2008-04-04 14:39:19 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) THE GENERATOR HAS A 1,000 GALLON DIESEL FUEL STORAGE | | TANK BELOW IT AND NEEDS TO COMPLY WITH NFPA 30 TABLE | | 4.3.2.1.1(B) WHICH REQUIRES THE TANK TO BE 15 FEET FROM | | A PROPERTY LINE THAT IS OR CAN BE BUILT UPON. PLANS | | SHOW THE TANK IS 10'-11" FROM THE WEST PROPERTY LINE, | | PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|