER SQUARE FT WHEN THE FANS
 WILL NOT RUN CONTINUOUSLY.
  
 5.PLAN SHEET A2.1 DETAIL 1 (WEST ELEVATION), WHAT
 WILL BE USING THE DRIVE-IN DOOR, VEHICLES, FORK-LIFTS,
 ETC.
  
 6.PLAN SHEET M3.1, PLEASE CLARIFY WHAT THE "SPECIAL
 HANDLING CAGE" WILL BE UTILIZED FOR.EF-10IS NOT
 INDICATED ON THE FAN SCHEDULE ON PLAN SHEET.PLAN
 SHEET M5.2 INDICATES AN EXHAUST FAN TO THE HOOD, IS
 THIS EF-10?
  
 7.PLEASE INDICATE WHAT THE FUME HOOD WILL BE USED
 FOR.
  
 8.PLAN SHEET M3.2 INDICATES DUCT SMOKE DETECTORS IN
 THE RETURN AIR DUCT.PER 2004 FMC 606.2.1, SMOKE
 DETECTORS ARE REQUIRED IN THE SUPPLY AIR DUCT.
  
 9.PLEASE PROVIDE A DETAIL OF THE RTU ATTACHMENT TO
 THE ROOF.NO SUPPORT IS INDICATED ON THE STRUCTURAL,
 ARCHITECTURAL OR MECHANICAL PLANS.SHOW COMPLIANCE
 WITH 2004 FBC 1509.7.
  
 10.PROVIDE LOCATION OF THE CONDENSING UNIT (GROUND OR
 ROOF).
  
 11.PLEASE INDICATE ACCESS TO THE EQUIPMENT LOCATED ON
 THE ROOF.PER 2001 FMC 306.5, EQUIPMENT ON LOCATED ON
 ROOF OR ELEVATED STRUCTURE AT A HEIGHT GREATER THAN 16
 FT SHALL HAVE A PERMANENT MEANS OF ACCESS.PLEASE
 NOTE,ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4/12 PITCH.
  
 12.PER 2004 FMC 306.6 ROOFS HAVING GREATER THAN 25%
 SLOPE AND HAVING AN EDGE MORETHAN 30 INCHES ABOVE GRADE
 AT SUCH EDGE, A LEVEL PLATFORM SHALL BE PROVIDED ON
 EACH SIDE OF THE APPLIANCETO WHICH ACDESS IS REQUIRED
 BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 SERVICE, REPAIR OR MAINTENANCE.THE PLATFORM SHALL NOT
 BE LESS THAN 30 INCHES IN ANY DIMENSION AND BE PROVIDED
 WITH GUARDS IN ACCORDANCE WTIH SECTION 304.10.
  
 13.PLEASE PROVIDE MOUNTING DETAIL FOR SF1 THROUGH
 7.13.
  
 14.PLANS DO NOT INDICATE OVERFLOW PROTECTION AS
 REQUIRED IN 2004 FMC 307.2.3.
  
 15.PLAN SHEET A0,2 INDICATES "FUTURE FUEL ISLAND &
 MAITENANCE GARAGE"WILL THIS BE UNDER A SEPARATE
 PERMIT?
  
 16.PLEASE PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 17.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE
 WITH 2004 FBC CHAPTER 13 SUB-CHAPTER 4.
  
 18.PER FAC 61G15-23.001(1), SEALS ARE TO BE EMBOSSED
 (RAISED) TYPE,STAMPS ARE NOT ACCEPTABLE.ENGINEERS
 SHALL LEGIBLY INDICATE NAME, ADDRESS, AND NUMBER ON
 EACH SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  