Plan Review Notes
Plan Review Notes For Permit 06090672
Permit Number 06090672
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-06 00:00:00***********UNSAT *************
  
 PUBLIX GENERATOR
 831 VILLAGE, #319
  
 1) NOTE:PLEASE ADJUST VALUE FOR
 COMPLETE SCOPE OF WORK BEING APPLIED
 FOR. THE VALUE OF $10K ON PERMIT
 APPLICATION AUBMITTED IS EXTREMELY LOW
 PLEASE KNOW, THAT VALUE SHALL BE
 ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED. PLEASE SEE
 VALUE FOR LABOR AND INSTALLATION IS WAY
 LOW FOR SCOPE PF WORK. PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
 PLEASE KNOW, A VALUE WILL BE ASSESSED
 USING THE MARSHALL'S& SWIFT GUIDE.
 PLEASE KNOW, UNDER CONTRACTING LAWS AND
 RULES SET UP AND ADOPTED INTO FLORIDA
 STATUES, 489, FBC ADMINISTRATIVE SECTION
 105.5.1 ANY INFORMATION PROVIDED ON
 OFFICAL PERMIT APPLICATION IF KNOWINGLY
 BEING FALSIFIED CAN VOID/REVOKE SUCH
 PERMIT/ APPLICATION.
  
 2) NOTE: PLEASE KNOW, ANY SYSTEMS
 LOCATED IN A FLOOD ZONE "A" WILL BE
 REQUIRED TO BE MOUNTED AT A MIN OF 6"
 ABOVE BFE. PLEASE SEE BUILDING REVIEW
 COMMENTS.
  
 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE
 CUT SHEETS.APS/ ATS DO NOT INDICATE
 THE REQUIRED MEANS OF DISCONNECT AS
 REQUIRED BY 230.76,230.79,225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT
 COULD NOT BE LOCATED RATED FOR THE LOAD
 SERVED ON THE OUTSIDE OF EQUIPMENT
 SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS
 PERMIT PULLED FOR PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS
 IS VERIFIED ON ALL SUBMITTED SPECS AND
 PLANS SUBMITTED BEFORE PERMIT IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED
 FOR USE.90.7, 110.3
  
 4) NOTE: PLEASE INDICATE THE OCP AT THE
 GEN. PLEASE SEE 445.13 AS IT HAS COME TO
 OUR ATTENTION ON A PREVIOUS PROJECT THAT
 THE GEN MAY NOT CONTAIN OCP AND CAN NOT
 BE VERIFIED AT THIS TIME.
  
 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD
 SHEDDING DETAILS IF APPLICABLE.
 702.5, 220
  
 6) NOTE: PLEASE PROVIDE INFORMATION IF
 THE GEN WILL BE FEEDING ANY "LEGALLY
 REQUIRED STAND-BY SYSTEMS.
  
  
 7) NOTE:PLEASE SEE PLANS SHALL
 INDICATE THE CURRENT CODES IN EFFECT FOR INSTALLATION
 AS FOLLOWS.
 PLEASE SEE FBC 2004 CHAPTER 27FOR
 ADOPTED CODES RELEVANT TO POWER
 GENERATORS.
 2002 NFPA-70, 2002 NFPA-110.
  
 8) NOTE: PLEASE EXPLAIN, NOTE WHICH
 MENTIONS TO SET THE OCP ABOVE THE
 EXISTING MAIN ON E-1.???
  
 9) NOTE: PLEASE SEE THE APS/ATS IS
 BECOMING THE NEW FIRST MEANS OF
 DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOES NOT SEEM TO BE
 COMPLETE AS PER 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW
 SLAB STEEL WHICH IS OK, HOWEVER PLEASE
 INDICATE ATTACHMENT.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT
 MEET THE MIN REQUIREMENTS. PER
 250.50,250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED ,
 THEN PLEASE INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE
 SYSTEM(S) AND BONDING FOR ALL AS ABOVE.
  
 10) NOTE:
  
 11) NOTE: PLEASE SEE SETS OF CONDUITS
 AND FEEDERS DO NOT SEEM TO INDICATE
 THEW NEW REQUIRED "EQUIPMENT GROUNDING
 CONDUCTOR" TO THE EXISITING MAINS. THESE
 ARE NO LONGER THE FIRST MEANS OF
 DISCONNECT.
 PER 250.110,250.122,250.24B
 215.5
  
  
 12) NOTE:PLEASE KNOW, BASED ON A
 PREVIOUS PROJECT, IS THIS UNIT GOING TO
 BE BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS
 ON UNIT(S).
 90.7, 110.3
  
  
 ** PLEASE KNOW, AS MUCH INFORMATION WAS
 NOT SUBMITTED, A COMPLETE REVIEW COULD
 NOT BE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW