2008-04-04 14:34:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 9/6/08 NOTE #1. THE
 GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE TANK
 BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE
 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM
 A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN SHOW
 THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE, PLEASE
 CORRECT.
  