Plan Review Notes
Plan Review Notes For Permit 06090672
Permit Number 06090672
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-28 09:58:50***********UNSAT *************
  
 PUBLIX GENERATOR
 831 VILLAGE, #319
  
 ** PLEASE SEE THE SAME PLANS AS PREVIOUSLY SUBMITTED
 ARE SUBMITTED BACK WITH OUT ANY CHANGES.
  
 1) NOTE:PLEASE SEE THE VALUE HAS BEEN ADJUSTED.
 PLEASE SEE AN AMOUNT OF FEES DUE ARE $1975.80.
 THIS IS DUE BEFORE PLANS CAN BE PICKED UP.
  
 2) NOTE:PLEASE SEE NOTE FROM PERVIOUS REVIEW WITH
 RESPECT TO THE EQUIPMENT SPECS. PLEASE SEE NONE WERE
 SUBMITTED IN PERMIT APPLICATION PACKAGE. PLEASE SEE
 NOTE BELOW WAS FROM PREVIOUS REVIEW.
 THE EQUIPMENT ON THE PREVIOUS PROJECT HAS NOT BEEN
 FINALIZED AND THERE IS STILL QUESTION ON THE
 EQUIPMENT.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS.APS/ ATS
 DO NOT INDICATE THE REQUIRED MEANS OF DISCONNECT AS
 REQUIRED BY 230.76, 230.79, 225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE
 LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF
 EQUIPMENT SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR
 PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON
 ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT
 IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7,
 110.3
  
 3) NOTE: PLEASE SEE THE RELAY DEVICE AS BEING NOTED IN
 THE RESPONSE LETTER IS NOT AN ACCEPTABLE MEANS OF OCP
 AS NOTED IN THE RESPONSE LETTER.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICATE THE OCP AT THE
 GEN. PLEASE SEE 445.13 AS IT HAS COME TO OUR ATTENTION
 ON A PREVIOUS PROJECT THAT THE GEN MAY NOT CONTAIN OCP
 AND CAN NOT BE VERIFIED AT THIS TIME.
  
 4) NOTE:PLEASE SUBMIT AND INDICATE ALL LOAD
 CALCULATIONS OR HIGHEST DEMAND LOADS ON PLANS. MAY NOT
 BE IN RESPONSE LETTER AS THE ENGINEER OF RECORD SHALL
 SIGN, DATE AND SEAL INFORMATION PROVIDED. PLEASE ADJUST
 PLANS AND INCLUDE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF
 APPLICABLE.
 702.5, 220
  
 5) NOTE: PLEASE SEE FBC CHAPTER 27, AS THIS HAS NOT
 BEEN REVISED TO INCLUDE AN EXCEPTION FOR EXCLUSION OF
 OPTIONAL STAND-BY SYSTEMS. PLEASE SEE2002 NFPA-70, 2002
 NFPA-110.
 PLEASE SEE PLANS SHALL INDICATE ALL RELEVANT CODES. **
 PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL INDICATE THE CURRENT CODES IN
 EFFECT FOR INSTALLATION AS FOLLOWS.
 PLEASE SEE FBC 2004 CHAPTER 27 FOR ADOPTED CODES
 RELEVANT TO POWER GENERATORS.
  
  
 6) NOTE: PLEASE CLARIFY THE COMPLETE GROUNDING
 ELECTRODE SYSTEM, PLEASE CLARIFY AND SHOW THE COLD
 WATER PIPE, SPRINKLER ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE APS/ATS IS BECOMING THE NEW FIRST MEANS
 OF DISCONNECT HOWEVER THE NEW GROUNDING ELECTRODE
 SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL
 WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT. THESE
 NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN
 REQUIREMENTS.
 PER 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED THEN PLEASE
 INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND
 BONDING FOR ALL AS ABOVE.
  
 7) NOTE: PLEASE SEE RESPONSE NOW MENTIONS THIS UNIT
 BEING A BI-FUEL UNIT, HOWEVER THE MANUFACTURE SPECS/CUT
 SHEETS SUBMITTED WERE NOT CHANGED, INFORMATION FOR THIS
 SYSTEM WAS NOT SUBMITTED AND GAS RISER INFORMATION WAS
 NOT SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, BASED ON A PREVIOUS PROJECT, IS THIS
 UNIT GOING TO BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S).
 90.7, 110.3
  
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]