Plan Review Notes For Permit 06090474 |
Permit Number |
06090474 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-21 00:00:00 | ***DENIED*** | | | | 1) PLANS SHOW EXISTING STROBE LIGHTS. | | WHAT ARE THEY CONNECTED TO? IF PART OF A | | FIRE ALARM SYSTEM OR EXISTING STAND | | ALONE AC UNIT DUCTS, PLEASE INDICATE AND | | ALSO SHOW IF THEY INCLUDE AUDIBILITY. | | | | 2) IS THERE AN EXISTING FIRE SPRINKLER | | SYSTEM, AND IF SO WILL THIS WORK HAVE AN | | IMPACT ON SUCH SYSTEM? | | | | 3) CONSTRUCTION, ALTERATION AND | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|