2006-10-06 00:00:00 | ***********UNSAT ************* |
| |
| PUBLIX GENERATOR |
| 831 VILLAGE, #319 |
| |
| 1) NOTE:PLEASE ADJUST VALUE FOR |
| COMPLETE SCOPE OF WORK BEING APPLIED |
| FOR. THE VALUE OF $10K ON PERMIT |
| APPLICATION AUBMITTED IS EXTREMELY LOW |
| PLEASE KNOW, THAT VALUE SHALL BE |
| ALL LABOR AND MATERIALS EVEN IF |
| MATERIALS ARE OWNER SUPPLIED. PLEASE SEE |
| VALUE FOR LABOR AND INSTALLATION IS WAY |
| LOW FOR SCOPE PF WORK. PLEASE SEE FBC |
| 2004, ADMINISTRATIVE CODE SECTION 108.3 |
| AS ADOPTED BY THE CITY OF WEST PALM |
| BEACH. |
| PLEASE KNOW, A VALUE WILL BE ASSESSED |
| USING THE MARSHALL'S& SWIFT GUIDE. |
| PLEASE KNOW, UNDER CONTRACTING LAWS AND |
| RULES SET UP AND ADOPTED INTO FLORIDA |
| STATUES, 489, FBC ADMINISTRATIVE SECTION |
| 105.5.1 ANY INFORMATION PROVIDED ON |
| OFFICAL PERMIT APPLICATION IF KNOWINGLY |
| BEING FALSIFIED CAN VOID/REVOKE SUCH |
| PERMIT/ APPLICATION. |
| |
| 2) NOTE: PLEASE KNOW, ANY SYSTEMS |
| LOCATED IN A FLOOD ZONE "A" WILL BE |
| REQUIRED TO BE MOUNTED AT A MIN OF 6" |
| ABOVE BFE. PLEASE SEE BUILDING REVIEW |
| COMMENTS. |
| |
| 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE |
| CUT SHEETS.APS/ ATS DO NOT INDICATE |
| THE REQUIRED MEANS OF DISCONNECT AS |
| REQUIRED BY 230.76,230.79,225.31-39. |
| PLEASE SEE A MANUAL MEANS OF DISCONNECT |
| COULD NOT BE LOCATED RATED FOR THE LOAD |
| SERVED ON THE OUTSIDE OF EQUIPMENT |
| SUBMITTED. |
| THIS WAS NEVER VERIFIED FROM PREVIOUS |
| PERMIT PULLED FOR PREVIOUS PROJECT. |
| NO PERMITS WILL BE RELEASED UNLESS THIS |
| IS VERIFIED ON ALL SUBMITTED SPECS AND |
| PLANS SUBMITTED BEFORE PERMIT IS ISSUED. |
| PLEASE SEE ALL EQUIPMENT SHALL BE LISTED |
| FOR USE.90.7, 110.3 |
| |
| 4) NOTE: PLEASE INDICATE THE OCP AT THE |
| GEN. PLEASE SEE 445.13 AS IT HAS COME TO |
| OUR ATTENTION ON A PREVIOUS PROJECT THAT |
| THE GEN MAY NOT CONTAIN OCP AND CAN NOT |
| BE VERIFIED AT THIS TIME. |
| |
| 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS |
| WERE SUBMITTED FOR REVIEW. PLEASE |
| SUBMIT. |
| PLEASE SUBMIT AND INDICATE ANY LOAD |
| SHEDDING DETAILS IF APPLICABLE. |
| 702.5, 220 |
| |
| 6) NOTE: PLEASE PROVIDE INFORMATION IF |
| THE GEN WILL BE FEEDING ANY "LEGALLY |
| REQUIRED STAND-BY SYSTEMS. |
| |
| |
| 7) NOTE:PLEASE SEE PLANS SHALL |
| INDICATE THE CURRENT CODES IN EFFECT FOR INSTALLATION |
| AS FOLLOWS. |
| PLEASE SEE FBC 2004 CHAPTER 27FOR |
| ADOPTED CODES RELEVANT TO POWER |
| GENERATORS. |
| 2002 NFPA-70, 2002 NFPA-110. |
| |
| 8) NOTE: PLEASE EXPLAIN, NOTE WHICH |
| MENTIONS TO SET THE OCP ABOVE THE |
| EXISTING MAIN ON E-1.??? |
| |
| 9) NOTE: PLEASE SEE THE APS/ATS IS |
| BECOMING THE NEW FIRST MEANS OF |
| DISCONNECT HOWEVER THE NEW GROUNDING |
| ELECTRODE SYSTEMS DOES NOT SEEM TO BE |
| COMPLETE AS PER 250.50. |
| PLEASE SEE GROUNDING DETAIL MENTIONS NEW |
| SLAB STEEL WHICH IS OK, HOWEVER PLEASE |
| INDICATE ATTACHMENT. |
| THESE NEW SLAB/STEEL ATTACHMENTS DO NOT |
| MEET THE MIN REQUIREMENTS. PER |
| 250.50,250.52, 250.104 |
| IF SLAB STEEL IS ONLY BEING BONDED , |
| THEN PLEASE INDICATE. |
| PLEASE COMPLETE GROUNDING ELECTRODE |
| SYSTEM(S) AND BONDING FOR ALL AS ABOVE. |
| |
| 10) NOTE: |
| |
| 11) NOTE: PLEASE SEE SETS OF CONDUITS |
| AND FEEDERS DO NOT SEEM TO INDICATE |
| THEW NEW REQUIRED "EQUIPMENT GROUNDING |
| CONDUCTOR" TO THE EXISITING MAINS. THESE |
| ARE NO LONGER THE FIRST MEANS OF |
| DISCONNECT. |
| PER 250.110,250.122,250.24B |
| 215.5 |
| |
| |
| 12) NOTE:PLEASE KNOW, BASED ON A |
| PREVIOUS PROJECT, IS THIS UNIT GOING TO |
| BE BE "BI-FUEL"?? |
| IF SO, SUBMIT ALL INFORMATION AND SPECS |
| ON UNIT(S). |
| 90.7, 110.3 |
| |
| |
| ** PLEASE KNOW, AS MUCH INFORMATION WAS |
| NOT SUBMITTED, A COMPLETE REVIEW COULD |
| NOT BE DONE. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |