Plan Review Notes For Permit 06090459 |
Permit Number |
06090459 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-12 18:20:20 | BUILDING PLAN REVIEW | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1) 2004 FL. BLD CODE 1603.1.4 THE | | FOLLOWING INFORMATION RELATED TO WIND | | SHALL BE SHOWN ON THE CONSTRUCTION | | DRAWINGS, | | 1)- BASIC WIND SPEED, MPH | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | CATEGORY | | 3)- WIND EXPOSURE | | 4)- INTERNAL PRESSURE COEFFICIENT, | | 5)- COMPONENTS & CLADDING, THE DESIGN | | WIND PRESSURES IN TERMS OF PSF. | | | | 2)PROVIDE CLEAR AND DETAIL INSTRUCTIONS (PHOTOS)FOR | | THE REMOVAL OF THE AWNINGS DURING PERIODS OF 75MPH | | WINDS VELOCITY, OR THE AWNINGS SHALL BE DESIGN TO | | WITH-STAND WINDS OF 140MPH WITH THEFABRIC IN PLACE | | AND THE FRAME ATTATCHED TO THE BUILDING. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 | | | | | | | | | | | | | | | | |
|