Date |
Text |
2006-11-28 09:58:50 | ***********UNSAT ************* |
| |
| PUBLIX GENERATOR |
| 831 VILLAGE, #319 |
| |
| ** PLEASE SEE THE SAME PLANS AS PREVIOUSLY SUBMITTED |
| ARE SUBMITTED BACK WITH OUT ANY CHANGES. |
| |
| 1) NOTE:PLEASE SEE THE VALUE HAS BEEN ADJUSTED. |
| PLEASE SEE AN AMOUNT OF FEES DUE ARE $1975.80. |
| THIS IS DUE BEFORE PLANS CAN BE PICKED UP. |
| |
| 2) NOTE:PLEASE SEE NOTE FROM PERVIOUS REVIEW WITH |
| RESPECT TO THE EQUIPMENT SPECS. PLEASE SEE NONE WERE |
| SUBMITTED IN PERMIT APPLICATION PACKAGE. PLEASE SEE |
| NOTE BELOW WAS FROM PREVIOUS REVIEW. |
| THE EQUIPMENT ON THE PREVIOUS PROJECT HAS NOT BEEN |
| FINALIZED AND THERE IS STILL QUESTION ON THE |
| EQUIPMENT. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS.APS/ ATS |
| DO NOT INDICATE THE REQUIRED MEANS OF DISCONNECT AS |
| REQUIRED BY 230.76, 230.79, 225.31-39. |
| PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE |
| LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF |
| EQUIPMENT SUBMITTED. |
| THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR |
| PREVIOUS PROJECT. |
| NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON |
| ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT |
| IS ISSUED. |
| PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7, |
| 110.3 |
| |
| 3) NOTE: PLEASE SEE THE RELAY DEVICE AS BEING NOTED IN |
| THE RESPONSE LETTER IS NOT AN ACCEPTABLE MEANS OF OCP |
| AS NOTED IN THE RESPONSE LETTER. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE INDICATE THE OCP AT THE |
| GEN. PLEASE SEE 445.13 AS IT HAS COME TO OUR ATTENTION |
| ON A PREVIOUS PROJECT THAT THE GEN MAY NOT CONTAIN OCP |
| AND CAN NOT BE VERIFIED AT THIS TIME. |
| |
| 4) NOTE:PLEASE SUBMIT AND INDICATE ALL LOAD |
| CALCULATIONS OR HIGHEST DEMAND LOADS ON PLANS. MAY NOT |
| BE IN RESPONSE LETTER AS THE ENGINEER OF RECORD SHALL |
| SIGN, DATE AND SEAL INFORMATION PROVIDED. PLEASE ADJUST |
| PLANS AND INCLUDE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED FOR |
| REVIEW. PLEASE SUBMIT. |
| PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF |
| APPLICABLE. |
| 702.5, 220 |
| |
| 5) NOTE: PLEASE SEE FBC CHAPTER 27, AS THIS HAS NOT |
| BEEN REVISED TO INCLUDE AN EXCEPTION FOR EXCLUSION OF |
| OPTIONAL STAND-BY SYSTEMS. PLEASE SEE2002 NFPA-70, 2002 |
| NFPA-110. |
| PLEASE SEE PLANS SHALL INDICATE ALL RELEVANT CODES. ** |
| PREVIOUS REVIEW NOTE ** |
| PLEASE SEE PLANS SHALL INDICATE THE CURRENT CODES IN |
| EFFECT FOR INSTALLATION AS FOLLOWS. |
| PLEASE SEE FBC 2004 CHAPTER 27 FOR ADOPTED CODES |
| RELEVANT TO POWER GENERATORS. |
| |
| |
| 6) NOTE: PLEASE CLARIFY THE COMPLETE GROUNDING |
| ELECTRODE SYSTEM, PLEASE CLARIFY AND SHOW THE COLD |
| WATER PIPE, SPRINKLER ETC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE APS/ATS IS BECOMING THE NEW FIRST MEANS |
| OF DISCONNECT HOWEVER THE NEW GROUNDING ELECTRODE |
| SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER 250.50. |
| PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL |
| WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT. THESE |
| NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN |
| REQUIREMENTS. |
| PER 250.50,250.52, 250.104 |
| IF SLAB STEEL IS ONLY BEING BONDED THEN PLEASE |
| INDICATE. |
| PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND |
| BONDING FOR ALL AS ABOVE. |
| |
| 7) NOTE: PLEASE SEE RESPONSE NOW MENTIONS THIS UNIT |
| BEING A BI-FUEL UNIT, HOWEVER THE MANUFACTURE SPECS/CUT |
| SHEETS SUBMITTED WERE NOT CHANGED, INFORMATION FOR THIS |
| SYSTEM WAS NOT SUBMITTED AND GAS RISER INFORMATION WAS |
| NOT SUBMITTED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW, BASED ON A PREVIOUS PROJECT, IS THIS |
| UNIT GOING TO BE "BI-FUEL"?? |
| IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S). |
| 90.7, 110.3 |
| |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |