Plan Review Notes For Permit 06090670 |
Permit Number |
06090670 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-12-13 11:41:49 | DENIED: | | 1.PLANS NEED APPROVAL BY PALM BEACH COUNTY | | ENVIRONMENTAL DEPARTMENT FOR STORAGE TANK COMPLIANCE. | | THIS AGENCY IS LOCATED AT: | | | | 2300 N JOG ROAD | | (4TH FLOOR) | | WEST PALM BEACH, FL33411 | | PLEASE RE-SUBMIT TO THE CITY OF WEST BEACH CONSTRUCTION | | SERVICES DEPARTMENT AFTER APPROVAL BY DERM. | | | | 3.PLAN SHEET E4 INDICATES THE GENERATOR AS BEING 4' | | 6" FROM A DOOR, PER 2004 FMC 401.5.1 EXHAUST SHALL | | TERMINATE A MINIMUM OF 10 FT FROM FRESH AIR INTAKES, | | DOORS, WINDOWS, ETC.PLEASE INDICATE LOCATION OF THE | | EXHAUST FROM THE GENERATOR. | | | | 4.PLAN SHEET SD1 THE "SPECIAL INSTRUCTIONS" INDICATE | | MOUNT UNIT AND INSTALL FUEL LINES.WILL THIS BE DONE | | AT THE JOB LOCATION OR AT THE FACTORY?PLEASE INDICATE | | IF ANY FUEL PIPING IS TO BE INSTALLED REMOTE TO THE | | GENERATOR. | | | | 5.PLEASE NOTE, THE PADS THAT ALL EQUIPMENT WILL BE | | INSTALLED ON SHALL MEET THE CITY'S REQUIREMENT OF 6" | | ABOVE THE BASE FLOOD ELEVATION.CITY CODE SEC. 94-546 | | (3) (B) (2). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|