Plan Review Notes For Permit 06090552
Permit Number 06090552
Review Stop ENG
Sequence Number 2
Notes
Date Text
2006-11-02 14:26:06FAILED FOR FOLLOWING REASONS:
  
 PLEASE ANSWER EACH ITEMS EXPLAINED ON 10/05/06,
  
 FOR EXAMPLE,POLLUTION PREVENTION PLANS, SILT FENCE
 AROUND SITEMUST BE DRAWN BY CAD OR DRAWN TO SCALE
 WITH SYMBOL EXPLAINED IN THE DRAWING, WHAT IS THAT
 SYMBOL FOR SILT FENCE AROUND SITE, IF ANY?ALSO,
 PLEASE DRAW DETAILS OF SILT, SILT POLES, SILT FENCE
 HEIGHT,CLOTHS, ETC., NEED COMPLETE DETAILS &
 DESCRIPTION OF THE SILT FENCE ON THE DRAWINGS, CALLED
 POLLUTION PREVENTION PLAN & DETAILS ON THE DRAWINGS.
 CONSTRUCTION WORKERS DO NOT HAVE ACCESS TO READ SECTION
 01000, GENERAL REQUIREMENTS, SUBSECTION 1.04 PROVISION
 ETC. ETC., AS YOU SAID IN YOURRESPONCE LETTER OF(NO
 DATE), WHICH IS NOT ACCEPTABLE TO US.
  
 ALL CITY OF WPB STANDARDS & DETAILS (WHICH WE ASKED ON
 10/05/06) MUST BE DRAWN ON THE DRAWINGS.
  
 ALSO, PLEASE PROVIDETOTAL SITE AREA, PERVIOUS AREA,
 IMPERVIOUS AREA ON THE DRAWING, NEED FULL EXPLANATION.
  
  
 RASIK CHOKSHI 805-6723