Plan Review Notes
Plan Review Notes For Permit 06090691
Permit Number 06090691
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-06 14:36:09*****DENIED*****
  
  
  
 01.NFPA 101 - 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA241.
  
 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 04.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF
 SUPPORTING 32 TONS FOR FIRE EQUIPMENT.
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING
 ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1"
 IN WIDTH.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A
 NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE
 GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED
 EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE
 HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR
 MARKEE.
  
 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.
  
 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY.
  
 10.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE
 CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724
 FOR APPLICATIONS.
  
 11.WILL THERE BE SECURITY GATES TO THE PREMISES AND
 IF SO, HOW WILL THE MEANS OF EGRESS BE IMPACTED?
  
 12.PLEASE PROVIDE PRESCIPTIVE STRENGHT FOR ALL
 HANDRAILS / GUARDRAILS.
  
 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 15.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF
 TRAVEL TO EXITS.
  
 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC.
  
 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 19.THE FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 20.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
 21.DELAYED-EGRESS LOCKS AND/ORACCESS-CONTROLLED
 EGRESS DOORS SHALL COMPLY WITH NFPA 101, CH. 7.2.1.6,
 SPECIAL LOCKING ARRANGEMENTS.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722