2006-10-23 14:05:24 | *****UNSAT ****** |
| |
| FED-EX GROUND. |
| |
| ** PLEASE ADDRESSING ON PLANS SHALL BE REQUIRED TO |
| CORRELATE. PLEASE SEE PERMIT APPLICATION AND PLANS DO |
| NOT MATCH WITH THE ADDRESS IN OUR SYSTEM AS SHOWN. |
| |
| |
| 1) NOTE: PLEASE SEE ALL MEP SHEETS SHALL CONTAIN THE |
| RAISED EMBOSSED SEAL FOR THE ENGINEER OF RECORD. PLEASE |
| SEE FAC 61G15-23.001,FS 471.025 |
| PLEASE ALSO SEE THE SEAL WHICH IS BEING INDICATED ON |
| SAID MEP'S IS NO LONGER VALID WITH THE STATE OF |
| FLORIDA. PLEASE SEE FAC 61G15-23.001, WHICH PASSED A |
| RULING IN FEB 04" WHICH REQUIRED THE SEAL WORDING TO |
| CHANGE FROM "CERTIFICATE" TO "LICENSE". PLEASE KNOW AN |
| EXTENSION WAS GIVEN TO 12/31/05. |
| |
| 2) NOTE: PLEASE SEE FS 471.025, PLEASE SEE ALL PLANS |
| DOCUMENTS ETC ARE REQUIRED TO CONTAIN THE ORIGINAL |
| LEGAL SIGNATURE DATE AND SEAL. |
| PLEASE SEE "VP" BUILDING SHEETS AS THESE CONTAIN A |
| RAISED SEAL OVER "PHOTO-COPIED" SIGNATURE OF THE DESIGN |
| PROFESSIONAL. |
| PLEASE SEE BUILDING REVIEW COMMENTS AS THESE ARE ALSO |
| MISSING THE REQUIRED TITLE BLOCK FOR THESE SHEETS/ |
| PLEASE SEE THE ELECTRICAL PLANS APPEAR TO BE SIGNED |
| WITH INITIALS? |
| IF INDEED THIS IS THE LEGAL SIGNATURE OF THE DESIGN |
| PROFESSIONAL PLEASE PROVIDE A SIGNED, DATED, SEALED AND |
| NOTARIZED LETTER FOR LEGAL SIGNATURE. |
| THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY |
| FUTURE REFERENCE AS NEEDED. |
| FS 471.025, FAC 61G15-23.002 |
| |
| 3) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON |
| TITLE BLOCKS. PLEASE SEE MISSING THE PRINTED LICENSE # |
| OF ARCHITECT ON A SHEETS. PLEASE SEE THE MISSING |
| INFORMATION AS REQUIRED ON ENGINEERING FIRM. PLEASE SEE |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE |
| ALL TITLE BLOCKS FOR ALL SHEETS ARE REQUIRED TO MEET |
| FAC 61G1-16.004, 61G15-23.002 AND FS 481.219, 471.023. |
| ** REQUIRED FOR ALL WHETHER OR NOT COMMENT IS MADE BY |
| OTHER REVIEWER(S). |
| |
| 4) NOTE: PLEASE SEE ALL OF THE FOLLOWING MINIMUM CODES |
| ARE REQUIRED TO BE REFLECTED ON PLANS. 2004 FBC, , 2002 |
| NFPA-70, 2002 NFPA-72, 2003 NFPA-101 . |
| |
| 5) NOTE: PLEASE SEE FBC 2004 FOR REQUIRED ENERGY |
| CALCULATIONS. PLEASE SEE 1993 ASHAE/ ETC IS BEING |
| REFLECTED ON SAID DOCUMENTS. PLEASE SEE FBC 2004 |
| CHAPTER 13. |
| 13-415.1.AB.1 |
| PLEASE KNOW THESE WILL ALSO BE REQUIRED TO BE SIGNED, |
| DATED AND SEALED AS REQUIRED ON NOTES ABOVE. PLEASE SEE |
| THESE ARE ALSO STAMPED WITH A "RUBBER STAMP" FOR SAID |
| SEAL AND CONTAINS "CERTIFICATE" IN SEAL. |
| |
| 6) NOTE: PLEASE SEE CHAPTER 13 13-415.1.ABC.1.1, .1.2 |
| AND .1.3 FOR MINIMUM LIGHTING CONTROLS REQUIRED. PLEASE |
| PROVIDE PERFORMANCE CALCULATIONS PER 13-415.2, |
| 13-415.2.ABC.1. PLEASE SEE TABLES AND SPACE BY SPACE |
| METHODS. |
| PLEASE PROVIDE SCHEDULING. |
| PLEASE SEE ALL OF CHAPTER 13, BASED ON THE 2004 FBC. |
| PLEASE PROVIDE ALL WORST CASE SCENARIO'S FOR VOLTAGE |
| DROP CALCULATIONS PER13-413.1ABC.1 FOR BOTH BRANCH |
| CIRCUIT AND FEEDERS. |
| |
| 7) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS FOR SITE |
| LIGHTING POLES. PLEASE KNOW, THE BUILDING/STRUCTURAL |
| REVIEWER WILL REVIEW SAID DOCUMENTS FOR ACTUAL WIND |
| LOADS WHICH WILL BE REQUIRED TO SHOW EPA FOR PROPOSED |
| FIXTURES. |
| FBC 2004 140MPH. ETC. |
| |
| 8) NOTE: PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR |
| EGRESS LIGHTING PER NFPA-101 7.8, 7.9 |
| PLEASE SEE NORMAL IS SHOWN, HOWEVER NEED TO SEE MIN |
| UNDER EMERGENCY CONDITIONS. |
| |
| 9) NOTE: PLEASE INDICATE THE REQUIRED MAIN AND GFP FOR |
| THE 1600A MAIN. |
| PLEASE SEE 230.70, 240.13 AND 230.95. |
| |
| 10) PLEASE ALSO SEE POSSIBLE MISPRINT FOR 2B BREAKER |
| WHICH IS BEING SHOWN AS 2225A'S.? |
| FBC ADMINISTRATIVE SECTION 106.3.5.1.2. |
| |
| 11) NOTE: PLEASE SEE 110.9, 240.13 AND PROVIDE ALL |
| MINIMUM REQUIRED AIC RATINGS AND SELECTIVE COORDINATION |
| FOR EQUIPMENT AS SHOWN. PLEASE SHOW DETAIL FOR |
| EQUIPMENT. |
| |
| 12) NOTE: PLEASE SEE 250.6, 250.24B AS AN "EQUIPMENT |
| GROUNDING CONDUCTOR" IS BEING SHOWN BEFORE THE FIRST |
| MEANS OF DISCONNECT ON THE LINE SIDE OF THE MAIN. |
| PLEASE KNOW THE EGC IS ONLY INSTALLED AFTER THE FIRST |
| MEANS OF DISCONNECT. |
| |
| 13) NOTE: PLEASE INDICATE THE FEED-THRU LUGS ON EACH |
| LP1 AND PP1, OR ARE THE SECONDARY SECTIONS FED BY OCP |
| DEVICES FROM SECTIONS (1). ? |
| 240.4,310.16 ETC? |
| 106.1.2 FBC ADMIN SECT. |
| |
| 14) NOTE: PLEASE PROVIDE A STRUCTURAL SUPPORT DETAIL |
| FOR BOTH TRANSFORMERS. |
| PLEASE KNOW THIS STRUCTURAL DETAIL WILL BE REVIEWED BY |
| BUILDING REVIEWER. |
| FBC 106.1.2 |
| |
| 15) NOTE: PLEASE SEE THERE ARE SHEETS WHICH INDICATE |
| NOTES, HOWEVER THOSE NOTES ARE ACTUALLY CROSSED OUT ON |
| SHEETS FOR NOTES.?? |
| PLEASE CLARIFY AND CORRELATE THIS. |
| FBC 106.1.2 |
| |
| 16) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.2 AND .3(4) |
| WHICH REQUIRE A MIN OF 75 CANDELAS AT ALL AREAS AS |
| STATED FOR ADA. PLEASE SEE MIN LEVELS STATED FOR ADA ON |
| PLANS MENTIONS 15CD? |
| PLEASE KNOW ALL OF THESE AREAS WILL BE TESTED FOR |
| MINIMUM LEVELS, PLEASE BE SURE THE DEVICES AS SHOWN AND |
| INSTALLED WILL MEET TESTED LEVELS. PLEASE ADJUST NOTES |
| ON PLANS AT THIS TIME. |
| |
| 17) NOTE: PLEASE ALSO SEE WITH RESPECT TO THE NOTE #16 |
| ABOVE , PLEASE SEE PLANS REFERENCE 2002 BOCA, FOR CODE. |
| PLEASE ADJUST. |
| 2004 FBC. |
| |
| 18) NOTE: PLEASE PROVIDE INFORMATION FOR CONVEYOR |
| SYSTEM, PLEASE PROVIDE INFORMATION ON ALL LISTINGS FOR |
| EQUIPMENT BRING INSTALLED. |
| PLEASE PROVIDE SPECS ON THE MCC. |
| 110.3, 90.7. |
| FBC 106.1.2 |
| |
| 19) NOTE: PLEASE PROVIDE LOAD CALCULATIONS FOR THE |
| MCC1. COULD NOT LOCATE ANY ON PLANS? |
| 220.31, LARGEST MOTOR LOADS ETC. |
| 215.3, 230.42 |
| FBC 106.3.5.1.2 |
| |
| 20) NOTE: PLEASE SEE POSSIBLE BUILDING FIRE REVIEW |
| NOTES AS TRANSFORMER/ AND ELECTRICAL EQUIPMENT APPEAR |
| TO BE LOCATED IN AN EGRESS CORRIDOR. PLEASE SEE THIS |
| MAY OR MAY NOT BE PERMITTED AS SHOWN? IF THIS IS A |
| RATED CORRIDOR, PLEASE KNOW, THIS EQUIPMENT WILL MOST |
| LIKELY BE REQUIRED TO BE RELOCATED. |
| |
| 21) NOTE: PLEASE SEE PANEL NOTES MENTIONS "LOCK-OFF" |
| BREAKERS, PLEASE KNOW THESE TYPE OF LOCK OFF DEVICES |
| SHALL BE AN INTEGRAL PART OF THE BREAKER AND SHALL NOT |
| BE REMOVABLE WITHOUT THE REMOVAL OF SAID BREAKER. 90.7, |
| 110.3, 90.4 |
| |
| 22) NOTE: PLEASE SEE SOME OTHER AREAS INDICATED AS |
| "FUTURE" AT THIS TIME MAY AFFECT THE INSTALLATIONS OF |
| SOME ELECTRICLA EQUIPMENT AND OTHER EQUIPMENT ON PLANS |
| AS SHOWN. PLEASE SEE NEC 500, AND OTHER NFPA'S RELEVANT |
| TO ANY OTHER POSSIBLE SCOPE OF WORK WHICH WILL BE |
| DECLARED AS HAZARDOUS AT THIS TIME OR AT A LATER TIME. |
| |
| ** PLEASE KNOW AS THERE IS INFORMATION WHICH HAS NOT |
| YET BEEN SUBMITTED FOR REVIEW, THERE MAY BE COMMENTS ON |
| NEXT REVIEW WHICH ARE NOT STATED IN THESE REVIEW |
| NOTES. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
2006-10-23 06:46:18 | REVIEW IN PROGRESS |
2006-10-22 19:46:04 | ONE SET IN ELEC FOR REVIEW. |