Plan Review Notes
Plan Review Notes For Permit 06090488
Permit Number 06090488
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-29 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED.INCREASE THE VALUE AT THE
 COUNTER AND RESUBMIT.
  
 2} PROVIDE EMERGENCY ILLUMINATION PER
 NFPA-101 7.8 (2003), AND CIRCUITED PER
 700.12 NEC. INDICATE SAME ON PLANS.
  
 3} INDICATE COMPLIANCE WITH 210.63 FOR
 ROOFTOP EQUIPMENT.
  
 4} PROVIDE PANEL SCHEDULES FOR PANELS
 "A" AND "B".
  
 5} INDICATE COMPLIANCE WITH CHAPTER 13
 OF THE FLORIDA BLDG CODE. 13.413,
 13.414, 13.415. SHOW TIME CLOCK AND
 OCCUPANCY SENSOR LOCATIONS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]