2006-10-18 07:57:36 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR , INCLUDE RECOMMENDATION REGARDING
 CLEARANCES.
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH
  
 4} PROVIDE A CALCULATION FOR THE LOAD BEING SERVED BY
 THE GENERATOR.
  
 5} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 6} PROVIDE A RISER DIAGRAM SHOWING ELECTRICAL
 CONNECTION OF ALL SERVICE AND GENERATOR EQUIPMENT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.