Plan Review Notes
Plan Review Notes For Permit 06090474
Permit Number 06090474
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-21 00:00:00***DENIED***
  
 1) PLANS SHOW EXISTING STROBE LIGHTS.
 WHAT ARE THEY CONNECTED TO? IF PART OF A
 FIRE ALARM SYSTEM OR EXISTING STAND
 ALONE AC UNIT DUCTS, PLEASE INDICATE AND
 ALSO SHOW IF THEY INCLUDE AUDIBILITY.
  
 2) IS THERE AN EXISTING FIRE SPRINKLER
 SYSTEM, AND IF SO WILL THIS WORK HAVE AN
 IMPACT ON SUCH SYSTEM?
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722