2006-09-20 00:00:00 | **********UNSAT ************* |
| |
| 1) NOTE: PLEASE INDICATE ALL CIRCUITING |
| ON PLANS AND CORRELATE WITH A PANEL |
| SCHEDULE TO BE PROVIDED. |
| 408.4, 310.16,240.4 |
| FBC 106.1.2 |
| |
| 2) NOTE: PLEASE CLARIFY THE NEW OR |
| EXISTING LIGHTING LEVELS FOR THE STAIRS |
| WAYS FOR A MIN OF 10FT CANDLES UDNER |
| NORMAL AND 1FT MIN UNDER EMERGENCY. |
| 7.8.1.3, 7.9.2.2 |
| PLEASE ALSO INDICATE SOME SORT OF EM |
| BATTERY BACK UP FIXTURE REQUIRED FOR MIN |
| LTS. |
| |
| 3) NOTE: PLEASE SEE BUILDING REVIEW |
| COMMENTS AS TO ANY COMMENTS WHIHC MAY |
| AFFECT THE ELECTRICAL DESIGN. |
| |
| 4) NOTE: PLEASE SEE ITEMS ON NOTES WHICH |
| ARE NOT ON PLANS. SD'S ETC. |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE THAT ALL PLANS ARE |
| REQUIRED TO CONTAIN THE PRINTED NAME, |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| PLANS AND DESIGN. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| WITH ALL OCP AND CONDUCTOR SIZES. PLEASE |
| SEE THAT SOME ITEMS ARE SHOWN , BUT NOT |
| CLEAR WHAT THEY ARE FEEDING. (50A |
| CIRCUIT, ETC |
| ALL AREAS /ROOMS ARE TO BE SPECIFIC . |
| 240.4,310.16,408.4 |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |