Date |
Text |
2006-10-20 15:28:51 | DENIED: |
| 1.PLAN SHEET M1.1 INDICATES THE DESIGN IS TO THE |
| INTERNATIONAL MECHANICAL CODE.THIS SHOULD READ 2004 |
| FLORIDA BUILDING CODE/MECHANICAL. |
| |
| 2.PLAN SHEET M3.1 "KEYED NOTES" NUMBER 6 INDICATES |
| THE INTAKE LOUVER FOR MAKE-UP AIR IS LOCATED 36" A.F.F. |
| THIS APPEARS TO BE LOCATED IN A LOADING OR PARKING |
| AREA.PER 2004 401.5.1 INTAKE OPENINGS SHALL BE |
| LOCATED A MINIMUM OF 10 FT FROM ANY NOXIOUS CONTAMINANT |
| SUCH AS PARKING LOTS, STREETS, ALLEYS, AND LOADING |
| DOCKS.PLEASE CLARIFY. |
| |
| 3.PLAN SHEET M3.1 NOTE 3 INDICATES FUME SENSOR |
| MOUNTED 5 FT A.F.F., MATCH TO EXISTING & CONNECT TO |
| EXISTING SYSTEM.THE PERMIT APPLICATION INDICATES THIS |
| IS A NEW BUILDING, WHAT WILL BE "EXISTING"? PROVIDE |
| MANUFACTURE SUBMITTAL DATA FOR THE SENSOR.AT WHAT |
| PARTS PER MILLION WILL THE SENSOR BE SET AT (25 PPM - |
| PER 2004 FMC 404.1). |
| |
| 4.PLEASE INDICATE HOW THE REQUIREMENT FOR |
| VENTILATION RATE OF .05 CFM PER SQUARE FT WHEN THE FANS |
| WILL NOT RUN CONTINUOUSLY. |
| |
| 5.PLAN SHEET A2.1 DETAIL 1 (WEST ELEVATION), WHAT |
| WILL BE USING THE DRIVE-IN DOOR, VEHICLES, FORK-LIFTS, |
| ETC. |
| |
| 6.PLAN SHEET M3.1, PLEASE CLARIFY WHAT THE "SPECIAL |
| HANDLING CAGE" WILL BE UTILIZED FOR.EF-10IS NOT |
| INDICATED ON THE FAN SCHEDULE ON PLAN SHEET.PLAN |
| SHEET M5.2 INDICATES AN EXHAUST FAN TO THE HOOD, IS |
| THIS EF-10? |
| |
| 7.PLEASE INDICATE WHAT THE FUME HOOD WILL BE USED |
| FOR. |
| |
| 8.PLAN SHEET M3.2 INDICATES DUCT SMOKE DETECTORS IN |
| THE RETURN AIR DUCT.PER 2004 FMC 606.2.1, SMOKE |
| DETECTORS ARE REQUIRED IN THE SUPPLY AIR DUCT. |
| |
| 9.PLEASE PROVIDE A DETAIL OF THE RTU ATTACHMENT TO |
| THE ROOF.NO SUPPORT IS INDICATED ON THE STRUCTURAL, |
| ARCHITECTURAL OR MECHANICAL PLANS.SHOW COMPLIANCE |
| WITH 2004 FBC 1509.7. |
| |
| 10.PROVIDE LOCATION OF THE CONDENSING UNIT (GROUND OR |
| ROOF). |
| |
| 11.PLEASE INDICATE ACCESS TO THE EQUIPMENT LOCATED ON |
| THE ROOF.PER 2001 FMC 306.5, EQUIPMENT ON LOCATED ON |
| ROOF OR ELEVATED STRUCTURE AT A HEIGHT GREATER THAN 16 |
| FT SHALL HAVE A PERMANENT MEANS OF ACCESS.PLEASE |
| NOTE,ACCESS SHALL NOT REQUIRE CLIMBING OVER |
| OBSTRUCTIONS GREATER THAN 30 INCHES OR WALKING ON ROOFS |
| HAVING A SLOPE GREATER THAN 4/12 PITCH. |
| |
| 12.PER 2004 FMC 306.6 ROOFS HAVING GREATER THAN 25% |
| SLOPE AND HAVING AN EDGE MORETHAN 30 INCHES ABOVE GRADE |
| AT SUCH EDGE, A LEVEL PLATFORM SHALL BE PROVIDED ON |
| EACH SIDE OF THE APPLIANCETO WHICH ACDESS IS REQUIRED |
| BY THE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR |
| SERVICE, REPAIR OR MAINTENANCE.THE PLATFORM SHALL NOT |
| BE LESS THAN 30 INCHES IN ANY DIMENSION AND BE PROVIDED |
| WITH GUARDS IN ACCORDANCE WTIH SECTION 304.10. |
| |
| 13.PLEASE PROVIDE MOUNTING DETAIL FOR SF1 THROUGH |
| 7.13. |
| |
| 14.PLANS DO NOT INDICATE OVERFLOW PROTECTION AS |
| REQUIRED IN 2004 FMC 307.2.3. |
| |
| 15.PLAN SHEET A0,2 INDICATES "FUTURE FUEL ISLAND & |
| MAITENANCE GARAGE"WILL THIS BE UNDER A SEPARATE |
| PERMIT? |
| |
| 16.PLEASE PROVIDE OUTSIDE AIR CALCULATIONS IN |
| ACCORDANCE WITH 2004 FMC TABLE 403.3. |
| |
| 17.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE |
| WITH 2004 FBC CHAPTER 13 SUB-CHAPTER 4. |
| |
| 18.PER FAC 61G15-23.001(1), SEALS ARE TO BE EMBOSSED |
| (RAISED) TYPE,STAMPS ARE NOT ACCEPTABLE.ENGINEERS |
| SHALL LEGIBLY INDICATE NAME, ADDRESS, AND NUMBER ON |
| EACH SHEET. |
| |