2007-09-06 14:40:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AT TIME OF LAST REVIEW I HAD MISSED THAT THIS
 GENERATOR HAD A 1,000 GALLON DIESEL FUEL STORAGE TANK
 BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE
 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM
 PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLAN PAGE
 E3 SHOWS THE TANK 10'-11" FROM THE PROPERTY LINE,
 PLEASE CORRECT.
  