2008-08-26 14:49:47** EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED FROM NEW
 MAINS TO EXISTING SWB. THERE IS NO WAY TO GUARANTEE NO
 METALLIC PATHS BETWEEN BUILDIGN AND EQUIPMENT SUCH AS
 PHONE, CABLE, PIPING ETC.
 NEUTRALS SHALL BE SEPARATED AT THE EXISITNG SERVICE
 LOCATION.
 250.32.
  