2006-10-19 15:39:56UNSAT
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1.
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW:
  
 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT (1ST AND 2ND STAGE REGULATORS) TO VERIFY
 COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 3. PLEASE SUBMIT MANUFACTURER CUT SHEETS AND
 INSTALLATION INSTRUCTIONS OF GENERATOR THAT VERIFY BTU
 LOAD AND RECOMMENDATION OF MINIMUM CLEARENCES TO
 STRUCTURES.
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES ON TWO COPIES
 OF SURVEY.
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 5. PROVIDE NOTICE OF COMMENCEMENT RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 END OF COMMENTS:
  