Plan Review Notes
Plan Review Notes For Permit 06090582
Permit Number 06090582
Review Stop M
Sequence Number 1
Notes
Date Text
2006-09-18 00:00:00*** DENIED ***
 1) MANUAL J CAL'S ARE CALLING FOR 23,867
 SENSIBLE BTU'S, THE PLANS ARE CALLING
 FOR 35,000 SENSIBLE BTU'S, THE PLANS CAN
 ONLY CALL FOR 20% MORE THAN THE MANUAL J
 CAL'S, PER 2005 FBC CH. 13
 607.1.ABC.1.1, PLEASE CORRECT.
  
 2) PLEASE SUBMIT A SIGNED PROPOSAL OR
 AJUST THE VALUE ON THE PERMIT
 APPLICATION, AS THE VALUE ON THE PERMIT
 APPLICATION APPEARS LOW FOR THE WORK TO
 BE DONE, OR THE CITY WPB WILL AJUST THE
 VALUE USING MARSHALL & SWIFT ESTIMATOR,
 PER 2004 CITY WPB AMEND. 108.3 .
  
 3) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE ARRANGE FOR PERMIT # 06071027
 TO BE VOIDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.