Plan Review Notes
Plan Review Notes For Permit 06090449
Permit Number 06090449
Review Stop P
Sequence Number 3
Notes
Date Text
2007-03-09 08:01:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE FLORIDA
 STATUTES
 NFPA 99C 2002
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER
 FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT
 MANUF. SPECIFICATION. SECTION 611.1.
 ****NO RESPONSE - NOT ADDRESSED.
 ******RESPONSE NOTED, AND INDICATES THE FILTERED WATER
 SYSTEM HAS BEEN DELETED, BUT THE PLANS STILL SHOW
 "FILTERED C.W. TYP. BRANCH"ON THE VAC. AIR & FILTERED
 WATER DIAGRAM. PLEASE CLARIFY. SECTION 106.1.1.
  
 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE
 WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER
 HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM
 SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE
 COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES
 ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR
 4.5.2.1.3(B) FOR THE VACUUM SYSTEM.
 ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN,
 AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES
 REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER
 RISER ISOMETRIC.
 ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE" NEAR THE
 FIXTURES, NOT IN THE CEILING. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
  
 *************NEW COMMENT*************
  
 1B. OK
  
  
 REVIEW BY KEN STEVENS