Date |
Text |
2006-11-06 14:36:09 | *****DENIED***** |
| |
| |
| |
| 01.NFPA 101 - 2003 EDITION AND FLORIDA FIRE |
| PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| |
| 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION SHALL COMPLY WITH NFPA241. |
| |
| 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| PROPERTY OR VICINITY THEREOF. |
| |
| 04.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF |
| SUPPORTING 32 TONS FOR FIRE EQUIPMENT. |
| |
| 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE |
| MAINTAINED AT ALL TIMES. |
| |
| 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING |
| ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, |
| THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" |
| IN WIDTH.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A |
| NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE |
| GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED |
| EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE |
| HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR |
| MARKEE. |
| |
| 07.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| VESSELS, EQUIPMENT, ETC. |
| |
| 08.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| DEPARTMENT CONNECTIONS. |
| |
| 09.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| IS REQUIRED FOR DOUBLECHECK DETECTOR ASSEMBLY. |
| |
| 10.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| FOR APPLICATIONS. |
| |
| 11.WILL THERE BE SECURITY GATES TO THE PREMISES AND |
| IF SO, HOW WILL THE MEANS OF EGRESS BE IMPACTED? |
| |
| 12.PLEASE PROVIDE PRESCIPTIVE STRENGHT FOR ALL |
| HANDRAILS / GUARDRAILS. |
| |
| 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| 80. |
| |
| 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND |
| EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| |
| 15.LIFE SAFETY PLAN SHALL INCLUDE ALL COMMON PATHS OF |
| TRAVEL TO EXITS. |
| |
| 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC. |
| |
| 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| |
| 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. |
| |
| 19.THE FIRE ALARM SHALL BE UL CERTIFIED FOR CENTRAL |
| STATION SERVICE. |
| |
| 20.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY |
| ADDRESSABLE. |
| |
| 21.DELAYED-EGRESS LOCKS AND/ORACCESS-CONTROLLED |
| EGRESS DOORS SHALL COMPLY WITH NFPA 101, CH. 7.2.1.6, |
| SPECIAL LOCKING ARRANGEMENTS. |
| |
| |
| |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |