Plan Review Notes
Plan Review Notes For Permit 06090691
Permit Number 06090691
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-23 14:05:24*****UNSAT ******
  
 FED-EX GROUND.
  
 ** PLEASE ADDRESSING ON PLANS SHALL BE REQUIRED TO
 CORRELATE. PLEASE SEE PERMIT APPLICATION AND PLANS DO
 NOT MATCH WITH THE ADDRESS IN OUR SYSTEM AS SHOWN.
  
  
 1) NOTE: PLEASE SEE ALL MEP SHEETS SHALL CONTAIN THE
 RAISED EMBOSSED SEAL FOR THE ENGINEER OF RECORD. PLEASE
 SEE FAC 61G15-23.001,FS 471.025
 PLEASE ALSO SEE THE SEAL WHICH IS BEING INDICATED ON
 SAID MEP'S IS NO LONGER VALID WITH THE STATE OF
 FLORIDA. PLEASE SEE FAC 61G15-23.001, WHICH PASSED A
 RULING IN FEB 04" WHICH REQUIRED THE SEAL WORDING TO
 CHANGE FROM "CERTIFICATE" TO "LICENSE". PLEASE KNOW AN
 EXTENSION WAS GIVEN TO 12/31/05.
  
 2) NOTE: PLEASE SEE FS 471.025, PLEASE SEE ALL PLANS
 DOCUMENTS ETC ARE REQUIRED TO CONTAIN THE ORIGINAL
 LEGAL SIGNATURE DATE AND SEAL.
 PLEASE SEE "VP" BUILDING SHEETS AS THESE CONTAIN A
 RAISED SEAL OVER "PHOTO-COPIED" SIGNATURE OF THE DESIGN
 PROFESSIONAL.
 PLEASE SEE BUILDING REVIEW COMMENTS AS THESE ARE ALSO
 MISSING THE REQUIRED TITLE BLOCK FOR THESE SHEETS/
 PLEASE SEE THE ELECTRICAL PLANS APPEAR TO BE SIGNED
 WITH INITIALS?
 IF INDEED THIS IS THE LEGAL SIGNATURE OF THE DESIGN
 PROFESSIONAL PLEASE PROVIDE A SIGNED, DATED, SEALED AND
 NOTARIZED LETTER FOR LEGAL SIGNATURE.
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE AS NEEDED.
 FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS. PLEASE SEE MISSING THE PRINTED LICENSE #
 OF ARCHITECT ON A SHEETS. PLEASE SEE THE MISSING
 INFORMATION AS REQUIRED ON ENGINEERING FIRM. PLEASE SEE
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 ALL TITLE BLOCKS FOR ALL SHEETS ARE REQUIRED TO MEET
 FAC 61G1-16.004, 61G15-23.002 AND FS 481.219, 471.023.
 ** REQUIRED FOR ALL WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE ALL OF THE FOLLOWING MINIMUM CODES
 ARE REQUIRED TO BE REFLECTED ON PLANS. 2004 FBC, , 2002
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 .
  
 5) NOTE: PLEASE SEE FBC 2004 FOR REQUIRED ENERGY
 CALCULATIONS. PLEASE SEE 1993 ASHAE/ ETC IS BEING
 REFLECTED ON SAID DOCUMENTS. PLEASE SEE FBC 2004
 CHAPTER 13.
 13-415.1.AB.1
 PLEASE KNOW THESE WILL ALSO BE REQUIRED TO BE SIGNED,
 DATED AND SEALED AS REQUIRED ON NOTES ABOVE. PLEASE SEE
 THESE ARE ALSO STAMPED WITH A "RUBBER STAMP" FOR SAID
 SEAL AND CONTAINS "CERTIFICATE" IN SEAL.
  
 6) NOTE: PLEASE SEE CHAPTER 13 13-415.1.ABC.1.1, .1.2
 AND .1.3 FOR MINIMUM LIGHTING CONTROLS REQUIRED. PLEASE
 PROVIDE PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1. PLEASE SEE TABLES AND SPACE BY SPACE
 METHODS.
 PLEASE PROVIDE SCHEDULING.
 PLEASE SEE ALL OF CHAPTER 13, BASED ON THE 2004 FBC.
 PLEASE PROVIDE ALL WORST CASE SCENARIO'S FOR VOLTAGE
 DROP CALCULATIONS PER13-413.1ABC.1 FOR BOTH BRANCH
 CIRCUIT AND FEEDERS.
  
 7) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS FOR SITE
 LIGHTING POLES. PLEASE KNOW, THE BUILDING/STRUCTURAL
 REVIEWER WILL REVIEW SAID DOCUMENTS FOR ACTUAL WIND
 LOADS WHICH WILL BE REQUIRED TO SHOW EPA FOR PROPOSED
 FIXTURES.
 FBC 2004 140MPH. ETC.
  
 8) NOTE: PLEASE PROVIDE MINIMUM PHOTO-METRICS FOR
 EGRESS LIGHTING PER NFPA-101 7.8, 7.9
 PLEASE SEE NORMAL IS SHOWN, HOWEVER NEED TO SEE MIN
 UNDER EMERGENCY CONDITIONS.
  
 9) NOTE: PLEASE INDICATE THE REQUIRED MAIN AND GFP FOR
 THE 1600A MAIN.
 PLEASE SEE 230.70, 240.13 AND 230.95.
  
 10) PLEASE ALSO SEE POSSIBLE MISPRINT FOR 2B BREAKER
 WHICH IS BEING SHOWN AS 2225A'S.?
 FBC ADMINISTRATIVE SECTION 106.3.5.1.2.
  
 11) NOTE: PLEASE SEE 110.9, 240.13 AND PROVIDE ALL
 MINIMUM REQUIRED AIC RATINGS AND SELECTIVE COORDINATION
 FOR EQUIPMENT AS SHOWN. PLEASE SHOW DETAIL FOR
 EQUIPMENT.
  
 12) NOTE: PLEASE SEE 250.6, 250.24B AS AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT ON THE LINE SIDE OF THE MAIN.
 PLEASE KNOW THE EGC IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 13) NOTE: PLEASE INDICATE THE FEED-THRU LUGS ON EACH
 LP1 AND PP1, OR ARE THE SECONDARY SECTIONS FED BY OCP
 DEVICES FROM SECTIONS (1). ?
 240.4,310.16 ETC?
 106.1.2 FBC ADMIN SECT.
  
 14) NOTE: PLEASE PROVIDE A STRUCTURAL SUPPORT DETAIL
 FOR BOTH TRANSFORMERS.
 PLEASE KNOW THIS STRUCTURAL DETAIL WILL BE REVIEWED BY
 BUILDING REVIEWER.
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE THERE ARE SHEETS WHICH INDICATE
 NOTES, HOWEVER THOSE NOTES ARE ACTUALLY CROSSED OUT ON
 SHEETS FOR NOTES.??
 PLEASE CLARIFY AND CORRELATE THIS.
 FBC 106.1.2
  
 16) NOTE: PLEASE SEE FBC 11-4.28, 11-4.28.2 AND .3(4)
 WHICH REQUIRE A MIN OF 75 CANDELAS AT ALL AREAS AS
 STATED FOR ADA. PLEASE SEE MIN LEVELS STATED FOR ADA ON
 PLANS MENTIONS 15CD?
 PLEASE KNOW ALL OF THESE AREAS WILL BE TESTED FOR
 MINIMUM LEVELS, PLEASE BE SURE THE DEVICES AS SHOWN AND
 INSTALLED WILL MEET TESTED LEVELS. PLEASE ADJUST NOTES
 ON PLANS AT THIS TIME.
  
 17) NOTE: PLEASE ALSO SEE WITH RESPECT TO THE NOTE #16
 ABOVE , PLEASE SEE PLANS REFERENCE 2002 BOCA, FOR CODE.
 PLEASE ADJUST.
 2004 FBC.
  
 18) NOTE: PLEASE PROVIDE INFORMATION FOR CONVEYOR
 SYSTEM, PLEASE PROVIDE INFORMATION ON ALL LISTINGS FOR
 EQUIPMENT BRING INSTALLED.
 PLEASE PROVIDE SPECS ON THE MCC.
 110.3, 90.7.
 FBC 106.1.2
  
 19) NOTE: PLEASE PROVIDE LOAD CALCULATIONS FOR THE
 MCC1. COULD NOT LOCATE ANY ON PLANS?
 220.31, LARGEST MOTOR LOADS ETC.
 215.3, 230.42
 FBC 106.3.5.1.2
  
 20) NOTE: PLEASE SEE POSSIBLE BUILDING FIRE REVIEW
 NOTES AS TRANSFORMER/ AND ELECTRICAL EQUIPMENT APPEAR
 TO BE LOCATED IN AN EGRESS CORRIDOR. PLEASE SEE THIS
 MAY OR MAY NOT BE PERMITTED AS SHOWN? IF THIS IS A
 RATED CORRIDOR, PLEASE KNOW, THIS EQUIPMENT WILL MOST
 LIKELY BE REQUIRED TO BE RELOCATED.
  
 21) NOTE: PLEASE SEE PANEL NOTES MENTIONS "LOCK-OFF"
 BREAKERS, PLEASE KNOW THESE TYPE OF LOCK OFF DEVICES
 SHALL BE AN INTEGRAL PART OF THE BREAKER AND SHALL NOT
 BE REMOVABLE WITHOUT THE REMOVAL OF SAID BREAKER. 90.7,
 110.3, 90.4
  
 22) NOTE: PLEASE SEE SOME OTHER AREAS INDICATED AS
 "FUTURE" AT THIS TIME MAY AFFECT THE INSTALLATIONS OF
 SOME ELECTRICLA EQUIPMENT AND OTHER EQUIPMENT ON PLANS
 AS SHOWN. PLEASE SEE NEC 500, AND OTHER NFPA'S RELEVANT
 TO ANY OTHER POSSIBLE SCOPE OF WORK WHICH WILL BE
 DECLARED AS HAZARDOUS AT THIS TIME OR AT A LATER TIME.
  
 ** PLEASE KNOW AS THERE IS INFORMATION WHICH HAS NOT
 YET BEEN SUBMITTED FOR REVIEW, THERE MAY BE COMMENTS ON
 NEXT REVIEW WHICH ARE NOT STATED IN THESE REVIEW
 NOTES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
2006-10-23 06:46:18REVIEW IN PROGRESS
2006-10-22 19:46:04ONE SET IN ELEC FOR REVIEW.