Plan Review Notes For Permit 06090474 |
Permit Number |
06090474 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-19 00:00:00 | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) 505.2 AREA LIMITATION. | | THE AGGREGATE AREA OF A MEZZANINE OR | | MEZZANINES WITHIN A ROOM SHALL NOT | | EXCEED ONE-THIRD OF THE AREA OF THAT | | ROOM OR SPACE IN WHICH THEY ARE LOCATED. | | THE ENCLOSED PORTIONS OF ROOMS SHALL NOT | | BE INCLUDED IN A DETERMINATION OF THE | | SIZE OF THE ROOM IN WHICH THE MEZZANINE | | IS LOCATED. IN DETERMINING THE ALLOWABLE | | MEZZANINE AREA, THE AREA OF THE | | MEZZANINE SHALL NOT BE INCLUDED IN THE | | AREA OF THE ROOM. SUBMIT CALCULATIONS | | INDICATING THAT THE AREA OF THE | | MEZZANINE DOES NOT EXCEED ONE-THIRD OF | | THE FLOOR AREA OF THE ROOM IN WHICH IT | | IS LOCATED, NOT INCLUDING THE ENCLOSED | | AREAS OF THE FIRST FLOOR (INCLUDING NEW | | ENCLOSURE AT OVERHEAD DOOR). | | | | 3) THE EXTERIOR OVERHEAD DOOR IS | | REQUIRED TO REMAIN. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|